400 V · up to 1.2 MVA
Modular UPS: 30 kVA to 1.2 MVA, hot-swap modules
A modular UPS adds hot-swappable power modules in one cabinet: it grows with the load and stays on line with N+1 redundancy. AEC's three IST6 ranges run from 30 to 120 kVA with 30 kVA modules, from 200 to 500 kVA with 50 kVA modules, and from 400 to 1,200 kVA with 100 kVA modules.



Models
One model, one page
Every rating has its own page: that model's technical data, ordering codes, batteries and the questions people ask.
Comparison
Modular UPS: how do the ranges compare?
| Range | Ratings | Voltage | Description | Batteries |
|---|---|---|---|---|
| IST6-120 | 30–120 kVA | 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L | Modular online UPS, double conversion, 30–120 kVA | VRLA |
| IST6 200–500 | 200–500 kVA | 380 / 400 / 415 V | Modular online UPS, double conversion, 200–500 kVA | VRLA |
| IST6 400–1200 | 400–1200 kVA | 380 / 400 / 415 V | Modular online UPS, double conversion, 400–1200 kVA | VRLA |
Questions
Questions people ask
Which IST6 modular range fits my power?
The IST6-120 uses 30 kVA modules from 30 to 120 kVA in one cabinet; the IST6 200–500 uses 50 kVA modules in cabinets of 200, 300, 400 and 500 kVA; the IST6 400–1200 uses 100 kVA modules from 400 kVA to 1.2 MVA per cabinet.
How do the modular ranges compare on efficiency?
The IST6-120 reaches 97% in double conversion and up to 99% in ECO; the IST6 200–500 up to 98.1%; the IST6 400–1200 up to 97.2% with General modules and 98.1% with PLUS modules, with 99.2% in ECO. All three offer redundancy sleep for spare modules at light load.
How do redundancy and parallel operation differ between the modular ranges?
The IST6-120 has a fifth slot for an N+1 module, and several cabinets work in parallel with the parallel kit. The IST6 200–500 and 400–1200 run up to eight UPS in parallel with N+X redundancy, up to 9.6 MW on the larger range, and add three-bus layouts to BSC dual bus.
How much floor space do the modular cabinets take?
All are 2000 mm high, and the IST6-120 cabinet is 600 × 860 mm. The IST6 200–500 cabinets are 607 × 860 mm (200–300 kVA) or 1203 × 864 mm (400–500 kVA); the IST6 400–1200 cabinets are 801 × 1000 mm (400–800 kVA) or 1201 × 1000 mm (1000–1200 kVA).
Do the modular ranges work with lithium batteries?
Yes, all three accept lead-acid or lithium batteries with the optional BMS expansion card, and parallel systems can share a common battery. Lead-acid strings are ±14 to ±23 × 12 V blocks on the IST6-120, and 30 to 50 blocks on the larger ranges (±240 V and 480 V nominal with 40 blocks).
Guides
Guides: Modular UPS
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need: we answer with the model and the batteries that fit.