Three-phase UPS · 400 V

IST7 60–200 Three-phase online UPS, 400 V

VRLAOnline double conversion

The AEC IST7 60–200 is a three-phase online double-conversion UPS for 400 V supplies in six ratings from 60 to 200 kVA, in two cabinet sizes. Output power factor 1 (kVA = kW), 96.5% peak efficiency and 99% in ECO mode, input THDi ≤ 3% at full load; up to 8 units in parallel for 1.6 MW with N+X redundancy.

96.5%peak efficiency
PF 1output power factor
≤3%input THDi at full load
1.6 MW8 units in parallel
AEC IST7 60–200, rendered from its 3D modelDrag to turn

In 3D

Look around the IST7 60–200

Drag it round, swipe on a phone or use the arrow keys. X-ray makes the enclosure see-through, so you can see what sits behind the panels.

Pick a size: the turn and the full 3D view follow it. Rendered from AEC's 3D models; the full 3D view zooms in, opens the unit and names every part.

Hands on

Open the IST7 60–200 yourself.

Click the unit: the door opens. Drag to move it by hand. The 3D shows every part.

AEC IST7 60–200, closed

Every part in 3D

Efficiency

How efficient is the AEC IST7 60–200 at your load?

AC/AC efficiency of each operating mode against the load: AEC's measured curves where they exist, elsewhere the typical curve derived from the datasheet figure by AEC's method. The losses and their cost follow the curve at the load you choose: drag along the chart or move the slider.

96.5%50% · Typical curve, derived from the datasheet efficiency of 96.5% (AEC method)

Filled points: measured by AEC (AC/AC technical datasheet). Hollow points: a typical curve, the shape of the most similar measured curve (same technology and size) moved to the range's datasheet efficiency: η(load) = reference curve + (datasheet figure − its highest point), AEC's method. Dashed lines: one figure without a load (ECO, W-ECO). Between points the efficiency is read on a straight line; beyond them, the nearest end. Losses = P × (1/η − 1).

Load
—
Lost as heat
—
Energy lost in a year, 24/7
—
Its cost in a year at € per kWh
—
The catalogue's examples use €0.20 per kWh.
Where each figure comes from
ModeEfficiencyKindModelsSource
Online, double conversion25%: 95.9% · 50%: 96.5% · 75%: 96.2% · 100%: 95.9%Typical curve, derived from the datasheet efficiency of 96.5% (AEC method)allAEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape)
ECO99%Datasheet figure, load not statedall

EMEA 2026 catalogue figures: Online, double conversion up to 96.5% · ECO up to 99%.

The display

The IST7 60–120 kVA display

The real display, drawn by AEC's own simulator: pick a UPS state (normal, battery, bypass) or a main page.

UPS state
IST7 60–120 kVA: Normal operation

IST7 60–120 kVA · the real display

Normal operation

Main pages
IST7 60 kVA in 3D, the displayThe camera moves in to the display. · 0:06

What is what

Inside the IST7 60–200, part by part.

Each number on the picture is named in the list.

Front, door open · 60–120 kVA

IST7 60–120 kVA with the front door open: power unit, bypass and control unit, switchgear
Switchgear behind the lockable door; all communication ports on the bypass and control unit. Cables enter from below.
  1. Power unitPFC rectifier, three-level inverter and battery booster in one unit, with RUN / ALARM / FAULT LEDs. 60–120 kVA: one unit; 160–200 kVA: two.
  2. Bypass and control unitStatic bypass, system control card and all the communication ports in one place: dry contacts, EPO, parallel, RS485, Modbus RTU, RS232, SNMP and expansion slots.
  3. Battery cold startStarts the UPS from the battery when there is no mains and no bypass.
  4. Mains input switchThe rectifier's mains supply.
  5. SPD switchOptional: the disconnect switch of the surge protection device.
  6. Output switchTo the load.
  7. Bypass input switchThe static bypass supply.
  8. Surge protection (SPD)Optional class C SPD, for sites exposed to lightning.
  9. Maintenance bypass switchManual bypass: the load stays supplied while the UPS is de-energised for service.

Front, door open · 160–200 kVA

IST7 160–200 kVA with the front door open: two power units, bypass and control unit, switches
160–200 kVA: two power units above the bypass and control unit; the four switches below.
  1. Power units
  2. Bypass and control unit
  3. Battery cold start
  4. Mains input switch
  5. Output switch
  6. Bypass input switch
  7. Maintenance bypass switch

Communication ports

Ports of the IST7 60–200 kVA bypass and control unit (drawing)
All the communication ports are on the bypass and control unit.
  1. Battery cold startStarts the UPS from the battery when there is no mains and no bypass.
  2. SNMP card slotOptional SNMP card: Ethernet web monitoring, COM1 (RS485) for a temperature and humidity sensor.
  3. RS485 parallel monitoringRS485 port for the monitoring of a parallel system.
  4. Dry contacts, EPO, battery temperature4 inputs (10 functions) and 3 changeover outputs NO / NC (18 functions), each assigned from the display; EPO; battery temperature probe.
  5. Parallel portsUp to 8 units in a ring: N units, N cables, two links per unit (parallel kit PAR-IST7-60/200).
  6. Expansion slotOptional dry-contact expansion (+3 inputs, +2 outputs) or BMS card for lithium battery communication.
  7. Control card LEDsStatus LEDs of the system control card.
  8. EPO2 inputSecond emergency power off input, normally closed.
  9. Modbus RTU and RS232Serial ports for building management and monitoring software.
  10. Touch-screen portLink to the touch screen on the door.
IST7 60 kVA in 3D, door openThe door opens on what is inside. · 0:06

Overview

Key facts

Power range
60–200 kVA
Input / output
220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L
Efficiency
up to 96.5% double conversion · 99% ECO mode
Battery
±192 V · ±216 V
Display
Colour touch screen, 5 status LEDs, ambient light bar
Communication
RS485 · Modbus RTU · RS232 · 4 IN / 3 OUT dry contacts · EPO · SNMP slot
Network card
SNMP card (optional)
Parallel
Up to 8 units, capacity or N+X · BSC dual-bus synchronisation
Warranty
3 years
Dimensions W × D × H
400 × 960 × 1193 · 600 × 1000 × 1600 mm

Datasheet

Datasheet IST7 60–200.

Every model side by side: keep only what differs, take it as CSV or print it.

IST7 60–200 · Technical data
ModelIST7-60IST7-80IST7-100IST7-120IST7-160IST7-200
General
Rated power (kVA / kW)6080100120160200
Capacity upgrade—to 100 / 120to 120—to 200—
Input
Connection3 phases + N + PE
Rated voltage220 / 230 / 240 V phase (380 / 400 / 415 V line)
Voltage range187–280 V phase at full power · 80–186 V with linear derating
Frequency · power factor · THDi40–70 Hz · ≥ 0.99 · ≤ 3% at full load
Bypass synchronisation range50 / 60 Hz ± 6 Hz
Battery
Nominal DC voltage (default)±192 V±192 V±216 V±216 V±216 V±216 V
String length28–48 × 12 V blocks, set on site · VRLA or lithium (BMS card)
Max. charge current30 A60 A
Output
Voltage · frequency220 / 230 / 240 V phase · 50 / 60 Hz (± 0.1 Hz on battery)
Power factor · THDv1 (settable 0.9) · ≤ 1% linear, ≤ 4% non-linear load
Transient · unbalance · phase error≤ 5% for 0–100–0% step · 100% unbalanced load · ≤ 1°
Transfer time inverter ↔ bypass< 1 ms synchronised · < 15 ms not synchronised
Inverter overload≤ 105% continuous · ≤ 110% 60 min · ≤ 125% 10 min · ≤ 150% 1 min (IST7-120: > 125% immediate)
Bypass overload≤ 130% continuous · ≤ 150% 5 min · ≤ 200% 1 s · ≤ 300% 100 ms
System
Efficiency AC/ACup to 96.5% double conversion · 99% ECO mode
ParallelUp to 8 units, capacity or N+X · BSC dual-bus synchronisation
CommunicationRS485 · Modbus RTU · RS232 · 4 IN / 3 OUT dry contacts · EPO · SNMP slot · expansion slot
DisplayColour touch screen, 5 status LEDs, ambient light bar, 10,000 events and 10,000 user-log entries
Environment−5 … 40 °C · 0–95% RH · IP20 · < 65 dB at 1 m · forced-air cooling
Cable entrybottom (all models)
EMCIEC 62040-2:2016 · category C3 (not for residential use without additional measures)
Dimensions W × D × H400 × 960 × 1193 mm600 × 1000 × 1600 mm
Weight153 kg163 kg165 kg167 kg294 kg296 kg

IST7-80: same hardware as IST7-100, upgradable to 100 or 120 kVA from the display. Specifications are subject to change without notice.

Full technical details17 sections of the EMEA 2026 catalogue: functions, panel, connections, diagrams and ordering codes

Why IST7 60–200

0196.5% · Efficiency that lowers lossesPeak AC/AC efficiency in online double conversion; up to 99% in ECO mode, with automatic return to the inverter when the bypass leaves tolerance.
02kVA = kW · Full rating as active powerUnity output power factor: a 120 kVA unit delivers 120 kW. Output PF can also be set to 0.9.
0380 → 120 · Power that follows the loadIST7-80 is upgraded to 100 or 120 kVA, IST7-100 to 120 kVA, IST7-160 to 200 kVA, by setting the capacity from the display. Same hardware, same footprint.
048 units · Parallel up to 1.6 MWCapacity or N+X redundant systems with up to 8 units. BSC synchronisation for dual-bus architectures.
05≤3% THDi · Clean input, wide windowPFC rectifier with input PF ≥ 0.99. Full power from 187 to 280 V phase voltage, linear derating down to 80 V.
0610,000 · Records for diagnosisUp to 10,000 events and 10,000 user-log entries, plus smart wave capture of the fault instant, on a colour touch screen with three access levels.

OPERATING COST

What efficiency means at 100 kW

Losses are the energy the UPS turns into heat: you pay for it once at the meter and again in the room cooling.

  • Online double conversion at 96.5%: 3.6 kW lost, 31,800 kWh per year, ≈ € 6,350 per year
  • ECO mode at 99%: 1.0 kW lost, 8,850 kWh per year, ≈ € 1,770 per year
  • Basis: 100 kW load, 24/7 operation, € 0.20/kWh, calculated at peak efficiency; losses = P × (1/η − 1). Indicative values.
  • In ECO mode the load is fed through the bypass while the mains stays within the set window (default ±15% voltage, ±2% frequency).
What efficiency means at 100 kW
ModeLossesEnergy lost / yearCost / year
Online double conversion · 96.5%3.6 kW31,800 kWh≈ € 6,350
ECO mode · 99%1.0 kW8,850 kWh≈ € 1,770

ARCHITECTURE

Three functional units behind one door

The rectifier converts the mains to DC with input PF ≥ 0.99; the inverter rebuilds a clean sine wave for the load. When the mains fails, the booster feeds the DC bus from the batteries with no break at the output. The static bypass takes over on overload or inverter fault; the maintenance bypass isolates the UPS for service.

  • Power unit: PFC rectifier, three-level inverter and battery booster in one unit, with RUN / ALARM / FAULT LEDs and a limit switch that puts the unit in or out of service
  • Bypass and control unit: static bypass, system control card, communication ports and the battery cold-start button
  • Switchgear: mains input, bypass input and output switches, accessible behind the lockable door
  • Maintenance bypass: manual bypass switch; the load stays supplied while the UPS is de-energised for service
  • Surge protection (option): class C SPD with its own disconnect switch, for sites exposed to lightning
  • 160–200 kVA: 2 power units · 60–120 kVA: 1 power unit
  • 80 → 100 → 120 kVA · 160 → 200 kVA: IST7-80 uses the same hardware as IST7-100 and is upgraded to 100 or 120 kVA, IST7-100 to 120 kVA, IST7-160 to 200 kVA; the rated capacity is set from the display at engineering level, inside the same footprint

DESIGN AND INSTALLATION

Front, rear and footprint

Two cabinets with the same layout: 400 mm wide for 60–120 kVA, 600 mm wide for 160–200 kVA. Cooling air enters at the front and leaves at the rear.

IST7 60–200 · front with the display
IST7 60–200 · rear, cabinet on castors
IST7 60–200 · rear, cabinet without castors
IST7 60–200 · clearances around the cabinet
  • Operation panel: colour touch screen, five status LEDs, two-key ON / OFF commands and an ambient light bar that shows the UPS state across the room
  • Perforated front door, lockable; cooling air enters from the front, fan speed follows the load
  • Perforated rear panel: hot-air outlet; keep the openings on the front and rear free
  • Cable entry (input, output, battery and PE): from below on all models
  • Indoor, IP20, forced-air cooling
  • Operating temperature −5 … 40 °C, humidity 0–95%
  • Noise < 65 dB at 1 m from the front
  • 60–120 kVA: castors for positioning, then anchored to the floor; 160–200 kVA: bolted to the floor
  • Self-dedusting every 360 h (default); optional fan and capacitor service-life alarms
  • Free space ≥ 800 mm at the front, rear and above; air in at the front, out at the rear
  • IST7-80: same hardware as IST7-100
Front, rear and footprint
ModelW × D × H (mm)Weight
IST7-60400 × 960 × 1193153 kg
IST7-80400 × 960 × 1193163 kg
IST7-100400 × 960 × 1193165 kg
IST7-120400 × 960 × 1193167 kg
IST7-160600 × 1000 × 1600294 kg
IST7-200600 × 1000 × 1600296 kg

TECHNOLOGY

Three-level inverter, fully digital DSP control

The inverter switches between +Vdc, 0 and −Vdc instead of two levels. Smaller voltage steps give lower switching losses and a cleaner output. A DSP controls inversion, synchronisation and current sharing between parallel units.

IST7 60–200 · Three-level inverter, fully digital DSP control
  • Grid-friendly input: PFC rectifier, input PF ≥ 0.99 and THDi ≤ 3% at full load, 40–70 Hz
  • Full power from 187 to 280 V phase voltage (rated 220–240 V); from 186 V down to 80 V the rated power decreases linearly; below 80 V and outside the window the batteries take over
  • Output THDv ≤ 1% with linear load (≤ 4% non-linear)
  • 100% unbalanced load accepted on the three phases
  • Voltage transient ≤ 5% for a 0–100–0% load step
  • Transfer inverter ↔ bypass < 1 ms when synchronised (< 15 ms unsynchronised)
  • Overload, inverter (linear load): 105% continuous, 110% 60 min, 125% 10 min, 150% 1 min; > 150% immediate protection; IST7-120: above 125% immediate protection
  • Overload, static bypass: 130% continuous, 150% 5 min, 200% 1 s, 300% 100 ms; > 300% immediate protection; handles inrush and fault-clearing currents up to 300% for 100 ms
  • Cooling that adapts: fan speed follows the load, extending fan life and lowering noise at partial load; timed self-dedusting every 360 h by default; optional service-life alarms for fans and bus capacitors (lifetime settable, default 10 years)
  • Protections: output short-circuit, over- and under-voltage; overload and over-temperature; battery under-voltage (two levels); communication fault between units; EMC to IEC 62040-2:2016
Three-level inverter, fully digital DSP control
OverloadContinuousStep 2Step 3Step 4Immediate protection
Inverter, linear load105%110% · 60 min125% · 10 min150% · 1 min> 150% (IST7-120: > 125%)
Static bypass130%150% · 5 min200% · 1 s300% · 100 ms> 300%

OPERATOR PANEL

Single-line diagram, five LEDs, ambient light bar

Colour touch screen with live single-line diagram, five status LEDs, two-key ON / OFF commands and an ambient light bar that shows the UPS state in colour, also when the display backlight is off.

IST7 60–200 · display panel: normal operation, blue light bar
IST7 60–200 · display panel: normal operation, blue light bar
IST7 60–200 · display panel: input fault in red
IST7 60–200 · display panel: battery operation, yellow light bar
  • Colour touch screen: live single-line diagram, measurements, settings and records
  • Five status LEDs (AC/DC, DC/AC, bypass, battery, overload): green when active or normal, red when abnormal
  • ON keys: press both keys for 3 s to power on; two keys prevent accidental switching
  • OFF keys: press both keys for 3 s; the inverter stops and the load moves to bypass
  • Ambient light bar: blue = normal operation; blue flashing = battery mode; yellow = abnormal, load still supplied; red = abnormal, output off
  • Screen settings: ambient light on / off; backlight time 1–999 min (default 5); brightness, language, date and time

Tap a light: green is normal operation, red an abnormal state, as in the catalogue's table.

AC/DC: green, Rectifier normal

Single-line diagram, five LEDs, ambient light bar
LEDGreenRed
AC/DCRectifier normalRectifier abnormal
DC/ACInverter normalInverter abnormal
BYP.Bypass outputBypass abnormal
BATT. LOWBattery modeBattery low voltage
OVERLOADOutput normalOutput overload

TOUCH SCREEN

Touch a block, read its measurements

The home page draws the UPS as it runs: yellow dots trace the active power path, faulty blocks turn red, and the bottom line shows output voltage and frequency. Touch any block (bypass, mains, battery, rectifier, inverter, output) to open its page.

  • Bypass info: phase voltage, current and frequency of the bypass input
  • Mains info: phase voltage, current, frequency and input energy (MWh)
  • Battery info: positive and negative battery voltage, charge and discharge current, status
  • Inverter info: output phase voltage, current and frequency of the inverter
  • Information menu: running info, history, user log, smart records, device info, wave capture
  • Settings menu: cabinet, battery, battery test, output, smart mode, dry contacts, screen, password, communication, records
  • Running info: UPS info, parameter match between units, UPS status
  • Device info: hardware, software and series version of each unit
  • 3 access levels (user, engineer, factory), each with its own password
  • USB port on the screen for record export and firmware update
  • 1–999 minutes of backlight time, then the light bar keeps showing the state
  • 5 status LEDs and two-key ON / OFF commands below the screen

RECORDS

Every event recorded, ready to export

The UPS keeps a history of up to 10,000 events and a user log of up to 10,000 entries, plus smart records and wave captures, all exportable to a USB stick.

  • History record: 10,000 events with fault and alarm information of the system and of each unit, newest first
  • User log: every setting change with date and time, up to 10,000 entries; when a record is full, the oldest entry is overwritten
  • Current alarms: opened from the alarm icon on the home page, active faults time-stamped
  • Smart records: records linked to the smart-mode settings, such as redundancy
  • Smart wave capture: when an abnormal event occurs, the UPS stores the waveforms around it with date, time and abnormal information; three sources (rectifier, inverter, system card); parameters shown on four channels are selectable
  • Download to USB (FAT32 stick) from the record manage page: history record, user log, smart records, smart wave capture, battery discharge record
  • Firmware is updated the same way, from a USB stick

OPERATION

Every operating state, shown live

Real screens of the IST7: the yellow dots trace the active power path.

  • Online double conversion: mains → rectifier → inverter → load; batteries kept charged; load isolated from mains disturbances
  • Battery mode: mains out of limits; the batteries feed the inverter through the booster, with no break at the output
  • Static bypass: on overload or inverter fault the load moves to the bypass and returns to the inverter when the cause is cleared
  • Maintenance bypass: manual switch; the load is fed directly while the UPS is de-energised for service
  • ECO, up to 99%: load on bypass while the mains is within the window (default ±15% V, ±2% f); Standard ECO and W-ECO selectable
  • Frequency converter: rectifier and inverter decouple input and output frequency; output set to 50 Hz or 60 Hz
  • Self-load test: output switch open, the power circulates back to the input, testing the UPS at 1–100% load for 1–1440 h
  • Generator mode: start manual or by dry contact from the ATS; generator rated power and charge-power derating set on screen, so the genset is not overloaded
  • Transfers: 0 ms mains → battery (DC bus fed by the booster without interruption); < 1 ms inverter ↔ bypass synchronised (< 15 ms not synchronised); automatic return from bypass to inverter once overload or fault is cleared; 3 restart attempts after an output short circuit, then protection
  • Typical use: Online for data centres, healthcare and industry (the load never sees the mains); ECO for stable mains and tolerant loads, when the lowest losses matter most; frequency converter for 60 Hz machines on a 50 Hz grid or the other way round; generator mode for sites with a genset (controlled start and limited load on the generator)

SMART FUNCTIONS

Functions that look after the UPS and the site

Set from the Smart mode pages of the touch screen. Cooling air enters at the front and leaves at the rear; a timed self-dedusting function keeps the air path clear between service visits.

IST7 60–200 · airflow: cold in at the front, hot out at the back
IST7 60–200 · display: smart mode (module sleep) settings
IST7 60–200 · display: frequency converter mode
IST7 60–200 · display: generator settings
  • Self-cleaning, timed: default every 360 h, period settable
  • Self-cleaning, forced: started on demand from the screen
  • Self-cleaning, logged: "Fan dedusting" event in the records
  • Also on the same page: fan mode, fan and bus capacitor service-life alarms (default service life 10 years)
  • Frequency converter, 50 ↔ 60 Hz: supplies 60 Hz loads from a 50 Hz grid or the other way round, e.g. marine, test benches or imported machinery
  • Generator mode: start manual or by dry contact from the ATS; generator rated power and charge-power derating set on screen
  • Self-load test: load 1–100%, time 1–1440 h; burn-in without a load bank
  • Fan speed follows the load: quieter at partial load, longer fan life
  • Automatic start when the mains returns
  • Cold start from the battery, without mains
  • Short-circuit protection time 20 ms (default), up to 200 ms
  • Output voltage fine-tuning ±10 V; output PF 1 or 0.9
  • Bypass window +10/15/20%, −10/15/20%; frequency range 2–20%

PARALLEL SYSTEMS

Parallel, redundancy and common battery

Up to 8 units on one load bus, with parallel address 1–8 set from the display. Units are linked by parallel cables in a ring: N units, N cables, so each unit always has two connections.

IST7 60–200 · parallel cables between two UPS units
IST7 60–200 · parallel cables between several UPS units, UPS1 to UPSn
IST7 60–200 · display: cabinet settings (parallel)
IST7 60–200 · display: parallel redundancy settings
  • Common battery: the units of a parallel system share the same battery bank (fewer cabinets, less floor space, one string to maintain); each unit can also keep its own batteries
  • Mode manage: single or parallel mode, parallel address and BSC address
  • Capacity or N+X redundancy: basic quantity and redundancy quantity of the parallel system
  • Power grows by adding units: up to 1.6 MW with 8 × IST7-200 (200 kVA)
  • BSC: the synchronous output of the dual bus control synchronises two independent UPS systems in frequency and phase, so dual-corded loads and static switches can move between bus A and bus B
  • Current sharing between units ≤ 5%
  • Parameter match page shows any setting that differs between units; one command copies the settings to all units
  • Staggered start of the units to limit inrush on the source
  • Optional EPO linkage: one stop button for all units
  • Parallel kit PAR-IST7-60/200

BATTERIES

Battery charging and end-of-discharge protection

Charging in stages: current-limited charge, equalising, float, then an optional sleep phase that pauses charging and wakes up on voltage or time: less float time, longer battery life.

  • Max. charge current 30 A on 60–120 kVA, 60 A on 160–200 kVA
  • Charge current limit 0.2 C lead-acid, 0.5 C lithium (default)
  • Optional timed equalising (default interval 720 h)
  • Capacity setting 1–2000 Ah; string 28–48 × 12 V blocks
  • End-of-discharge protection: two levels in V/cell plus a maximum discharge time (default 960 min) and an optional pre-alarm; float charge 2.27 V/cell, under-voltage protection 1.667 V/cell (inverter output off), level II protection 1.617 V/cell (UPS fully shut down)
  • Battery test: standard (10 min) or deep test to the low-voltage alarm, started from the screen; runs only when the mains is normal, batteries are fully charged, the UPS has no fault and the load is at least 10%
  • Temperature: with the optional probe, charge voltage is compensated (default 3 mV/°C/cell) and alarms trip at 50 °C and 0 °C (defaults)
  • Best battery temperature 20–30 °C: below 20 °C backup time drops, above 30 °C battery life shortens
  • Lithium ready: BMS card for battery communication plus charge-disable and discharge-disable inputs
  • Three-pole battery string: split into two equal halves with the neutral at the midpoint, giving a positive and a negative DC bus from one set of 12 V blocks; battery breaker with three poles (+, N, −)
  • Set on site from the display at commissioning: blocks per string (28–48), capacity in Ah and battery type; default ±192 V (32 blocks) on IST7-60/80, ±216 V (36 blocks) on IST7-100…200

BATTERY CABINETS

BB5 to BB8, matched to every IST7

Steel cabinets for 12 V VRLA AGM batteries, supplied empty or complete with batteries, fuses and cables. Every configuration has its own AEC wiring diagram. Each cabinet holds one string with neutral at the midpoint; BB8 holds two strings in parallel.

IST7 60–200 · UPS cabinet with the display, three-quarter view
IST7 60–200 · wide battery cabinet with its breaker handle, three-quarter view
IST7 60–200 · tall battery cabinet with its breaker handle, three-quarter view
IST7 60–200 · double battery cabinet, front
  • BB5: 460 × 800 × 1400 mm, 110 kg empty
  • BB6: 800 × 800 × 1400 mm, 140 kg empty
  • BB7: 800 × 800 × 1900 mm, 160 kg empty
  • BB8: 1400 × 800 × 1900 mm, 250 kg empty
  • UPS for comparison: IST7-60…120 400 × 960 × 1193 mm, 153–167 kg; IST7-160…200 600 × 1000 × 1600 mm, 294–296 kg
  • Stored energy, max. layout (nominal: 12 V × Ah × batteries): BB5 18.2 kWh, BB6 25.9 kWh, BB7 43.2 kWh, BB8 76.8 kWh, 2 × BB8 153.6 kWh; backup time depends on load and battery data
  • IST7-80 has the IST7-100 hardware; cabinet fuses are selected for the UPS model
  • In every cabinet: 3-pole DC switch-disconnector Q1 with DC fuses; RAL 9005, IP20 (IP21–IP44 on request)
  • Options: forced ventilation, Q1 auxiliary contact, internal and external cables
  • IEC/EN 62040-1 · EN IEC 62485-2 · CE
  • Wiring diagram, commissioning record and battery log supplied; 3-year warranty on the cabinet
  • Order as one code: IST7-160-64X100 = IST7-160 + BB8 with 64 × 12 V 100 Ah · 294 kg + 2,215 kg
BB5 to BB8, matched to every IST7
UPSBB5BB6BB7BB82 × BB8
IST7-6030–38 × 40 Ah30–36 × 60 Ah30–36 × 80 / 100 Ah60 / 64 × 80 / 100 Ah120 / 128 × 80 / 100 Ah
IST7-80 · 100 · 120—30–36 × 60 Ah30–36 × 80 / 100 Ah60 / 64 × 80 / 100 Ah120 / 128 × 80 / 100 Ah
IST7-160——30–36 × 80 / 100 Ah60 / 64 × 80 / 100 Ah120 / 128 × 80 / 100 Ah
IST7-200———60 / 64 × 80 / 100 Ah120 / 128 × 80 / 100 Ah

BATTERY CABINETS

Battery connection by UPS model

Battery discharge current and recommended cable cross-section from the IST7 user manual; IST7-80 has the IST7-100 hardware. Cabinet fuses are selected for the UPS model.

Battery connection by UPS model
UPSI nom. (A)I max. (A)+/N/− mm²PE mm²
IST7-601631863516
IST7-80≤ 241≤ 2795035
IST7-1002412795035
IST7-1202893727035
IST7-1603864969570
IST7-2004825589570

CONNECTIVITY

Every port on the bypass and control unit

All ports sit in one place on the bypass and control unit; every dry-contact input and output is assigned from the display.

IST7 60–200 · SNMP card: network port and COM1
IST7 60–200 · dry-contact terminals
IST7 60–200 · BMS and dry-contact terminals
IST7 60–200 · communication panel with numbered ports
  • Bypass and control unit ports: battery cold start, SNMP card slot, RS485 parallel monitoring, dry contacts / EPO / battery temperature, parallel ports, expansion slot, control card LEDs, EPO2 input (NC), Modbus RTU and RS232, touch-screen port
  • 4 inputs, 10 functions: battery abnormal, battery earthing abnormal, battery switch open, bypass switch open, output switch open, battery discharge disable, battery charge disable, generator mode, SPD abnormal, maintenance bypass start
  • 3 changeover outputs (NO / NC), 18 functions: inverter output, bypass output, battery trip, on battery, battery low alarm, battery low protection, overload, UPS abnormal, bypass abnormal, mains abnormal, start generator, ECO output, inverter abnormal, single bypass feedback*, parallel bypass feedback*, UPS on, fan abnormal, UPS alarm (* on request)
  • Options: SNMP card (Ethernet, web pages, temperature/humidity sensor port); dry-contact expansion (+3 inputs, +2 outputs); BMS card (lithium battery communication); parallel kit PAR-IST7-60/200; battery temperature kit (probe and extension cable); surge protection (class C SPD with switch); battery release control (24 Vdc for shunt / UV release); lithium cabinets on request

AEC SERVICE

Survey, installation, commissioning, maintenance

AEC engineers size, install, commission and maintain the IST7. The UPS keeps its own records, and AEC service works from them.

IST7 60–200 · display: history record
IST7 60–200 · display: smart wave record
IST7 60–200 · display: battery test
IST7 60–200 · display: record management and export
  • 24/7 technical assistance by phone and WhatsApp, also on non-working days
  • < 30 min WhatsApp reply to technical and commercial questions
  • 3 years warranty, extendable with a maintenance contract
  • 21+ countries with spare parts in stock across the Allis Electric group
  • 01 Consulting and sizing: feasibility study and design for critical sites and data centres; UPS, battery and parallel system sized by the AEC engineering team (IST7: upgradable models, size for today, grow to 120 or 200 kVA)
  • 02 Survey and installation: site survey, positioning and cabling of the UPS and battery cabinets by AEC technicians (IST7: cable entry from below on all models)
  • 03 Commissioning: verification of every value and parameter, access levels and dry-contact functions (IST7: full-power self-load test without a load bank)
  • 04 Maintenance: programmes and contracts written for each site, battery checks and replacement, generator tests (IST7: fan and capacitor service-life alarms; battery test from the screen)
  • 05 Assistance 24/7: call centre 24 hours a day, 7 days a week, by phone and WhatsApp, with an engineer on site when needed (IST7: 10,000 events and wave capture exported to USB for analysis)
  • 06 Expansion: capacity upgrades and new units in parallel, configured by AEC service (IST7: up to 8 units; parameter match and copy across units)
  • Service data straight from the UPS: event history, wave capture, battery test records, USB export for the service report
  • AEC Service: service@aecups.com · +39 393 080 5211 · www.aecups.com · Via Nerviano 55, 20045 Lainate (MI), Italy

Ordering codes IST7 60–200

CodeDescription
IST7-6060 kVA / 60 kW
IST7-8080 kVA, upgradable to 100 or 120 kVA
IST7-100100 kVA, upgradable to 120 kVA
IST7-120120 kVA / 120 kW
IST7-160160 kVA, upgradable to 200 kVA
IST7-200200 kVA / 200 kW
PAR-IST7-60/200Parallel kit
IST7-[kVA]-[n]X[Ah]UPS with battery cabinet, n × 12 V [Ah] (e.g. IST7-160-64X100 = IST7-160 + BB8 with 64 × 12 V 100 Ah)

Diagrams

The IST7 60–200, in diagrams

The path of the power, the ratings, the footprints and the losses, drawn from the figures of the EMEA 2026 catalogue.

How the power flows

Pick an operating mode: the path the power takes to the load lights up.

Maintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypassMaintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypass

Normal. Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 96.5% (peak AC/AC).

The ratings

Every model in the range, in proportion to its power.

  1. IST7-6060 kVA · 60 kW
  2. IST7-8080 kVA · 80 kW
  3. IST7-100100 kVA · 100 kW
  4. IST7-120120 kVA · 120 kW
  5. IST7-160160 kVA · 160 kW
  6. IST7-200200 kVA · 200 kW

Losses per 100 kW of load

Worked out as P × (1/η − 1) at the stated maximum efficiency, with the load steady all year. peak AC/AC.

  1. Double conversion 96.5%3.63 kW31,770 kWh/year
  2. ECO 99%1.01 kW8,850 kWh/year

Phase configurations

Input / output: three-phase (3) or single-phase (1).

UPS
3/3 3~ → 3~

In parallel Up to 8 units on the same load, for redundancy or for more power.

Footprints to scale

Front view of the cabinets, all at the same scale, beside a 2 m rule. W × D × H, mm.

00.5 m1 m1.5 m2 m60–120 kVA400 × 960 × 1,193160–200 kVA600 × 1,000 × 1,600
  • 60–120 kVA 400 × 960 × 1,193 mm · 145–163 kg
  • 160–200 kVA 600 × 1,000 × 1,600 mm · 310–312 kg

Questions

Questions people ask

Can an IST7 60–200 kVA be upgraded later?

Yes, selected models: the IST7-80 is upgraded to 100 or 120 kVA, the IST7-100 to 120 kVA and the IST7-160 to 200 kVA, by setting the capacity from the display. Hardware and footprint stay the same.

How many IST7 units can run in parallel?

Up to 8 units, for capacity or N+X redundancy, reaching 1.6 MW with 8 × IST7-200. BSC synchronisation supports dual-bus architectures, current sharing between units is within 5%, and the units can share a common battery bank.

How efficient is the IST7 60–200 kVA?

Peak AC/AC efficiency is 96.5% in online double conversion and 99% in ECO mode, with output power factor 1 (kVA = kW). At a 100 kW load, AEC's indicative calculation gives 3.6 kW of losses (≈ € 6,350 per year) in double conversion against 1.0 kW (≈ € 1,770) in ECO.

Which batteries does the IST7 60–200 kVA use?

A string of 28–48 × 12 V blocks set on site, VRLA or lithium with the BMS card: default ±192 V (32 blocks) on IST7-60/80 and ±216 V (36 blocks) on IST7-100…200. The maximum charge current is 30 A on 60–120 kVA and 60 A on 160–200 kVA, and AEC BB5 to BB8 cabinets are ordered with the UPS in one code.

What are the dimensions, weights and clearances?

The 60–120 kVA cabinet measures 400 × 960 × 1193 mm (153–167 kg) with bottom cable entry; the 160–200 kVA cabinet 600 × 1000 × 1600 mm (294–296 kg) with top cable entry. Leave at least 800 mm at the front, rear and above: cooling air enters at the front and leaves at the rear.

Which communication interfaces does it have?

RS485, Modbus RTU, RS232, EPO, USB and 4 dry-contact inputs / 3 outputs with assignable functions are standard. Options include an SNMP card with a temperature and humidity sensor port, dry-contact expansion (+3 inputs, +2 outputs) and a BMS card for lithium batteries.

What warranty and service come with the IST7 60–200 kVA?

A 3-year warranty, extendable with a maintenance contract, and 24/7 technical assistance by phone and WhatsApp. The UPS stores up to 10,000 events and wave captures that are exported to USB for the service report.