RADIANT-IB · 208V three-phase UPS
RADIB100-1X20 RADIANT-IB 20 kVA, 208V three-phase UPS
The AEC RADIANT-IB RADIB100-1X20 is a 20 kVA / 20 kW online double-conversion UPS for 208 V three-phase loads, built on one 20 kVA power module, with VRLA batteries on internal trays. Kept at 80 % of its rating, it carries loads up to 16 kW.
One of the frame's five module slots is fitted, so no module is spare at this size; four more modules take the frame to 100 kVA. As configured it weighs 1,998 lb (906.3 kg) net.
Series picture.
Drag to turnIn 3D
Look around the RADIB100-1X20
The turntable shows the 100 kVA · 5 modules configuration; the full 3D view opens on this model.
The same on every RADIANT-IB:The RADIANT-IB display
Load by load
The RADIB100-1X20 at 25, 50, 75 and 100 % load.
Its 20 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current per phase, at 208 V | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|
| 25 % of the RADIB100-1X20, 5.0 kW | 13.9 A per phase | 92.7 % efficient | 394 W of heat | 1,340 BTU/h to cool |
| 50 % of the RADIB100-1X20, 10 kW | 27.8 A per phase | 93.9 % efficient | 650 W of heat | 2,220 BTU/h to cool |
| 75 % of the RADIB100-1X20, 15 kW | 41.6 A per phase | 94.0 % efficient | 957 W of heat | 3,270 BTU/h to cool |
| 100 % of the RADIB100-1X20, 20 kW | 55.5 A per phase | 93.8 % efficient | 1.3 kW of heat | 4,510 BTU/h to cool |
Current = kVA × load ÷ (√3 × volts).
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the RADIB100-1X20 at your load?
The RADIB100-1X20 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What is the RADIB100-1X20?
The code RADIB100-1X20 orders these catalog items, shipped in 26 cartons:
- 1 × RADIB-FRAME: 100 kVA frame, without power modules, 23.6 × 39.4 × 78.7 in (600 × 1,000 × 2,000 mm)
- 1 × RADIB-PWR-20: 20 kVA hot-swappable power module, 44 lb (20 kg)
- 24 × RADIB-BATTR-10x9A: battery tray of 10 × 12 V 9 Ah VRLA blocks, 63.5 lb (28.8 kg) each
- Architecture: 1 × 20 kVA hot-swappable power module in a 100 kVA / 100 kW frame (scalable to 5 modules / 100 kVA); parallel up to 3 cabinets.
The lines every RADIANT-IB shares, from technology to warranty, are in the RADIANT-IB key facts and in the datasheet below.
1 × 20 kVA power modules fitted in a 5-slot frame: 4 free slots to grow or add redundancy.
Size and floor
How big it is
23.6" W × 39.3" D × 78.7" H (599 × 998 × 1,999 mm); 1,998 lb (906.3 kg) net.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
The RADIB100-1X20 takes the clearances, wiring, cable entry and breakers of every RADIANT-IB model, from its AEC US user manual: see them on the RADIANT-IB page.
Place the RADIB100-1X20 in your room, to the inch, with Room fit
Datasheet
RADIB100-1X20 datasheet.
The RADIB100-1X20 in the AEC 2026 catalog, figure by figure. Compare it with every RADIANT-IB model.
| Parameter | RADIB100-1X20 |
|---|---|
| Power | |
| Rated power (kVA) | 20 |
| Active power (kW) | 20 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 208 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X |
| Efficiency, up to | 94% |
| Battery DC bus | 240 V DC |
| Battery and runtime | |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | Internal Tray System |
| Runtime at 50 % load | 85 min |
| Runtime at 100 % load | 32 min |
| Mechanical | |
| Form factor | Modular |
| Dimensions W × D × H | 23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm) |
| Net weight | 1,998 lb (906.3 kg) |
| Footprint | 6.4 ft² (0.60 m²) |
| Shipping | |
| Cartons | 26 |
| Common to every RADIANT-IB | |
| Technology | 3-level IGBT; unity power factor (kVA = kW); 40 A settable charger |
| Battery, RADIB100-1X20 | internal hot-swappable VRLA, up to 240 × 12V 9Ah (240 pcs) |
| Display | 7-inch color touchscreen |
| Comms | RS-232, EPO and USB, standard |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The RADIANT-IB documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
Quick answers
RADIB100-1X20: what people ask
What is the output current of the RADIB100-1X20?
55.5 A per phase at full load: 20 kVA ÷ (√3 × 208 V). Size the input breaker and the cables of the RADIB100-1X20 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the RADIB100-1X20 give off?
About 1.3 kW, 4,510 BTU/h, at full load, where it is 93.8% efficient. Plan the room's cooling for a little more than that: the RADIB100-1X20 is less efficient at part load and while its battery recharges.
Will the RADIB100-1X20 fit through a standard door?
Yes: 23.6 in (599 mm) across its narrow side and 78.7 in (1,999 mm) high, it passes a standard 36 × 80-inch door upright, with little to spare in height. On the way in, check corridors, elevators and the floor load of the RADIB100-1X20 (size section above).
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
RADIANT-IB
Other RADIANT-IB models
By power, the RADIB100-1X20 is the smallest in the RADIANT-IB series, which runs from 20 to 100 kVA. One size up is the RADIB100-2X20 (20 kVA more and 44 lb heavier).
Every RADIANT-IB model side by side (5)
| Model | Power | Power against this model | Net weight | Weight against this model | Runtime at 50 % load |
|---|---|---|---|---|---|
| RADIB100-1X20 | 20 kVA | this page | 1,998 lb | this page | 85 min at 50 % load |
| RADIB100-2X20 | 40 kVA | 20 kVA more | 2,042 lb | 44 lb heavier | 32 min at 50 % load |
| RADIB100-3X20 | 60 kVA | 40 kVA more | 2,086 lb | 88 lb heavier | 21.5 min at 50 % load |
| RADIB100-4X20 | 80 kVA | 60 kVA more | 2,130 lb | 132 lb heavier | 14 min at 50 % load |
| RADIB100-5X20 | 100 kVA | 80 kVA more | 2,174 lb | 176 lb heavier | 12 min at 50 % load |
The RADIB100-1X20 for your project