Pick the AEC configuration and give the room: Room fit places the UPS and its battery cabinets to the millimetre with the manual's clearances, the HD 60364-7-729 operating gangway, door swing, cable entry, floor load, heat and ventilation, and says what fails and how to fix it.

Room fit

Loading Room fit…

How it works

The room, checked before the site.

  1. The configurationThe AEC UPS with its battery cabinets, as ordered.
  2. The roomSize, door, windows, obstacles and height.
  3. The layoutUPS and cabinets to the millimetre, with the manual's clearances.
  4. The checksWhat does not fit and how to fix it, in plan and 3D.
7checks: clearances, gangway, doors, floor, heat, air, cables
HD 60364-7-729the operating gangway
EN IEC 62485-2battery ventilation
mmto the millimetre, plan and 3D

Questions

What people ask

How much space does a UPS need in front?

What the range's manual asks for, and at least the operating gangway of HD 60364-7-729: 700 mm from the cabinet to the wall, 600 mm from the breaker handles, 500 mm past an open door or a withdrawn module. Room fit draws and checks both.

Does the battery room need ventilation?

Yes, with lead-acid batteries: EN IEC 62485-2 gives the air flow from the number of cells and the Ah, and the opening area for natural ventilation. Room fit works it out for the cabinets chosen.

Can I get the PDF report or the CAD drawing?

Yes, with the project: ask AEC and an engineer sends the PDF report and the drawing for CAD.

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need: we answer with the model and the batteries that fit.