How long your load runs on All-in-One lithium modules, L6 cabinets or OZ Power VRLA batteries: lithium from the catalogue's tables, VRLA with AEC's own calculator, the one AEC's portal uses. AEC's engineers check every system.
How many minutes, on which battery.
Battery, load and string: lithium from the EMEA 2026 catalogue's tables, VRLA with AEC's calculator.For lithium the catalogue gives the backup time by number of modules: nothing to choose here.
A worked example: 10 kW on an IST7-20
- The load: 10 kW, half of the 20 kW of the AEC IST7-20 (power factor 1: 20 kVA = 20 kW).
- With 36 × 12 V 9 Ah (code IST7-20-36X9) the backup time is 6 minutes; at full load, 20 kW, it falls to 2 minutes.
- With 40 × 12 V 80 Ah (code IST7-20-40X80) the same 10 kW run for 167 minutes, 60 at full load.
- Doubling the load more than halves the minutes: a battery gives less in a fast discharge. So the sum starts from the real kW, not from the UPS rating.
Minutes AEC publishes for these ordering codes, new batteries at 25 °C. The tool above uses the same method as AEC's portal (the maker's constant-power table read on a straight line, 1.70 V/cell, 96% efficiency): on another string than the code's, or after rounding, it can differ by a minute.
Questions
Questions people ask
How is UPS backup time calculated?
You need the load in kW (not kVA), the battery (type, capacity in Ah, blocks per string and strings) and the end-of-discharge voltage. For VRLA batteries AEC's calculator reads the power per block in the battery maker's constant-power table, at 1.70 V/cell and 96% efficiency, as AEC's portal does.
Why is the backup time more than double at half load?
Because a battery gives more in a slow discharge. In the example the AEC IST7-20 with 36 × 12 V 9 Ah runs 2 minutes at full load and 6 at half load.
Do the minutes hold for the whole battery life?
No: the tables give minutes with new batteries at 25 °C. Capacity falls with age and with higher temperatures, so a system is sized with a margin. AEC's engineers check every sizing.
Lithium or VRLA: how does the tool work them out?
For lithium (All-in-One modules and L6 cabinets) the tool reads the EMEA 2026 catalogue's tables; for OZ Power VRLA batteries it uses AEC's calculator. One L6 cabinet with 100 Ah modules stores 69 kWh.
Talk to an AEC engineer