Single-phase UPS · 230 V

IST3-J Online rack UPS 1–10 kVA, 2U, 230 V

VRLAOnline double conversion

The AEC IST3-J is an online double-conversion UPS from 1 to 10 kVA, 2U high in a 19-inch rack, for 230 V supplies. The 1 to 3 kVA ratings also stand as a tower and have a hot-pluggable battery pack.

PF 1output power factor
95.5%AC/AC efficiency
3 yearswarranty
RCK · TWRrack or tower, 1–3 kVA
AEC IST3-J, rendered from its 3D modelDrag to turn

In 3D

Look around the IST3-J

Drag it round, swipe on a phone or use the arrow keys. X-ray makes the enclosure see-through, so you can see what sits behind the panels.

Pick a size: the turn and the full 3D view follow it. Rendered from AEC's 3D models; the full 3D view zooms in, opens the unit and names every part.

Efficiency

How efficient is the AEC IST3-J at your load?

AC/AC efficiency of each operating mode against the load: AEC's measured curves where they exist, elsewhere the typical curve derived from the datasheet figure by AEC's method. The losses and their cost follow the curve at the load you choose: drag along the chart or move the slider.

90.83%100% · Measured (AEC datasheet)

Filled points: measured by AEC (AC/AC technical datasheet). Hollow points: a typical curve, the shape of the most similar measured curve (same technology and size) moved to the range's datasheet efficiency: η(load) = reference curve + (datasheet figure − its highest point), AEC's method. Dashed lines: one figure without a load (ECO, W-ECO). Between points the efficiency is read on a straight line; beyond them, the nearest end. Losses = P × (1/η − 1).

Load
—
Lost as heat
—
Energy lost in a year, 24/7
—
Its cost in a year at € per kWh
—
The catalogue's examples use €0.20 per kWh.
Where each figure comes from
ModeEfficiencyKindModelsSource
Online, double conversion30%: 86.14% · 50%: 88.7% · 75%: 90.06% · 100%: 90.83%Measured (AEC datasheet)IST3-J 1 kVAAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
ECO98.3%Datasheet figure, load not statedallAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
Online, double conversion30%: 89.36% · 50%: 91.23% · 75%: 92.16% · 100%: 92.56%Measured (AEC datasheet)IST3-J 2 kVAAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
Online, double conversion30%: 90.84% · 50%: 91.85% · 75%: 93.3% · 100%: 93.1%Measured (AEC datasheet)IST3-J 3 kVAAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency
Online, double conversion30%: 93.04% · 50%: 94.05% · 75%: 95.5% · 100%: 95.3%Typical curve, derived from the datasheet efficiency of 95.5% (AEC method)IST3-J 6 kVA · IST3-J 10 kVAAEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency

EMEA 2026 catalogue figures: Online, double conversion up to 95.5%.

The display

The IST3-J 1–3 kVA display

The real display, drawn by AEC's own simulator: pick a UPS state (normal, battery, bypass) or a main page.

UPS state
IST3-J 1–3 kVA: Output voltage

IST3-J 1–3 kVA · the real display

Output voltage

Main pages

What is what

Inside the IST3-J, part by part.

Each number on the picture is named in the list.

Rear · 1 kVA

Rear panel of the IST3-J 1 kVA rack / tower UPS
  1. Output sockets8 × IEC C13: general outlets for the critical loads, programmable outlets for the others.
  2. Input socketMains input socket (IEC C14).
  3. Over-current protectorResettable protector of the mains input.
  4. External battery portDC input for the optional 2U battery box.
  5. Cooling fanLeave 300–500 mm free at the rear and sides for the air flow.
  6. EPO connectorThe EPO input cuts the output.
  7. RS232 portFor the UPS power management software: monitoring, remote ON / OFF.
  8. Intelligent slotUSB as standard; optional RS485 + dry-contact card or SNMP card.

Rear · 2–3 kVA

Rear panel of the IST3-J 2–3 kVA rack UPS
The rear of the 2–3 kVA: IEC sockets, the mains input, the battery port and the communication ports.
  1. Output sockets8 × IEC C13 + 1 × IEC C19: general outlets for the critical loads, programmable outlets for the others.
  2. Input socketMains input socket (IEC C20).
  3. Over-current protectorResettable protector of the mains input.
  4. External battery portDC input for the optional 2U battery box.
  5. Cooling fansLeave 300–500 mm free at the rear and sides for the air flow.
  6. EPO connectorThe EPO input cuts the output.
  7. RS232 portFor the UPS power management software: monitoring, remote ON / OFF.
  8. Intelligent slotUSB as standard; optional RS485 + dry-contact card or SNMP card.

Rear · 1–3 kVA with battery box

Rear of the IST3-J 1 kVA on its battery box
  1. Output sockets8 × IEC C13: general outlets for the critical loads, programmable outlets for the others.
  2. Input socketMains input socket (IEC C14).
  3. Over-current protectorResettable protector of the mains input.
  4. External battery portDC input for the optional 2U battery box.
  5. Cooling fanLeave 300–500 mm free at the rear and sides for the air flow.
  6. EPO connectorThe EPO input cuts the output.
  7. RS232 portFor the UPS power management software: monitoring, remote ON / OFF.
  8. Intelligent slotUSB as standard; optional RS485 + dry-contact card or SNMP card.
  9. Battery inputTwo battery ports: to the UPS's DC input and on to the next battery box.
  10. Battery breakerThe battery string's breaker.

Rear · 6–10 kVA

Rear panel of the IST3-J 6–10 kVA rack UPS
The rear of the 6–10 kVA: the terminal block for the wiring, two IEC output sockets and the communication ports.
  1. Battery expansion portDC input for the external battery: 192 V by default, 12 to 20 blocks of 12 V settable.
  2. Surge protection groundingGround point of the surge protection.
  3. Input breakerMains input breaker of the UPS. Upstream breaker recommended: 50 A (6 kVA), 100 A (10 kVA).
  4. Over-current protectorResettable protector, 250 V AC 10 A.
  5. Output socketsIEC output sockets, 10 A max.
  6. Wire terminalInput and output cables on screw terminals; size the cables by current.
  7. Parallel port10 kVA /B model only: two units in parallel.
  8. RS232 portFor the UPS power management software: monitoring, remote ON / OFF.
  9. EPO connectorThe EPO input cuts the output.
  10. Intelligent slotOptional RS485 + dry-contact card or SNMP card.

Overview

Key facts

Power range
1–10 kVA
Input / output
1/1 · 208 / 220 / 230 / 240 V
Efficiency
95.5% online double conversion · 98.3% ECO
Battery
36 V · 48 V · 72 V · 192 V default (12–20 × 12 V settable)
Communication
RS232 + USB · options: RS485 + dry contact, protocol card, SNMP · RS232
Network card
SNMP card (optional)
Warranty
3 years
Dimensions W × D × H
438 × 423 × 86 to 438 × 572 × 86 mm

Datasheet

Datasheet IST3-J.

Every model side by side: keep only what differs, take it as CSV or print it.

IST3-J · Technical data
Model1 kVA2 kVA3 kVA6 kVA (L)10 kVA (/B)
Rating
Power (VA / W)1000 / 10002000 / 20003000 / 30006000 / 600010000 / 10000
Input
Voltage range176–295 V > 75% load · 154–176 V 50–75% · 120–154 V < 50%176–275 V full load · 80–176 V linear derating
Frequency · connection50 / 60 Hz ± 10%, self-adapting · single phase, L + N + PE, TN system
Output
Voltage208 / 220 / 230 / 240 V ± 1%, settable220 V ± 2% default · 208 / 220 / 230 / 240 V
Frequency · waveform · transfer50 / 60 Hz ± 0.2% in battery mode · sine wave · 0 ms
Voltage distortionTHD < 2% (linear load)THD < 1% linear · < 4% non-linear
Power factor1.0 (kVA = kW)
Overload105–110% 10 min · 110–130% 1 min · 130–150% 1 s · > 150% 200 ms115–130% 10 min · 130–150% 30 s · > 150% 500 ms
Output outlets8 × C13 (1 kVA) · 8 × C13 + 1 × C19 (2–3 kVA)2 × IEC C13 (each ≤ 10 A) + wire terminal
Battery
Battery voltage36 V48 V72 V192 V default (12–20 × 12 V settable)192 V default (12–20 × 12 V settable)
Backup · recharge3 min full load · < 10 hexternal battery, any backup time
General
CommunicationRS232 + USB · options: RS485 + dry contact, protocol card, SNMPRS232 · intelligent slot options
Protectionsbattery under-voltage, overload, short circuit, over-temperature, input overvoltage
Noise< 50 dB< 55 dB
Environment−5 … 50 °C (derated 40–50 °C) · 0–95% RH · IP20 · 2000 m−5 … 40 °C · 0–95% RH · < 1000 m (derate above)
Dimensions W × D × H (mm)438 × 423 × 86438 × 572 × 86438 × 572 × 86438 × 500 × 86438 × 500 × 86
Weight (kg)14202610.612.2

6 kVA: long backup model only (L). 10 kVA: long backup, /B parallel version. Specifications are subject to change without notice.

Full technical details11 sections of the EMEA 2026 catalogue: functions, panel, connections, diagrams and ordering codes

Why IST3-J

012U · 19-inch rack19-inch, 2U: UPS and battery box mount in the same cabinet, with the battery box below the UPS.
02RCK · TWR · Rack or tower1–3 kVA: the LCD reading is set for rack (default) or tower mounting from the panel.
03Hot-plug · Battery packsOn 1–3 kVA the battery packs of the UPS and of the battery box are hot-pluggable, from the front.
04Programmable · Outlets that save backupOptional programmable outlets switch off non-critical loads after a set time on battery, to extend backup.
05120 V · The battery stays fullDown to 120 V of mains (1–3 kVA, load below 50%) the battery does not discharge, so it stays at 100%.
061–8 A · Charger to match the battery1–3 kVA with the 7 A charging module: charging current 1–8 A (default 1 A).

THE RANGE

From 1 to 10 kVA, always 2U

Three frames in the same 19-inch, 2U format. On 1–3 kVA the optional battery box has the same footprint as the UPS.

IST3-J · UPS and battery unit stacked, three-quarter view
IST3-J · rack UPS without rack ears, front
IST3-J · rack UPS with rack ears and handles, front
  • AEC rack battery cabinets: BBJ, up to 8 × 12 V 9 Ah, 2U, 438 × 413 mm, 6 kg; BBJ2, up to 16 × 12 V 9 Ah, 3U, 438 × 500 mm, 10 kg.
  • Several cabinets per UPS for longer backup; for the number of cabinets per UPS, see the ordering codes.
  • Rack examples: UPS 1–3 kVA (2U) with two battery boxes (2U each); long backup UPS 6–10 kVA (2U) with two BBJ2 · 16 × 9 Ah (3U each). Heavy units always below the UPS.
  • 2U UPS height, 1–10 kVA · 19" rack format, chassis 438 mm · 3 min at full load, 1–3 kVA standard · 192 V battery on 6–10 kVA, 12–20 × 12 V.
  • Batteries inside the UPS are 12 V 9 Ah on every 1–3 kVA model (codes IST3J-1-3X9 · IST3J-2-4X9 · IST3J-3-6X9). The optional 1 kVA battery box takes the same 9 Ah blocks: 2 × 3 × 12 V 9 Ah (catalogue p. 29, edition of 31 October 2026).
From 1 to 10 kVA, always 2U
UPSBattery box: batteriesW × D × H (mm)kg
1 kVA2 × (3 × 12 V 9 Ah)438 × 420 × 8720
2 kVA2 × (4 × 12 V 9 Ah)438 × 570 × 8729
3 kVA2 × (6 × 12 V 9 Ah)438 × 570 × 8740

HOW IT WORKS

Online double conversion in two rack units

Active PFC, a half-bridge inverter and a DC/DC boost; on 6–10 kVA the charger is fed from the DC bus.

IST3-J · block diagram: rectifier, inverter, battery and transfer switch, charger fed from the AC input
IST3-J · block diagram: rectifier, inverter, battery and transfer switch, charger fed after the PFC stage
IST3-J · rack UPS, three-quarter view
IST3-J · standing as a tower on its feet
  • Step 1 · Active PFC: with the mains normal, the PFC turns the input into a steady ±360 V DC bus with a high input power factor.
  • Step 2 · Half-bridge inverter: the DC/AC inverter rebuilds a steady sine wave for the load while the battery is charged.
  • Step 3 · DC/DC boost: with the mains abnormal, the DC/DC raises the battery voltage to the DC bus. The charger is fully isolated on every size.
  • Rack (RCK): fix two angle irons on the UPS, push it into the rack and fix it; the battery box mounts the same way, below the UPS. The battery box is heavy: always mount it below the UPS.
  • Tower (TWR, 1–3 kVA): fit the support bases, stand the UPS on them, then set TWR on the panel. With a battery box, add two 1U joint bases per box. Default reading: RCK.
  • 0 ms transfer time · ±360 V DC bus · ±0.2% output frequency in battery mode · THD < 2% with linear load (1–3 kVA).

BATTERY-FRIENDLY

More backup where it matters

A wide input window saves the battery for real outages; programmable outlets and a settable charger stretch backup and battery life.

  • 1–3 kVA: 176–295 V above 75% load, 154–176 V at 50–75%, 120–154 V below 50%.
  • 6–10 kVA: full load from 176 to 275 V, linear derating down to 80 V; 50 / 60 Hz ± 10%, self-adapting.
  • Programmable outlets (optional, 1–3 kVA): on mains failure the general outlets keep critical loads on battery, while the programmable outlets for non-critical loads switch off after a time limit of 0–999 min, set from the PC.
  • Discharge time limit, 2–3 kVA: no time limit with load below 75%; 6.0 min at 75% load down to 3.0 min at 100%. 75–100% load: T = 18000 / (2 × load % − 100) / 60 (T in minutes). The 1 kVA model has no time limit.
  • Charging current 1 A by default; 2–8 A settable only with the 7 A charging module. Recommended: 0.1–0.2 C of the battery capacity.
  • Hot-pluggable battery packs: UPS and battery box, 1–3 kVA, replaced from the front panel. Use the same capacity, model and make.

1 · 2 · 3 KVA

Everything on the rear panel

IEC outlets, IEC inlet, battery port and communication on the back of a 2U chassis.

  • Output outlets: IEC C13 (plus one C19 on 2–3 kVA); general outlets for critical loads, programmable outlets (optional) for non-critical loads.
  • Input inlet: IEC mains input. Over-current protector: resettable circuit protector on the input.
  • External battery port: DC input for the battery box or the external battery.
  • Cooling fan: one fan on 1 kVA, two on 2–3 kVA.
  • EPO connector: opening the contact closes the output. RS232 port: for UPS power management software.
  • Intelligent slot: USB as standard; RS485 + dry contact, protocol transfer card or SNMP card as options.
  • Outlets: 1 kVA 8 × IEC 320 C13; 2–3 kVA 8 × IEC 320 C13 + 1 × IEC 320 C19. Load current per 10 A outlet: generally not more than 5 A.
  • Programmable outlets: connect non-critical devices to them; a backup time limit of 0–999 minutes (default 999), set from the PC, switches them off on battery or overload, leaving more backup time to critical loads.

6 · 10 KVA

Long backup power in a 2U chassis

The 6 and 10 kVA models are long backup models: no internal batteries, an external battery string of 192 V by default, and a wire terminal for input and output.

  • Rear panel: battery expansion port · surge protection earthing · input breaker · over-current protector · output sockets · wire terminal · parallel port (/B only) · RS232 port · EPO connector · intelligent slot.
  • Wide input: full load from 176 to 275 V; from 80 to 176 V the load capacity decreases linearly with the input voltage. 50 / 60 Hz ± 10%, self-adapting.
  • Battery set on site: 192 V by default; 12 to 20 batteries of 12 V can be set through communication. Backup time set by the external battery.
  • Parallel version: the 10 kVA /B model can be used in parallel through its parallel port.
  • Overload 6–10 kVA: 115–130% 10 min, 130–150% 30 s, > 150% 500 ms.
  • Output: 220 V ± 2% default, 208 / 220 / 230 / 240 V settable. THD < 1% linear, < 4% non-linear load.
  • Recommended upstream input breaker: 50 A (6 kVA), 100 A (10 kVA). Noise < 55 dB · −5 … 40 °C.

PANEL AND SETTINGS

Set the UPS from its own panel

An LCD and three buttons on the front (1–3 kVA). Settings are scrolled with SELECT and confirmed with ON; without confirmation the page closes after 20 s.

IST3-J · control panel: LCD and three keys
IST3-J · LCD, output reading
IST3-J · LCD, input reading
  • Display: input / output voltage and frequency, load, temperature, fault code, parameters, mode; icons for mains, bypass, battery and ECO mode, silence (buzzer silenced) and failure. RCK rack reading or TWR tower reading.
  • ON: hold 1 s to switch on · in mains mode hold 3 s for a battery test · in battery mode hold 3 s to silence (again 3 s to cancel) · hold 1 s to confirm.
  • OFF: hold 1 s to switch off. SELECT: press to scroll voltages, frequencies, battery, temperature, load and faults · hold 5 s for the setting page.
  • Fault codes: EPO (long beep) emergency stop, bypass and inverter output closed · BUS (long beep) DC bus voltage fault, inverter output closed · TMP (long beep) over-temperature, check fans and air vents · FAN (every 0.2 s) fan fault, alarm then protection.
  • OUT (long beep) output short circuit or load too large · BAT (long beep) battery voltage too low or too high · load bars all flashing (every 0.2 s): overload, reduce the load · battery bars off with frame flashing (every 0.2 s): battery nearly empty.
  • Settings from panel and PC: ECO or INV operating mode · output 208–240 V (default 220 V) · programmable outlets 0–999 min, from the PC · 50 / 60 Hz converter mode, from the PC.

OVERLOAD AND PROTECTION

Absorbs peaks, contains faults

The inverter carries overloads for a set time, and the UPS protects battery, output, input, temperature, fans and DC bus.

  • Overload 1–3 kVA: 105–110% 10 min, 110–130% 1 min, 130–150% 1 s, > 150% 200 ms.
  • Overload 6–10 kVA: 115–130% 10 min, 130–150% 30 s, > 150% 500 ms.
  • Protections: battery under-voltage · output overload and short circuit · input overvoltage · over-temperature · fan blocked or damaged · EPO emergency power off · DC bus voltage fault.
  • Alarms: battery low, mains abnormal, UPS fault, overload.
  • Battery care: charge for 10 hours before first use; discharge and recharge every 4–6 months (every 2 months in hot areas); in storage, charge and discharge every 3 months; after a discharge, recharge completely within 24 h.
  • Output quality 1–3 kVA: 208 / 220 / 230 / 240 V ± 1%, settable; THD < 2% linear load.
  • Output quality 6–10 kVA: 220 V ± 2% default, 208 / 220 / 230 / 240 V settable; THD < 1% linear, < 4% non-linear load.
  • Do not connect half-wave rectified or inductive loads such as motors or air conditioners.
  • 3 min at full load (standard 1–3 kVA) · < 10 h charge recovery (standard models) · 1–8 A charging current with module · 24 h full recharge after a discharge.

CONNECTIVITY

Monitored from the desk or the network

RS232 and USB with power management software as standard; cards for SNMP, RS485 with dry contacts or protocol transfer in the intelligent slot.

  • RS232 · USB (standard): power management software for monitoring of status and electrical data, remote ON / OFF, support for an external SNMP adaptor on RS232. USB on 1–3 kVA.
  • Intelligent slot cards (optional): RS485 + dry contact; protocol transfer card (1–3 kVA; RS232 or RS485 on DB9, not both at once; RS485 reserved for lithium battery communication).
  • SNMP card (optional): RJ45 network port, COM1 for a temperature and humidity module (RS485), status indicators for running and alarm.
  • EPO (standard): the EPO input cuts the output.
  • Dry-contact outputs normally closed by default; jumpers CN1–CN3 select NC (pins 1–2, default) or NO (pins 2–3). Input signal below 60 V DC or 42 V AC RMS, below 1.25 A.
Monitored from the desk or the network
PinSignal
1 · 2Mains abnormal: COM · NC/NO
3 · 4Battery undervoltage: COM · NC/NO
5 · 6UPS failure: COM · NC/NO
7 · 8RS485-A · RS485-B

INSTALLATION

In the rack or on the floor

Rack mounting with angle irons, tower mounting on support bases. Size the input breaker for the model and keep the air vents free.

  • Rack mounting in 4 steps: fit the right plastic panel; fix two angle irons on the UPS; push the UPS into the rack; fix the UPS on the rack, with the battery box below, the same way.
  • Clearance of at least 300–500 mm around the UPS and 500 mm on top (1–3 kVA, tower or free-standing).
  • −5 … 50 °C on 1–3 kVA, derating 40–50 °C; 6–10 kVA −5 … 40 °C · 0–95% RH non-condensing.
  • Altitude ≤ 2000 m on 1–3 kVA; 6–10 kVA < 1000 m · TN system, N-PE below 5 V.
  • 1–3 kVA cables for about 5 m; 6–10 kVA: size cables by current. Input breaker 1.5–2 times the maximum input current, without leakage protection.
  • Tower: fit the support bases, stand the UPS on them, then set TWR on the panel; add two 1U joint bases per battery box.
  • Intelligent slot: cards in 3 steps; remove the standard slot, fit and fix the optional card, connect the communication cable.
  • Battery, front replacement: 1–3 kVA hot-pluggable battery packs, replaced after removing the plastic panel and battery plate.
  • First start (1–3 kVA): 10 h first charge before use; connect the UPS to the mains, hold ON for 1 s; about 10 s later, if the UPS runs steadily, start the loads.
In the rack or on the floor
ModelAC input max. (A)AC breaker (A)DC input max. (A)DC breaker (A)AC cable (mm²)DC cable (mm²)
1 kVA61029.1 (rated)—0.756
2 kVA122042.6 (rated)—1.56
3 kVA183242.6 (rated)—2.56
6 kVA36503950——
10 kVA6010065100——

Ordering codes IST3-J

CodeDescription
IST3J-1-3X9 · IST3J-2-4X9 · IST3J-3-6X9UPS with internal 12 V 9 Ah batteries (3 · 4 · 6)
IST3J-[kVA]-[n]X91–3 kVA with internal batteries plus BBJ / BBJ2 rack cabinets, n × 12 V 9 Ah in total
IST3J-6 · IST3J-106 / 10 kVA, external batteries only
IST3J-6/10-[n]X96 / 10 kVA with 1 to 8 BBJ2 cabinets, 16 to 128 × 12 V 9 Ah
BBJ · BBJ2Rack battery cabinet, max. 8 × 12 V 9 Ah (2U) · max. 16 × 12 V 9 Ah (3U)

Diagrams

The IST3-J, in diagrams

The path of the power, the ratings, the footprints and the losses, drawn from the figures of the EMEA 2026 catalogue.

How the power flows

Pick an operating mode: the path the power takes to the load lights up.

MainsRectifierDC busBatteryInverterStatic switchLoadStatic bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypass

Normal. Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge.

The ratings

Every model in the range, in proportion to its power.

  1. IST3J-11 kVA · 1 kW
  2. IST3J-22 kVA · 2 kW
  3. IST3J-33 kVA · 3 kW
  4. IST3J-66 kVA · 6 kW
  5. IST3J-1010 kVA · 10 kW

Phase configurations

Input / output: three-phase (3) or single-phase (1).

UPS
1/1 1~ → 1~

Questions

Questions people ask

Can the IST3-J be mounted in a rack and as a tower?

Yes for the 1–3 kVA: every model from 1 to 10 kVA is 19-inch and 2U high, and the 1–3 kVA models can also stand as a tower: the LCD reading is set to RCK (rack, default) or TWR (tower) from the panel. The battery box always mounts below the UPS.

What backup time does the IST3-J offer?

The 1–3 kVA standard models give 3 minutes at full load with internal batteries, extended with BBJ (2U, up to 8 × 12 V 9 Ah) or BBJ2 (3U, up to 16 × 12 V 9 Ah) rack cabinets. The 6 and 10 kVA are long backup models with no internal batteries: an external string of 192 V by default (12–20 × 12 V settable) sets the backup time, with 1 to 8 BBJ2 cabinets.

What do the programmable outlets do?

On 1–3 kVA, the optional programmable outlets switch off non-critical loads after a time limit of 0–999 minutes on battery, set from the PC (default 999). The general outlets keep the critical loads running, so they get more backup time.

Can IST3-J units run in parallel?

Only the 10 kVA /B version can be used in parallel, through its parallel port. The other models work as single units.

Can the batteries be replaced without switching off?

Yes, on the 1–3 kVA: the battery packs of the UPS and of the battery box are hot-pluggable and replaced from the front, using the same capacity, model and make. The charging current is 1 A by default, settable to 2–8 A with the 7 A charging module.

What are the IST3-J dimensions, weights and outlets?

The 1 kVA measures 438 × 423 × 86 mm (14 kg) with 8 × IEC C13 outlets. The 2–3 kVA measure 438 × 572 × 86 mm (20 / 26 kg) with 8 × C13 + 1 × C19; the 6–10 kVA measure 438 × 500 × 86 mm (10.6 / 12.2 kg) with 2 × C13 and a wire terminal. On 1–3 kVA leave at least 300–500 mm around the UPS and 500 mm on top.

Which communication options does the IST3-J have?

RS232 with power management software is standard, plus USB on 1–3 kVA and an EPO input. The intelligent slot takes an optional SNMP card (RJ45 network port and COM1 for a temperature and humidity module), an RS485 and dry-contact card, or a protocol transfer card (1–3 kVA).