OZ Power VRLA 12 V AGM VRLA batteries for UPS, 9–200 Ah

VRLA

OZ Power are 12 V AGM VRLA lead-acid batteries for UPS in seven sizes from 9 to 200 Ah: thin pressed plates for the short discharges a UPS makes, pure lead with self-discharge under 3% a month, and 99% recombination with no topping up. 12-year design life for the 40 to 200 Ah models.

9–200 Ahseven 12 V models
−20…60 °Cdischarge temperature
2000 A5 s discharge, 200 Ah
< 3%self-discharge a month
AEC OZ Power VRLA

Overview

Key facts

Range
9–200 Ah
Voltage
12 V
Dimensions W × D × H
151 × 65 × 94 to 522 × 240 × 219 mm

Hands on

Open the OZ Power VRLA.

The cabinets at one scale, beside a 2 m rule.

AEC OZ Power VRLA · OZ-12100, 100 Ah

Models

Which OZ Power VRLA fits your load?

Every rating has its own page: that model's technical data, ordering codes, batteries and the questions people ask.

OZ Power 12 V 9 Ah9 AhThe OZ Power 12 V 9 Ah is a sealed AGM valve-regulated lead-acid block, 151 × 65 × 94 mm and 2.3 kg, the battery inside AEC single-phase UPS.151 × 65 × 94 mmSize2.3 kgWeightSee the model OZ Power 12 V 24 Ah24 AhThe OZ Power 12 V 24 Ah is a sealed AGM VRLA block of the general-purpose series, 166 × 175 × 125 mm and 7.0 kg, used in the BB5 cabinet.166 × 175 × 125 mmSize7.0 kgWeightSee the model OZ Power 12 V 40 Ah40 AhThe OZ Power 12 V 40 Ah is the first block of the long-life series: sealed AGM VRLA, 197 × 166 × 170 mm, 11.5 kg, 12-year design life in float.197 × 166 × 170 mmSize11.5 kgWeightSee the model OZ Power 12 V 60 Ah60 AhThe OZ Power 12 V 60 Ah is a long-life sealed AGM VRLA block, 230 × 138 × 211 mm and 16.5 kg, used in the BB6 and BB7 cabinets.230 × 138 × 211 mmSize16.5 kgWeightSee the model OZ Power 12 V 80 Ah80 AhThe OZ Power 12 V 80 Ah is a long-life sealed AGM VRLA block, 260 × 169 × 211 mm and 22.0 kg, used in the BB7 and BB8 cabinets.260 × 169 × 211 mmSize22.0 kgWeightSee the model OZ Power 12 V 100 Ah100 AhThe OZ Power 12 V 100 Ah is a long-life sealed AGM VRLA block, 328 × 172 × 215 mm and 28.5 kg, the largest battery in the standard AEC cabinets.328 × 172 × 215 mmSize28.5 kgWeightSee the model OZ Power 12 V 200 Ah200 AhThe OZ Power 12 V 200 Ah is the largest long-life AGM VRLA block of the range: 522 × 240 × 219 mm, 58.0 kg, supplied for large systems on request.522 × 240 × 219 mmSize58.0 kgWeightSee the model

Datasheet

Datasheet OZ Power VRLA.

Every model side by side: keep only what differs, take it as CSV or print it.

OZ Power VRLA · Technical data
Model9 Ah24 Ah40 Ah60 Ah80 Ah100 Ah200 Ah
OZ Power 12 V
Capacity C10 · C208.4 · 9.0 Ah22.4 · 24.0 Ah40.0 · 42.4 Ah55.0 · 58.2 Ah80.0 · 84.8 Ah100 · 106 Ah200 · 212 Ah
Capacity C3 · C56.8 · 7.7 Ah18.0 · 20.4 Ah30.0 · 34.0 Ah41.4 · 46.8 Ah60.0 · 68.0 Ah75.0 · 85.0 Ah150 · 170 Ah
L × W × H (mm)151 × 65 × 94166 × 175 × 125197 × 166 × 170230 × 138 × 211260 × 169 × 211328 × 172 × 215522 × 240 × 219
Total height (mm)100125170216216220224
Weight (approx.)2.3 kg7.0 kg11.5 kg16.5 kg22.0 kg28.5 kg58.0 kg
Internal resistance≤ 22 mΩ≤ 16 mΩ≤ 10 mΩ≤ 6.0 mΩ≤ 6.0 mΩ≤ 5.5 mΩ≤ 3.5 mΩ
TerminalF2F13 (M5)F11 (M6)F11 (M6)F11 (M6)F12 (M8)F10 (M8)
Max. discharge (5 s)90 A240 A400 A550 A800 A1000 A2000 A
Short-circuit current450 A850 A920 A1160 A1840 A2150 A3430 A
Max. charge current2.7 A7.2 A12.0 A16.5 A24.0 A30.0 A60.0 A
Design life (float)6–8 years6–8 years12 years12 years12 years12 years12 years
Used inIST3 · IST3-J · IST9 · IST7 · BB1–BB5 · BBJ · BBJ2BB5BB5BB6BB7 · BB8BB7 · BB8on request

Values at 25 °C, fully charged, from the battery data sheets; C3–C20 = capacity at 3, 5, 10 and 20 h discharge (C3, C5 and C10 to 1.80 V/cell, C20 to 1.75 V/cell). Weight tolerance ± 5%. Terminal: default type, others optional. Specifications are subject to change without notice.

Full technical details21 sections of the EMEA 2026 catalogue: functions, panel, connections, diagrams and ordering codes

Why OZ Power VRLA

01Thin pressed platesMore plate surface in the same block: higher power for the short, high-rate discharges of a UPS.
02Pure leadHigh-purity lead keeps grid corrosion and self-discharge low: long float life, long storage.
0399% recombinationOxygen and hydrogen recombine into water inside the cell: no water loss, no maintenance.
04AGM glass matElectrolyte fully absorbed in the glass mat: no free acid, no leakage, even ageing block to block.
05Low self-dischargeBelow 3% per month at 25 °C: up to 6 months of storage before recharging.
06Safe ABS caseUL94-HB container, flame-retardant UL94-V0 available. Non-dangerous goods for road, rail and air.
0799% recyclableAt end of life the lead, the acid and the plastics of the block are recovered: 99% of the battery, as the OZ Power catalogue states.

TECHNOLOGY

Sealed power, built to last

Thin pressed plates, pure lead and 99% gas recombination: AGM technology that delivers high power and stays free of maintenance for its whole life.

OZ Power VRLA · Sealed power, built to last
  • How AGM recombination works: oxygen produced at the positive plate crosses the glass mat, which holds the electrolyte, and goes back to water at the negative plate.
  • 99% of the gas produced while charging recombines inside the cell: the valve opens only on overpressure, no water is lost.
  • Two series: 9 · 24 Ah general purpose, 6–8 years design life; 40–200 Ah long life, 12 years design life (float service, 25 °C).
  • Data-sheet standards of the 12 V range: IEC (international), JIS (Japan), BS (British). CE marked.

THE RANGE

Seven models, 9 to 200 Ah

From the 9 Ah block inside every single-phase UPS to the 200 Ah block for long backup, all 12 V AGM VRLA.

OZ Power VRLA · OZ Power 12 V block
OZ Power VRLA · OZ-1280 block
OZ Power VRLA · OZ-12100 block
OZ Power VRLA · OZ-12200 block
  • Values at 25 °C, fully charged, from the battery data sheets; C3–C20 = capacity at 3, 5, 10 and 20 h discharge (C3, C5 and C10 to 1.80 V/cell, C20 to 1.75 V/cell).
  • Weight tolerance ± 5%. Terminal: default type, others optional.

PERFORMANCE

Power when it matters

Constant power data for UPS sizing, capacity at every discharge rate, and the conditions that make a battery last.

  • Constant power discharge: watts per 12 V block (6 cells), 25 °C, end voltage 1.75 V per cell; average values from the data sheets. UPS backup time also depends on UPS efficiency and battery voltage: AEC sizes every system.
  • Capacity by discharge time (3 h, 5 h, 10 h, 20 h) shown relative to the 10 h capacity.
  • Temperature and life: 25 °C 100% of design life; 35 °C about 43%; 45 °C about 19%. Battery life halves about every 8 °C above 25 °C.
  • Charging at 25 °C: float 13.5–13.8 V per battery, compensation −3 mV/°C/cell; cycle 14.6–14.8 V per battery, compensation −4 mV/°C/cell.
  • Operating range: discharge −20 to 60 °C, charge 0 to 50 °C; best life at 25 ± 5 °C.
  • Charge current: up to about 0.3 C; AEC UPS and cabinets charge in float mode.
  • Storage: recharge every 6 months, or when the open-circuit voltage falls below 12.6 V.
  • Replacement: same model, capacity and batch across the whole string.
Power when it matters
W per 12 V block, 1.75 V/cell9 Ah24 Ah40 Ah60 Ah80 Ah100 Ah200 Ah
15 min161404671931131516933217
30 min10025042759383810792137
60 min571442533475056311263

OZ POWER · GENERAL PURPOSE SERIES

12 V 9 Ah · constant power, W per 12 V block, 25 °C

AGM VRLA battery · design life 6–8 years in float · used in IST3 · IST3-J · IST9 · IST7 · BB1–BB5 · BBJ.

OZ Power VRLA · 12 V 9 Ah · constant power, W per 12 V block, 25 °C
  • Dimensions L × W × H 151 × 65 × 94 mm; total height 100 mm.
  • Weight 2.3 kg (approx.); internal resistance ≤ 22 mΩ.
  • Terminal F2 (F1 optional).
  • Max. discharge current (5 s) 90 A; short-circuit current 450 A; max. charge current 2.7 A.
  • Float at 25 °C: 13.5–13.8 V (−3 mV/°C/cell); cycle use at 25 °C: 14.6–14.8 V (−4 mV/°C/cell).
  • Capacity by discharge time: 3 h 6.75 Ah · 5 h 7.65 Ah · 10 h 8.41 Ah · 20 h 9 Ah.
  • Capacity rated at 20 h to 1.75 V/cell, 25 °C. 6 cells per block; ABS case UL94-HB (V0 optional).
  • Thin pressed plates · pure lead · 99% gas recombination.
  • Constant power at 1.75 V/cell: 161 W for 15 min, 56.8 W for 1 h, 26.9 W for 3 h, 10.1 W for 10 h.
  • Average values from the battery data sheet, battery fully charged. End voltage per cell and per 12 V block; 1.75 V/cell (10.5 V) is the usual UPS end voltage.
12 V 9 Ah · constant power, W per 12 V block, 25 °C
End V/cell · V/block5 min10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V35025118511062.038.429.123.619.612.810.55.50
1.65 V · 9.9 V32924217910760.237.328.323.119.212.710.45.50
1.70 V · 10.2 V30422717010358.636.327.722.518.812.510.25.40
1.75 V · 10.5 V27821116199.756.835.226.922.018.412.410.15.30
1.80 V · 10.8 V24919515196.355.034.126.221.517.912.210.05.30
1.85 V · 11.1 V20216212783.849.631.424.320.016.811.59.405.00

OZ POWER · GENERAL PURPOSE SERIES

12 V 9 Ah · constant current, A, 25 °C

Constant current discharge of the 12 V 9 Ah block, by end voltage and discharge time.

12 V 9 Ah · constant current, A, 25 °C
End V/cell · V/block5 min10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V35.224.617.610.15.503.382.542.051.701.090.890.47
1.65 V · 9.9 V32.723.316.99.725.313.272.461.991.651.080.880.46
1.70 V · 10.2 V29.521.415.89.295.143.162.391.941.611.060.860.46
1.75 V · 10.5 V26.419.614.78.884.953.052.321.891.571.050.850.45
1.80 V · 10.8 V23.217.713.68.484.762.942.251.831.531.030.840.45
1.85 V · 11.1 V18.414.511.27.314.272.692.081.711.430.970.790.42

OZ POWER · GENERAL PURPOSE SERIES

12 V 24 Ah · constant power, W per 12 V block, 25 °C

AGM VRLA battery · design life 6–8 years in float · used in BB5.

  • Dimensions L × W × H 166 × 175 × 125 mm; total height 125 mm.
  • Weight 7.0 kg (approx.); internal resistance ≤ 16 mΩ.
  • Terminal F13 · M5 (F3 optional).
  • Max. discharge current (5 s) 240 A; short-circuit current 850 A; max. charge current 7.2 A.
  • Float at 25 °C: 13.5–13.8 V (−3 mV/°C/cell); cycle use at 25 °C: 14.6–14.8 V (−4 mV/°C/cell).
  • Capacity by discharge time: 3 h 18 Ah · 5 h 20.4 Ah · 10 h 22.4 Ah · 20 h 24 Ah.
  • Capacity rated at 20 h to 1.75 V/cell, 25 °C. 6 cells per block; ABS case UL94-HB (V0 optional).
  • Thin pressed plates · pure lead · 99% gas recombination.
  • Constant power at 1.75 V/cell: 404 W for 15 min, 144 W for 1 h, 71.9 W for 3 h, 26.9 W for 10 h.
  • Average values from the battery data sheet, battery fully charged. End voltage per cell and per 12 V block; 1.75 V/cell (10.5 V) is the usual UPS end voltage.
12 V 24 Ah · constant power, W per 12 V block, 25 °C
End V/cell · V/block5 min10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V86062346427715710277.662.952.434.127.914.8
1.65 V · 9.9 V80960145026815299.675.561.451.233.827.614.5
1.70 V · 10.2 V74756342825914896.873.760.050.033.427.214.4
1.75 V · 10.5 V68452540425014493.971.958.748.933.026.914.2
1.80 V · 10.8 V61348337824213991.069.957.247.832.526.614.1
1.85 V · 11.1 V49740231821012683.864.953.444.830.625.113.4

OZ POWER · GENERAL PURPOSE SERIES

12 V 24 Ah · constant current, A, 25 °C

Constant current discharge of the 12 V 24 Ah block, by end voltage and discharge time.

12 V 24 Ah · constant current, A, 25 °C
End V/cell · V/block5 min10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V86.561.144.225.413.99.006.775.464.532.912.371.25
1.65 V · 9.9 V80.457.842.224.413.48.726.565.324.412.882.341.23
1.70 V · 10.2 V72.653.239.623.313.08.436.385.174.292.842.301.22
1.75 V · 10.5 V65.048.736.822.312.58.136.195.044.192.802.271.20
1.80 V · 10.8 V57.144.134.021.312.17.846.004.894.082.752.241.19
1.85 V · 11.1 V45.336.028.218.310.87.195.554.553.802.582.111.13

OZ POWER · LONG LIFE SERIES

12 V 40 Ah · constant power, W per 12 V block, 25 °C

AGM VRLA battery · design life 12 years in float · used in BB5.

OZ Power VRLA · 12 V 40 Ah · constant power, W per 12 V block, 25 °C
  • Dimensions L × W × H 197 × 166 × 170 mm; total height 170 mm.
  • Weight 11.5 kg (approx.); internal resistance ≤ 10 mΩ.
  • Terminal F11 · M6 (F4 optional).
  • Max. discharge current (5 s) 400 A; short-circuit current 920 A; max. charge current 12.0 A.
  • Float at 25 °C: 13.5–13.8 V (−3 mV/°C/cell); cycle use at 25 °C: 14.6–14.8 V (−4 mV/°C/cell).
  • Capacity by discharge time: 3 h 30 Ah · 5 h 34 Ah · 10 h 40 Ah · 20 h 42.4 Ah.
  • Capacity rated at 10 h to 1.80 V/cell, 25 °C. 6 cells per block; ABS case UL94-HB (V0 optional).
  • Thin pressed plates · pure lead · 99% gas recombination.
  • Constant power at 1.75 V/cell: 671 W for 15 min, 253 W for 1 h, 120 W for 3 h, 48.0 W for 10 h.
  • Average values from the battery data sheet, battery fully charged. End voltage per cell and per 12 V block; 1.75 V/cell (10.5 V) is the usual UPS end voltage.
12 V 40 Ah · constant power, W per 12 V block, 25 °C
End V/cell · V/block5 min10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V1,28397677047327516612910287.059.449.826.1
1.65 V · 9.9 V1,27094074745826816112699.685.258.949.325.7
1.70 V · 10.2 V1,22288171044326015712397.283.458.148.525.4
1.75 V · 10.5 V1,16282167142725315212095.481.657.448.025.1
1.80 V · 10.8 V1,07775662841324414711693.079.856.647.424.9
1.85 V · 11.1 V96562952935922013610886.474.453.244.723.7

OZ POWER · LONG LIFE SERIES

12 V 40 Ah · constant current, A, 25 °C

Constant current discharge of the 12 V 40 Ah block, by end voltage and discharge time.

12 V 40 Ah · constant current, A, 25 °C
End V/cell · V/block5 min10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V12495.773.443.424.414.611.38.877.555.074.222.21
1.65 V · 9.9 V12090.470.241.623.614.110.98.637.355.014.172.17
1.70 V · 10.2 V11483.265.739.822.813.610.68.397.164.944.112.15
1.75 V · 10.5 V10676.261.238.022.013.210.38.186.984.874.052.12
1.80 V · 10.8 V97.069.056.536.421.212.710.07.946.804.794.002.10
1.85 V · 11.1 V85.456.446.931.319.011.69.247.386.344.493.771.99

OZ POWER · LONG LIFE SERIES

12 V 60 Ah · constant power, W per 12 V block, 25 °C

AGM VRLA battery · design life 12 years in float · used in BB6.

  • Dimensions L × W × H 230 × 138 × 211 mm; total height 216 mm.
  • Weight 16.5 kg (approx.); internal resistance ≤ 6.0 mΩ.
  • Terminal F11 · M6 (F15 optional).
  • Max. discharge current (5 s) 550 A; short-circuit current 1160 A; max. charge current 16.5 A.
  • Float at 25 °C: 13.5–13.8 V (−3 mV/°C/cell); cycle use at 25 °C: 14.6–14.8 V (−4 mV/°C/cell).
  • Capacity by discharge time: 3 h 41.4 Ah · 5 h 46.8 Ah · 10 h 55 Ah · 20 h 58.2 Ah.
  • Capacity rated at 10 h to 1.80 V/cell, 25 °C. 6 cells per block; ABS case UL94-HB (V0 optional).
  • Thin pressed plates · pure lead · 99% gas recombination.
  • Constant power at 1.75 V/cell: 931 W for 15 min, 347 W for 1 h, 165 W for 3 h, 66.0 W for 10 h.
  • Average values from the battery data sheet, battery fully charged. End voltage per cell and per 12 V block; 1.75 V/cell (10.5 V) is the usual UPS end voltage.
12 V 60 Ah · constant power, W per 12 V block, 25 °C
End V/cell · V/block5 min10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V1,8201,3691,07065637922717814012081.668.435.9
1.65 V · 9.9 V1,8011,3191,03863736822117313711881.067.835.3
1.70 V · 10.2 V1,7321,23698661535821516913411579.866.635.0
1.75 V · 10.5 V1,6471,15293159334720916513111279.266.034.6
1.80 V · 10.8 V1,5261,06187257333620216012811078.065.434.3
1.85 V · 11.1 V1,36788373449930318714911910373.261.232.6

OZ POWER · LONG LIFE SERIES

12 V 60 Ah · constant current, A, 25 °C

Constant current discharge of the 12 V 60 Ah block, by end voltage and discharge time.

12 V 60 Ah · constant current, A, 25 °C
End V/cell · V/block5 min10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V17613410260.233.620.015.512.210.46.975.803.04
1.65 V · 9.9 V17012797.557.832.519.415.011.910.16.905.732.99
1.70 V · 10.2 V16211791.355.331.418.714.611.59.846.795.652.95
1.75 V · 10.5 V15110785.052.830.218.114.211.29.606.695.572.91
1.80 V · 10.8 V13896.878.550.529.117.413.810.99.356.585.502.89
1.85 V · 11.1 V12179.165.143.526.116.012.710.28.726.185.182.74

OZ POWER · LONG LIFE SERIES

12 V 80 Ah · constant power, W per 12 V block, 25 °C

AGM VRLA battery · design life 12 years in float · used in BB7 · BB8.

  • Dimensions L × W × H 260 × 169 × 211 mm; total height 216 mm.
  • Weight 22.0 kg (approx.); internal resistance ≤ 6.0 mΩ.
  • Terminal F11 · M6 (F15 · L4 optional).
  • Max. discharge current (5 s) 800 A; short-circuit current 1840 A; max. charge current 24.0 A.
  • Float at 25 °C: 13.5–13.8 V (−3 mV/°C/cell); cycle use at 25 °C: 14.6–14.8 V (−4 mV/°C/cell).
  • Capacity by discharge time: 3 h 60 Ah · 5 h 68 Ah · 10 h 80 Ah · 20 h 84.8 Ah.
  • Capacity rated at 10 h to 1.80 V/cell, 25 °C. 6 cells per block; ABS case UL94-HB (V0 optional).
  • Thin pressed plates · pure lead · 99% gas recombination.
  • Constant power at 1.75 V/cell: 1,315 W for 15 min, 505 W for 1 h, 239 W for 3 h, 96.0 W for 10 h.
  • Average values from the battery data sheet, battery fully charged. End voltage per cell and per 12 V block; 1.75 V/cell (10.5 V) is the usual UPS end voltage.
12 V 80 Ah · constant power, W per 12 V block, 25 °C
End V/cell · V/block10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V1,8741,51092655133125920417511999.652.1
1.65 V · 9.9 V1,8051,46589953532225119917011898.451.4
1.70 V · 10.2 V1,6931,39286852131324619516711697.250.8
1.75 V · 10.5 V1,5771,31583850530423919116311596.050.3
1.80 V · 10.8 V1,4531,23180948829523318616011394.849.9
1.85 V · 11.1 V1,2081,03670444127121717314910689.447.4

OZ POWER · LONG LIFE SERIES

12 V 80 Ah · constant current, A, 25 °C

Constant current discharge of the 12 V 80 Ah block, by end voltage and discharge time.

12 V 80 Ah · constant current, A, 25 °C
End V/cell · V/block10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V18414485.048.929.122.617.715.110.18.444.41
1.65 V · 9.9 V17413881.647.228.221.917.314.710.08.344.34
1.70 V · 10.2 V16012978.045.727.321.316.814.39.878.214.29
1.75 V · 10.5 V14612074.644.026.320.616.414.09.748.104.24
1.80 V · 10.8 V13211171.342.325.420.015.913.69.578.004.20
1.85 V · 11.1 V10891.961.438.023.218.514.812.78.997.533.99

OZ POWER · LONG LIFE SERIES

12 V 100 Ah · constant power, W per 12 V block, 25 °C

AGM VRLA battery · design life 12 years in float · used in BB7 · BB8.

  • Dimensions L × W × H 328 × 172 × 215 mm; total height 220 mm.
  • Weight 28.5 kg (approx.); internal resistance ≤ 5.5 mΩ.
  • Terminal F12 · M8 (F5 optional).
  • Max. discharge current (5 s) 1000 A; short-circuit current 2150 A; max. charge current 30.0 A.
  • Float at 25 °C: 13.5–13.8 V (−3 mV/°C/cell); cycle use at 25 °C: 14.6–14.8 V (−4 mV/°C/cell).
  • Capacity by discharge time: 3 h 75 Ah · 5 h 85 Ah · 10 h 100 Ah · 20 h 106 Ah.
  • Capacity rated at 10 h to 1.80 V/cell, 25 °C. 6 cells per block; ABS case UL94-HB (V0 optional).
  • Thin pressed plates · pure lead · 99% gas recombination.
  • Constant power at 1.75 V/cell: 1,693 W for 15 min, 631 W for 1 h, 299 W for 3 h, 120 W for 10 h.
  • Average values from the battery data sheet, battery fully charged. End voltage per cell and per 12 V block; 1.75 V/cell (10.5 V) is the usual UPS end voltage.
12 V 100 Ah · constant power, W per 12 V block, 25 °C
End V/cell · V/block10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V2,3651,9451,19368941432325621814912465.4
1.65 V · 9.9 V2,2781,8871,15866940331425021414712364.2
1.70 V · 10.2 V2,1351,7931,11865239230724420914512163.6
1.75 V · 10.5 V1,9901,6931,07963138029923820414312063.0
1.80 V · 10.8 V1,8321,5861,04261136829223219914211962.4
1.85 V · 11.1 V1,5251,33490755133927121718713311259.2

OZ POWER · LONG LIFE SERIES

12 V 100 Ah · constant current, A, 25 °C

Constant current discharge of the 12 V 100 Ah block, by end voltage and discharge time.

12 V 100 Ah · constant current, A, 25 °C
End V/cell · V/block10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V23218511061.136.428.222.218.912.710.55.52
1.65 V · 9.9 V21917710559.035.227.321.618.412.510.45.43
1.70 V · 10.2 V20216610057.134.126.621.017.912.310.35.36
1.75 V · 10.5 V18515496.055.032.925.820.417.412.210.15.30
1.80 V · 10.8 V16714391.852.931.725.019.917.012.010.05.25
1.85 V · 11.1 V13711879.147.429.123.118.515.911.29.414.98

OZ POWER · LONG LIFE SERIES

12 V 200 Ah · constant power, W per 12 V block, 25 °C

AGM VRLA battery · design life 12 years in float · used in large systems, on request.

  • Dimensions L × W × H 522 × 240 × 219 mm; total height 224 mm.
  • Weight 58.0 kg (approx.); internal resistance ≤ 3.5 mΩ.
  • Terminal F10 · M8 (F16 optional).
  • Max. discharge current (5 s) 2000 A; short-circuit current 3430 A; max. charge current 60.0 A.
  • Float at 25 °C: 13.5–13.8 V (−3 mV/°C/cell); cycle use at 25 °C: 14.6–14.8 V (−4 mV/°C/cell).
  • Capacity by discharge time: 3 h 150 Ah · 5 h 170 Ah · 10 h 200 Ah · 20 h 212 Ah.
  • Capacity rated at 10 h to 1.80 V/cell, 25 °C. 6 cells per block; ABS case UL94-HB (V0 optional).
  • Thin pressed plates · pure lead · 99% gas recombination.
  • Constant power at 1.75 V/cell: 3,217 W for 15 min, 1,263 W for 1 h, 599 W for 3 h, 240 W for 10 h.
  • Average values from the battery data sheet, battery fully charged. End voltage per cell and per 12 V block; 1.75 V/cell (10.5 V) is the usual UPS end voltage.
12 V 200 Ah · constant power, W per 12 V block, 25 °C
End V/cell · V/block10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V4,4813,6952,3631,378828646511436297249130
1.65 V · 9.9 V4,3163,5852,2931,338805629499427295246128
1.70 V · 10.2 V4,0463,4082,2131,303783615487417290243127
1.75 V · 10.5 V3,7703,2172,1371,263759599476408287240126
1.80 V · 10.8 V3,4723,0132,0631,222736583464399283237125
1.85 V · 11.1 V2,8882,5361,7951,102678541433373266224118

OZ POWER · LONG LIFE SERIES

12 V 200 Ah · constant current, A, 25 °C

Constant current discharge of the 12 V 200 Ah block, by end voltage and discharge time.

12 V 200 Ah · constant current, A, 25 °C
End V/cell · V/block10 min15 min30 min1 h2 h3 h4 h5 h8 h10 h20 h
1.60 V · 9.6 V43935221712272.856.444.337.725.421.111.0
1.65 V · 9.9 V41533720811870.554.743.136.825.120.810.9
1.70 V · 10.2 V38231519911468.253.242.035.824.720.510.7
1.75 V · 10.5 V35029419011065.851.640.934.924.320.310.6
1.80 V · 10.8 V31727118210663.450.039.734.023.920.010.5
1.85 V · 11.1 V25922515694.958.146.236.931.722.518.810.0

BATTERY SIZING

From load to backup time

Battery data sheets give constant power per block. Divide the UPS load by the inverter efficiency and the number of blocks, then read the time in the tables.

  • 01 Power per block: P block = P load ÷ (efficiency × number of blocks). The DC efficiency of the UPS comes from its data sheet.
  • 02 Read the table: find P block in the constant power table at the end voltage of the UPS (usually 1.75 V/cell): the column gives the backup time.
  • 03 Choose the battery: pick the capacity, and if needed a second string, that reaches the backup time required. AEC checks every calculation.
  • Example: 15 kW on 32 blocks: 15 kW UPS load, 95% assumed DC → AC efficiency, 493 W per 12 V block.
  • Example only: 15 kW load, 95% efficiency assumed, one string of 32 blocks, 25 °C, end voltage 1.75 V/cell, new batteries; times interpolated in the constant power tables of this catalogue. Real backup depends on the UPS, the temperature and battery age.
  • More backup: two identical strings in parallel halve the power per block; BB8 cabinets hold two strings as standard.
  • Temperature: below 25 °C the available capacity drops; above 25 °C battery life shortens.
  • Ageing: capacity falls with age; size with a reserve so the backup holds until replacement.
From load to backup time
BatteryBackup time, 15 kW on 32 blocks
12 V 9 Ahbelow 5–10 min: not suitable for this load
12 V 24 Ah≈ 11 min
12 V 40 Ah≈ 24 min
12 V 60 Ah≈ 38 min
12 V 80 Ah≈ 62 min
12 V 100 Ah≈ 84 min
12 V 200 Ah≈ 3.8 h

SIZING SUPPORT

Send us your loads and backup time

AEC sizes the battery for your project: send the loads and the backup time required.

  • Sales: +39 02 9415 8991 · sales@aecups.com
  • Service: +39 393 080 5211 · service@aecups.com
  • www.aecups.com

Ordering codes OZ Power VRLA

CodeDescription
OZ-1209 · OZ-1224 · OZ-1240 · OZ-1260 · OZ-1280 · OZ-12100 · OZ-12200OZ Power 12 V AGM VRLA blocks: 9 · 24 · 40 · 60 · 80 · 100 · 200 Ah

Questions

Questions people ask

How long do OZ Power batteries last?

The 9 and 24 Ah general purpose models have a design life of 6–8 years, and the 40–200 Ah long life models 12 years, in float service at 25 °C. Life halves about every 8 °C above 25 °C: about 43% of design life at 35 °C and 19% at 45 °C (OZ Power data).

Do OZ Power batteries need maintenance?

No topping up: they are sealed AGM batteries in which 99% of the gas recombines into water, with the electrolyte absorbed in the glass mat and no free acid. Self-discharge is below 3% per month at 25 °C, so they can be stored up to 6 months before recharging.

What backup time do OZ Power batteries give?

In AEC's example of a 15 kW load on one string of 32 blocks, the backup is about 11 minutes with 24 Ah and 24 minutes with 40 Ah. It is 38 minutes with 60 Ah, 62 minutes with 80 Ah, 84 minutes with 100 Ah and 3.8 hours with 200 Ah; 9 Ah is not suitable for this load. Real backup depends on the UPS, temperature and battery age, and AEC checks every calculation.

How is a battery string sized for a UPS?

Divide the UPS load by the inverter efficiency and the number of blocks to get the power per block, then read the backup time in the constant power table at the UPS end voltage, usually 1.75 V per cell. Two identical strings in parallel halve the power per block for more backup.

What are the dimensions and weights of the OZ Power range?

The 12 V 9 Ah block measures 151 × 65 × 94 mm and weighs 2.3 kg; the 200 Ah block 522 × 240 × 219 mm and 58.0 kg. In between, the 40 Ah is 197 × 166 × 170 mm (11.5 kg) and the 100 Ah 328 × 172 × 215 mm (28.5 kg). Weights are approximate, with ± 5% tolerance.

Which AEC cabinets use which OZ Power battery?

The 9 Ah block is used inside AEC UPS and in BB1–BB5 and BBJ cabinets; 24 and 40 Ah in the BB5; 60 Ah in BB6 and BB7; 80 and 100 Ah in BB7 and BB8. The 200 Ah block is for large systems, on request.

What charging voltage and temperatures do OZ Power batteries need?

At 25 °C, float charge is 13.5–13.8 V per battery (−3 mV/°C/cell) and cycle charge 14.6–14.8 V (−4 mV/°C/cell), with charge current up to about 0.3 C. They discharge from −20 to 60 °C and charge from 0 to 50 °C, with the best life at 25 ± 5 °C.

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC OZ Power VRLA 9–200 Ah: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.