RADIANT · 208V three-phase UPS
RAD90-1X15 RADIANT 15 kVA, 208V three-phase UPS
The AEC RADIANT RAD90-1X15 is a 15 kVA / 15 kW online double-conversion UPS for 208 V three-phase loads, built on one 15 kVA power module, with external battery cabinets. Kept at 80 % of its rating, it carries loads up to 12 kW.
One of the frame's six module slots is fitted, so no module is spare at this size; five more modules take the frame to 90 kVA. As configured it weighs 238 lb (108 kg) net.
Series picture.
Drag to turnIn 3D
Look around the RAD90-1X15
The turntable shows the 90 kVA · 6 modules configuration; the full 3D view opens on this model.
The same on every RADIANT:The RADIANT display
Load by load
The RAD90-1X15 at 25, 50, 75 and 100 % load.
Its 15 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current per phase, at 208 V | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|
| 25 % of the RAD90-1X15, 3.8 kW | 10.4 A per phase | 92.8 % efficient | 291 W of heat | 990 BTU/h to cool |
| 50 % of the RAD90-1X15, 7.5 kW | 20.8 A per phase | 93.9 % efficient | 487 W of heat | 1,660 BTU/h to cool |
| 75 % of the RAD90-1X15, 11 kW | 31.2 A per phase | 94.0 % efficient | 718 W of heat | 2,450 BTU/h to cool |
| 100 % of the RAD90-1X15, 15 kW | 41.6 A per phase | 93.8 % efficient | 991 W of heat | 3,380 BTU/h to cool |
Current = kVA × load ÷ (√3 × volts).
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the RAD90-1X15 at your load?
The RAD90-1X15 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What is the RAD90-1X15?
The code RAD90-1X15 orders these catalog items:
- 1 × RAD90-FRAME: 90 kVA frame, without power modules, 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm)
- 1 × RAD-PWR-15: 15 kVA hot-swappable power module, 30.5 lb (13.9 kg)
- Architecture: 1 × 15 kVA hot-swappable power module in a 90 kVA / 90 kW frame, 6 slots with 4 breakers (scalable to 6 modules / 90 kVA); parallel up to 4 frames.
The lines every RADIANT shares, from technology to warranty, are in the RADIANT key facts and in the datasheet below.
1 × 15 kVA power modules fitted in a 6-slot frame: 5 free slots to grow or add redundancy.
Size and floor
How big it is
17.4" W × 33.1" D × 59.4" H (442 × 840 × 1,510 mm); 238 lb (108 kg) net.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
The RAD90-1X15 takes the clearances, wiring, cable entry and breakers of every RADIANT model, from its AEC US user manual: see them on the RADIANT page.
Place the RAD90-1X15 in your room, to the inch, with Room fit
Datasheet
RAD90-1X15 datasheet.
The RAD90-1X15 in the AEC 2026 catalog, figure by figure. Compare it with every RADIANT model.
| Parameter | RAD90-1X15 |
|---|---|
| Power | |
| Rated power (kVA) | 15 |
| Active power (kW) | 15 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 208 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X |
| Efficiency, up to | 94% |
| Battery DC bus | 240 V DC |
| Battery and runtime | |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | External battery bank |
| Mechanical | |
| Form factor | Modular Rack 19" |
| Dimensions W × D × H | 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm) |
| Net weight | 238 lb (108 kg) |
| Footprint | 4.0 ft² (0.37 m²) |
| Common to every RADIANT | |
| Technology | 3-level IGBT; unity power factor (kVA = kW); 40 A settable charger |
| Battery, RAD90-1X15 | external VRLA (battery bank sized separately) |
| Display | 7-inch color touchscreen |
| Comms | RS-232, EPO and USB, standard |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The RADIANT documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
Quick answers
RAD90-1X15: what people ask
What is the output current of the RAD90-1X15?
41.6 A per phase at full load: 15 kVA ÷ (√3 × 208 V). Size the input breaker and the cables of the RAD90-1X15 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the RAD90-1X15 give off?
About 991 W, 3,380 BTU/h, at full load, where it is 93.8% efficient. Plan the room's cooling for a little more than that: the RAD90-1X15 is less efficient at part load and while its battery recharges.
Will the RAD90-1X15 fit through a standard door?
Yes: 17.4 in (442 mm) across its narrow side and 59.4 in (1,510 mm) high, it passes a standard 36 × 80-inch door upright. On the way in, check corridors, elevators and the floor load of the RAD90-1X15 (size section above).
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
RADIANT
Other RADIANT models
By power, the RAD90-1X15 is the smallest in the RADIANT series, which runs from 15 to 90 kVA. One size up is the RAD90-2X15 (15 kVA more and 31 lb heavier).
Every RADIANT model side by side (6)
| Model | Power | Power against this model | Net weight | Weight against this model |
|---|---|---|---|---|
| RAD90-1X15 | 15 kVA | this page | 238 lb | this page |
| RAD90-2X15 | 30 kVA | 15 kVA more | 269 lb | 31 lb heavier |
| RAD90-3X15 | 45 kVA | 30 kVA more | 299 lb | 61 lb heavier |
| RAD90-4X15 | 60 kVA | 45 kVA more | 330 lb | 92 lb heavier |
| RAD90-5X15 | 75 kVA | 60 kVA more | 360 lb | 122 lb heavier |
| RAD90-6X15 | 90 kVA | 75 kVA more | 391 lb | 153 lb heavier |
The RAD90-1X15 for your project
Send the load, the voltage and the minutes you need from the RAD90-1X15. We reply with the configuration, the batteries and the lead time.