RADIANT · 208V three-phase UPS

RAD90-6X15 RADIANT 90 kVA, 208V three-phase UPS

VRLA90 kVAOnline double conversion

The AEC RADIANT RAD90-6X15 is a 90 kVA / 90 kW online double-conversion UPS for 208 V three-phase loads, built on six 15 kVA power modules, with external battery cabinets. Kept at 80 % of its rating, it carries loads up to 72 kW.

All six module slots are fitted, so the frame is at its full 90 kVA; with one module held as a spare (N+1) it carries 75 kVA. As configured it weighs 390.5 lb (177.2 kg) net.

90 kVA / 90 kWRating
17.4 × 33.1 × 59.4 inW × D × H
390.5 lbWeight
VRLA, externalBattery

Series picture.

AEC RAD90-6X15, rendered from its 3D modelDrag to turn

In 3D

Look around the RAD90-6X15

Load by load

The RAD90-6X15 at 25, 50, 75 and 100 % load.

Its 90 kW rating in four steps, worked out from its own catalog figures.

At 25, 50, 75 and 100 % load
LoadOutput current per phase, at 208 VLoad on each of its 6 power modulesEfficiencyHeat to removeHeat to remove (BTU/h)
25 % of the RAD90-6X15, 23 kW62.5 A per phase25 % on each module92.8 % efficient1.7 kW of heat5,960 BTU/h to cool
50 % of the RAD90-6X15, 45 kW125 A per phase50 % on each module93.9 % efficient2.9 kW of heat9,970 BTU/h to cool
75 % of the RAD90-6X15, 68 kW187 A per phase75 % on each module94.0 % efficient4.3 kW of heat14,700 BTU/h to cool
100 % of the RAD90-6X15, 90 kW250 A per phase100 % on each module93.8 % efficient5.9 kW of heat20,300 BTU/h to cool

Current = kVA × load ÷ (√3 × volts).

Module load = load ÷ the kVA of the power modules fitted.

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

What is the RAD90-6X15?

The code RAD90-6X15 orders these catalog items:

  • 1 × RAD90-FRAME: 90 kVA frame, without power modules, 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm)
  • 6 × RAD-PWR-15: 15 kVA hot-swappable power module, 30.5 lb (13.9 kg) each
  • Architecture: 6 × 15 kVA hot-swappable power modules in a 90 kVA / 90 kW frame, 6 slots with 4 breakers; parallel up to 4 frames.

The lines every RADIANT shares, from technology to warranty, are in the RADIANT key facts and in the datasheet below.

6 × 15 kVA power modules fitted in a 6-slot frame: the frame is full.

Size and floor

How big it is

17.4" W × 33.1" D × 59.4" H (442 × 840 × 1,510 mm); 390.5 lb (177.2 kg) net.

4.0 ft²footprint (0.37 m²)
98 lb/ft²floor load of the cabinet alone
Modular Rack 19"form factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

5′9″ FrontSide 17.4″33.07″59.45″

Datasheet

RAD90-6X15 datasheet.

The RAD90-6X15 in the AEC 2026 catalog, figure by figure. Compare it with every RADIANT model.

RAD90-6X15 datasheet
ParameterRAD90-6X15
Power
Rated power (kVA)90
Active power (kW)90
Output power factor1.0
Electrical
Input / output208 V three-phase, 4-wire (3P+N)
TopologyOnline double conversion, modular N+X
Efficiency, up to94%
Battery DC bus240 V DC
Battery and runtime
Battery typeVRLA (sealed lead-acid)
Battery configurationExternal battery bank
Mechanical
Form factorModular Rack 19"
Dimensions W × D × H17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm)
Net weight390.5 lb (177.2 kg)
Footprint4.0 ft² (0.37 m²)
Common to every RADIANT
Technology3-level IGBT; unity power factor (kVA = kW); 40 A settable charger
Battery, RAD90-6X15external VRLA (battery bank sized separately)
Display7-inch color touchscreen
CommsRS-232, EPO and USB, standard
Network cardSNMP-M (SNMP)
Warranty3 years on UPS · 2 years on VRLA batteries
Quality systemISO 9001:2015, the group's quality system (SGS)

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

RAD90-6X15: what people ask

What is the output current of the RAD90-6X15?

249.8 A per phase at full load: 90 kVA ÷ (√3 × 208 V). Size the input breaker and the cables of the RAD90-6X15 from its installation manual and the local electrical code, not from this figure alone.

How much heat does the RAD90-6X15 give off?

About 5.9 kW, 20,300 BTU/h, at full load, where it is 93.8% efficient. Plan the room's cooling for a little more than that: the RAD90-6X15 is less efficient at part load and while its battery recharges.

Will the RAD90-6X15 fit through a standard door?

Yes: 17.4 in (442 mm) across its narrow side and 59.4 in (1,510 mm) high, it passes a standard 36 × 80-inch door upright. On the way in, check corridors, elevators and the floor load of the RAD90-6X15 (size section above).

The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h

RADIANT

Other RADIANT models

The RADIANT series, with pictures

By power, the RAD90-6X15 is the largest in the RADIANT series, which runs from 15 to 90 kVA. One size down is the RAD90-5X15 (15 kVA less and 31 lb lighter).

Every RADIANT model side by side (6)
RADIANT models side by side
ModelPowerPower against this modelNet weightWeight against this model
RAD90-1X1515 kVA75 kVA less238 lb153 lb lighter
RAD90-2X1530 kVA60 kVA less269 lb122 lb lighter
RAD90-3X1545 kVA45 kVA less299 lb92 lb lighter
RAD90-4X1560 kVA30 kVA less330 lb61 lb lighter
RAD90-5X1575 kVA15 kVA less360 lb31 lb lighter
RAD90-6X1590 kVAthis page391 lbthis page

The RAD90-6X15 for your project

Send the load, the voltage and the minutes you need from the RAD90-6X15. We reply with the configuration, the batteries and the lead time.