Modular UPS · 400 V

IST6-120 Modular UPS 30–120 kVA, 30 kVA modules

VRLAOnline double conversion

The AEC IST6-120 is a modular online double-conversion UPS from 30 to 120 kVA in one cabinet: it grows in 30 kVA steps with hot-swappable 2U power modules, and the fifth slot takes a module for N+1 redundancy. For 400 V supplies, with 97% efficiency in double conversion and up to 99% in ECO mode.

30→120kVA in 30 kVA steps
N+1fifth slot for redundancy
97%double-conversion efficiency
Hot-swapmodules replaced online
AEC IST6-120, rendered from its 3D modelDrag to turn

In 3D

Look around the IST6-120

Drag it round, swipe on a phone or use the arrow keys. X-ray makes the enclosure see-through, so you can see what sits behind the panels.

Rendered from AEC's 3D model of the IST6 120 kVA. The full 3D view zooms in, opens the unit and names every part.

Hands on

Open the IST6 120 kVA yourself.

Click the unit: the door opens, then a module comes out. Drag to move it by hand. The 3D shows every part.

AEC IST6 120 kVA, closed

Every part in 3D

Efficiency

How efficient is the AEC IST6-120 at your load?

AC/AC efficiency of each operating mode against the load: AEC's measured curves where they exist, elsewhere the typical curve derived from the datasheet figure by AEC's method. The losses and their cost follow the curve at the load you choose: drag along the chart or move the slider.

97%50% · Typical curve, derived from the datasheet efficiency of 97% (AEC method)

Filled points: measured by AEC (AC/AC technical datasheet). Hollow points: a typical curve, the shape of the most similar measured curve (same technology and size) moved to the range's datasheet efficiency: η(load) = reference curve + (datasheet figure − its highest point), AEC's method. Dashed lines: one figure without a load (ECO, W-ECO). Between points the efficiency is read on a straight line; beyond them, the nearest end. Losses = P × (1/η − 1).

Load
—
Lost as heat
—
Energy lost in a year, 24/7
—
Its cost in a year at € per kWh
—
The catalogue's examples use €0.20 per kWh.
Where each figure comes from
ModeEfficiencyKindModelsSource
Online, double conversion25%: 96.4% · 50%: 97% · 75%: 96.7% · 100%: 96.4%Typical curve, derived from the datasheet efficiency of 97% (AEC method)allAEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape)
ECO99%Datasheet figure, load not statedall

EMEA 2026 catalogue figures: Online, double conversion up to 97% · ECO up to 99%.

The display

The IST6 30–120 kVA display

The real display, drawn by AEC's own simulator: pick a UPS state (normal, battery, bypass) or a main page.

UPS state
IST6 30–120 kVA: Normal operation

IST6 30–120 kVA · the real display

Normal operation

Main pages

What is what

Inside the IST6-120, part by part.

Each number on the picture is named in the list.

Front, door open

IST6 120 kVA with the front door open: modules, control box and switches
Everything is reached from the front: power modules, system control box and the four switches. Cables enter from the bottom (top entry with an accessory).
  1. Power modules30 kVA each, 2U, hot-swap: rectifier, inverter and battery converter in every module.
  2. System control boxTwo control cards, monitor card, SNMP and expansion slots: 4 dry-contact inputs and 3 outputs (7 + 5 with the expansion card), Modbus, RS232, RS485, 2 EPO inputs (NO and NC).
  3. Battery cold startStarts the UPS from the battery when there is no mains and no bypass.
  4. Mains switchThe rectifier's mains supply.
  5. SPD and SPD switchOptional class C surge protection device with its own switch, inside the cabinet.
  6. Output switchTo the load.
  7. Bypass switchThe static bypass supply.
  8. Maintenance bypass switchManual bypass with no switching time, for service with the load running.

Overview

Key facts

Power range
30–120 kVA
Input / output
3/3 · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L
Efficiency
97% double conversion · up to 99% ECO
Battery
±168 … ±276 V DC · ±14 … ±23 × 12 V (default ±16; below ±16 load 80%)
Display
7" colour touch screen
Communication
Modbus · RS232 · RS485 · 4 dry-contact inputs, 3 outputs
Network card
SNMP card (optional)
Parallel
with parallel kit, ring cables; BSC dual bus
Warranty
3 years
Dimensions W × D × H
600 × 860 × 2000 mm

Datasheet

Datasheet IST6-120.

Every model side by side: keep only what differs, take it as CSV or print it.

IST6-120 · Technical data
ModelIST6-120
General
ModelIST6-120 with IST6-30-J power modules
Rated power30 to 120 kVA / kW in 30 kVA steps (1–4 modules) + 1 redundancy slot
Topologyonline double conversion, modular, hot-swap power modules, removable bypass module
Input
Connection · voltage3 ph + N + PE · 220 / 230 / 240 V L-N
Voltage range176–280 V full power · 80–176 V derated (linear load)
Frequency · power factor · THDi40–70 Hz · ≥ 0.99 · ≤ 2% resistive, ≤ 3% non-linear full load
Bypass220 / 230 / 240 V L-N; synchronisation 50 / 60 Hz ± 6 Hz
Battery
Voltage · blocks±168 … ±276 V DC · ±14 … ±23 × 12 V (default ±16; below ±16 load 80%)
Charging current10 A × number of modules (max.)
Functionscold start · standard / deep test · common battery · lithium with BMS card
Output
Connection · voltage3 ph + N + PE · 220 / 230 / 240 V L-N, 380 / 400 / 415 V L-L
Power factor · THDv1 · ≤ 1% linear, ≤ 4% non-linear
Frequency · phase errortracks the bypass; 50 / 60 Hz ± 0.2% without mains · ≤ 1° (balanced load)
Transfer · dynamic response0 ms synchronised, < 15 ms not synchronised · < 5% for 0↔100% step
Inverter overload (PF 1)≤ 105% continuous · 106–110% 60 min · 111–125% 10 min · 126–150% 1 min · > 151% to bypass
Bypass overload< 130% continuous · 131–150% 5 min · 151–200% 1 s · 201–300% 100 ms
Unbalanced load100%
System
Efficiency97% double conversion · up to 99% ECO
Display · records7" colour touch screen · 10,000 events · 5 LEDs · status light bar
CommunicationModbus · RS232 · RS485 · 4 dry-contact inputs, 3 outputs · options: SNMP, dry-contact expansion, BMS card
Parallelwith parallel kit, ring cables; BSC dual bus
Environment−5 … 40 °C · 0–95% RH · ≤ 2000 m · IP20 · < 65 dB · EMC class C3
Dimensions W × D × H600 × 860 × 2000 mm · cable entry bottom (top with accessory)
Weightcabinet without power modules 195 kg · power module 24 kg · bypass module 17 kg

Data from the IST6 120 kVA user manual. Specifications are subject to change without notice.

Full technical details18 sections of the EMEA 2026 catalogue: functions, panel, connections, diagrams and ordering codes

Why IST6-120

0130→120 · Modules added as the load growsBuy the power you need today. Add 30 kVA modules in the same cabinet when the load grows, with no new footprint.
02N+1 · Redundancy built inFour power modules plus a redundancy slot for a fifth module, two system control cards (main and secondary) and a centralised bypass module.
03Hot-swap · Service without shutdownPower modules are inserted and removed online. A faulty power module is isolated automatically; normally the others carry the load.
0499% · Efficiency that pays back97% in double conversion, up to 99% in ECO mode, plus a redundancy sleep function set from the screen.
05±14…±23 · Battery set on site28 to 46 × 12 V blocks (default ±16), charging current up to 10 A per module, lead-acid or lithium with the BMS card.
067" · Easy to runColour touch screen with live power-flow topology, module-by-module data and 10,000 event records.

OPERATING COST

What efficiency means at 96 kW

Losses become heat: you pay for them at the meter and again in the room cooling.

  • IST6 120 kVA at 80% load (96 kW), 8,760 h/year, € 0.20/kWh, cooling excluded; losses = P × (1/η − 1). Indicative values.
What efficiency means at 96 kW
ModeLossesEnergy lost / yearCost / year
Online double conversion · 97%2.97 kW26,010 kWh≈ € 5,200
ECO mode · 99%0.97 kW8,490 kWh≈ € 1,700

SCALABILITY

Power added one 30 kVA module at a time

The cabinet is the same from the first module to the last: power is added by sliding a 30 kVA module into a free slot.

IST6-120 · cabinet open, power modules sliding in
IST6-120 · power module
IST6-120 · power module
IST6-120 · parallel cards wiring
  • 30, 60, 90 or 120 kVA: add 30 kVA power modules (2U) in the free slots of the same cabinet; modules slide in from the front.
  • Redundancy N+1: install one module more than the load needs; if a module stops, the others carry the load without transfer to bypass.
  • Slots are numbered 1 to 5 from bottom to top; the fifth is the redundancy slot.
  • Beyond 120 kVA: several IST6 cabinets work in parallel with the parallel kit; cables in a ring, one display can monitor the whole system, and a common battery group can be shared.
  • Codes: IST6-120 modular cabinet for up to 4 × 30 kVA power modules, supplied without modules; IST6-30-J 30 kVA / 30 kW power module, 2U, hot-swappable, order as many as the load needs; PAR - IST6 parallel kit for cabinets in parallel.
Power added one 30 kVA module at a time
Load up toModules (N)Modules for N+1
30 kVA12
60 kVA23
90 kVA34
120 kVA44 + redundancy slot

SCALE AND SLEEP

30 kVA steps, redundancy sleep at light load

Add 30 kVA modules or whole cabinets as the site grows; set redundancy and redundancy sleep from the screen.

IST6-120 · display: smart mode (module sleep) settings
IST6-120 · display: system run information
IST6-120 · display: rectifier information
  • Step size 30 kVA: one 2U module at a time, added online in a free slot.
  • 4 + 1 slots per cabinet: four power modules plus a dedicated redundancy slot.
  • More cabinets in parallel with the parallel kit, cables in a ring.
  • N+X, two redundancy levels: basic and redundant modules per cabinet and cabinets per system.
  • Redundancy sleep (Smart mode › Sleep redundancy): spare modules can sleep at light load, with a sleep cycle period (h) and a sleep safety load capacity (kVA) set on screen; an alarm warns if the load exceeds the safety load.
  • Run information shows the parameter match between cabinets and the state of both system cards; module data is shown module by module.
  • Alarms when module or cabinet redundancy is missing or insufficient, and when a system card has no redundancy.
  • Over RS485, the integrated display can monitor the other UPS of a parallel system.
  • Modules and further cabinets are added and configured by AEC service.

INSIDE THE CABINET

Every module in front, everything modular

Power modules, bypass module, control box and switches are all reached from the front of the cabinet.

  • 1 Redundancy slot: space for the N+1 module.
  • 2 Power modules 1–4: 30 kVA each, 2U, hot-swap.
  • 3 Bypass module: centralised static bypass, 3U, removable.
  • 4 System control box: two control cards, monitor card, SNMP and expansion slots.
  • 5 Battery cold start: starts the UPS from the battery with no mains and no bypass.
  • 6 Mains switch; 7 surge protection switch (optional); 8 SPD (optional surge protection device); 9 output switch; 10 bypass switch; 11 maintenance bypass switch (manual bypass with no switching time).
  • Power module: 30 kVA, 2U, 86 × 500 × 700 mm (H × W × D, with handles), 24 kg; rectifier, inverter and battery converter in each module.
  • Bypass module: centralised, 3U, 130 × 500 × 635.5 mm, 17 kg; static bypass for the whole cabinet, with its own ready switch.
  • Cabinet: 600 × 860 × 2000 mm; four switches as standard (mains, bypass, output, maintenance bypass); SPD optional; IP20.

HOT-SWAP

Replace a module with the load running

Every power module has a ready switch and three status LEDs: power modules are replaced without shutting down the UPS.

IST6-120 · cabinet, three-quarter view
IST6-120 · cabinet front with numbered parts
  • Power module front: ventilation grille, RUN / ALARM / FAULT LEDs, ready switch and handles; the bypass module has the same LEDs and ready switch.
  • LEDs: green, inverter on (flashing: standby); yellow, input voltage, fan or overload alarm; red, module fault.
  • A faulty power module is isolated automatically; normally the system continues on the other modules, with reduced redundancy.
  • No master, no slave: modules share the load equally under digital control; any module can be removed or added online.
  • Power module 2U, 24 kg; bypass module 3U, removable; 0 UPS shutdowns to add or replace a power module.
  • Wait at least 10 minutes after removal before opening a module. Replacement by AEC or authorised personnel.

ARCHITECTURE

Online double conversion in every module

N power modules (rectifier, inverter, DC/DC) and one bypass module, with a manual maintenance bypass.

IST6-120 · Online double conversion in every module
  • Mains mode: the PFC rectifier of each module builds the DC bus, the three-level inverter rebuilds a clean sine wave; the battery is charged at the same time.
  • Battery mode: with the mains abnormal, the battery converter boosts the battery onto the DC bus; the output continues without a break.
  • Bypass and maintenance: the bypass module transfers the load on overload or fault; the manual maintenance bypass keeps the load supplied during service.
  • Fully digital DSP control of inverter, synchronisation, current sharing and module logic.
  • Three-level inverter: THDv ≤ 1% on linear load, ≤ 4% on non-linear load.
  • Two control cards (main and secondary system control cards); an alarm warns if one is missing.
  • Short-circuit restart: after an output short circuit the UPS retries up to three times before protection.
  • Input power factor ≥ 0.99; input THDi ≤ 3% at non-linear full load; 0 ms transfer when synchronised; 100% unbalanced load.

SMART ENERGY

Efficiency features, from ECO to redundancy sleep

ECO mode: the load runs on the bypass while it is within the set window; outside it, the inverter takes over. Efficiency up to 99%.

IST6-120 · display: self-aging test, the power circulating from the mains through the rectifier and inverter and back through the bypass
IST6-120 · display: output settings (bypass and ECO ranges)
  • Grid-tied aging: a dedicated test state for commissioning, shown live on the home page, with its own alarms (self-load switch, time-out).
  • Output set: bypass range, ECO voltage (e.g. ±5%) and frequency (e.g. ±4%) windows; Timing ECO for scheduled operation.
  • Cooling: fan speed follows the load to extend fan life and reduce noise; a fan dedusting alarm is provided.
  • Generator mode: dry contacts start a generator on mains failure; charging can be disabled while on generator.
  • Timing ECO: ECO mode by schedule, set from the output settings.
  • 97% efficiency in double conversion, up to 99% in ECO mode.
Efficiency features, from ECO to redundancy sleep
PageSettingWhat it does
Smart modeRedundancy sleep · cycle period · safety loadSleep function for redundant modules
Smart modeGeneratorGenerator operation and charging control
Output setECO voltage and frequency rangeWindow in which the load stays on bypass
Output setTiming ECOECO mode by schedule
Dry contactStart generator · mains abnormalGenerator start and status signals

PERFORMANCE

Full power from 176 to 280 V

Full power from 176 to 280 V phase voltage; down to 80 V the UPS keeps working from the mains with derated power.

  • Linear load: rated power decreases between 80 and 186 V. Input frequency 40–70 Hz.
  • Input THDi ≤ 3% at non-linear full load.
  • Inverter overload (linear load, PF 1): ≤ 105% continuous, 106–110% 60 min, 111–125% 10 min, 126–150% 1 min; above 151% transfer to bypass at once. PF 0.9: 106–110% 60 min, above 110% to bypass at once; PF 0.8: above 105% to bypass.
  • Bypass overload: < 130% continuous, 131–150% 5 min, 151–200% 1 s, 201–300% 100 ms; above 300% immediate protection.
Full power from 176 to 280 V
Output qualityValue
Voltage220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L
THDv≤ 1% linear · ≤ 4% non-linear
Phase error≤ 1° balanced load
Frequency, no mains50 or 60 Hz ± 0.2%
Load step 0↔100%voltage change < 5%
Unbalanced load100%
Transfer0 ms synchronised · < 15 ms not synchronised

BATTERIES

One battery strategy for every site

A split battery (+ / N / −) of ±14 to ±23 blocks of 12 V: ±168 to ±276 V DC. With fewer than ±16 blocks the output load is limited to 80%.

IST6-120 · One battery strategy for every site
  • Charging current 10 A per power module (max.); 40 A with four modules.
  • Live battery information: voltage and current of each half string, remaining capacity and time, temperature, status.
  • Lithium: optional BMS expansion card, with BMS port plus charge- and discharge-disable inputs for lithium battery systems.
  • Common battery: in parallel systems one battery group can be shared by all cabinets (parameter set on screen).
  • Battery cold start button: the UPS starts from the battery with no mains and no bypass.
  • Options: battery temperature sensor for charge compensation; battery tripper control (24 V DC) for the DC breaker.
  • First battery charge 24 h (UPS usable meanwhile); best battery temperature 20–30 °C.
One battery strategy for every site
Battery settingValue
Battery typelead-acid; lithium with BMS card
Blocks per string±14 … ±23 × 12 V (default ±16)
Charging current10 A × number of modules (max.)
Equalising / floating2.350 / 2.270 V/cell (example screen)
Under-voltage alarm / protection1.950 / 1.667 V/cell (example screen)
Battery teststandard or deep, from the screen

OPERATOR PANEL

Seven-inch touch screen, LEDs and light bar

A seven-inch colour touch screen, five status LEDs, two-key ON / OFF commands and a status light bar.

IST6-120 · display panel: normal operation, blue light bar
IST6-120 · display panel: normal operation
IST6-120 · display panel: input fault in red
IST6-120 · display panel: battery operation, yellow light bar
  • Colour touch screen, seven inches: live power flow, measurements, settings and records.
  • Five status LEDs (AC/DC, DC/AC, bypass, battery, load): green when normal or active, red when abnormal.
  • ON keys: press both keys for 3 s to power on, no accidental switching; OFF keys: press both keys for 3 s to power off.
  • Status light bar, four states: blue, normal operation; blue flashing, battery mode; yellow, abnormal with UPS still running; red, abnormal with UPS stopped. Alarms also light the yellow or red ambient lamp.
  • Screen settings: date and time, backlight time, language, brightness.

Tap a light: green is normal operation, red an abnormal state, as in the catalogue's table.

AC/DC: green, Rectifier normal

Seven-inch touch screen, LEDs and light bar
LEDGreenRed
AC/DCRectifier normalRectifier abnormal
DC/ACInverter normalInverter abnormal
BypassBypass outputBypass abnormal
BatteryBattery outputBattery low voltage
LoadOutput normalOutput overload

TOUCH SCREEN

Touch a block, read its measurements

The home page draws the UPS as it runs: yellow dots trace the active power path, abnormal blocks turn red, and the bottom line shows output voltage and frequency. Touch a block (bypass, mains, battery, rectifier, inverter, output) to open its page.

  • Bypass info: phase and line voltage, current and frequency of the bypass input.
  • Mains info: phase and line voltage, current, frequency and input energy.
  • Battery info: voltage, charge and discharge current, remaining capacity and time, temperature, state.
  • Inverter info: output voltage, current, power and load of each module.
  • Information menu: run info, history record, user log, smart record, device info, smart wave record.
  • Settings menu: cabinet, battery, battery test, output, smart mode, dry contact, HMI, password, communication, records.
  • Run information: system info, parameter match, system status, system cards 1 and 2.
  • Output info: voltage, current, active and apparent power, load, PF, frequency and output energy.
  • 10,000 records in the history, newest first; 6 live info pages (mains, bypass, rectifier, inverter, battery, output); live single-line diagram with the active power path; 3 s two-key ON / OFF commands.

RECORDS

10,000 events in the history

10,000 records in the history, newest first. When the record is full, the earliest entry is overwritten.

  • Total input and output energy (MWh) on the information pages.
  • Run information: parameter match between cabinets and state of both system cards.
  • Current fault: active faults, time-stamped, from the alarm icon of the menu bar.
  • Device info: hardware and software versions of screen and system cards.
  • Record management: history record, user log, smart record and smart wave record are kept in the UPS and saved or cleared from the record manage page.
  • User log: parameter changes with date and time. Smart wave record: waveforms of abnormal events.
  • Further screens: battery test, communication set, HMI set.

OPERATION

Every operating state, shown live

Real screens of the IST6: the yellow dotted line traces the active power path.

  • Mains inverter: normal operation, mains → rectifier → inverter → load, battery charging.
  • Battery inverter: mains abnormal, the battery feeds the inverter with no break.
  • Bypass: load on the bypass module, e.g. on overload or inverter fault.
  • ECO: load on the bypass within the ECO window; the rectifier keeps the battery charged.
  • Grid-tied aging: test state shown live, with its own alarms.
  • Maintenance bypass: load on the manual bypass, modules ready for service.
  • Transfers: mains → battery with no break (the modules move to the battery input); inverter ↔ bypass 0 ms synchronised, < 15 ms not synchronised; inverter output state shown (Transducer INV. output).
  • Start from battery: with no mains and no bypass, the battery cold start button starts the UPS from the battery.
  • Mains outside range: the UPS starts from the mains between 80 and 280 V; outside this range it starts from the battery.

CONNECTIVITY

4 dry-contact inputs, 3 outputs, SNMP

The system control box holds the expansion card position (optional), the SNMP card position (optional), control cards 1 and 2 and the system monitor card.

IST6-120 · communication panel with numbered ports
IST6-120 · SNMP card: network port and COM1
IST6-120 · dry-contact card
IST6-120 · control board
  • 4 dry-contact inputs (NO) and 3 outputs (NO / NC) as standard, each assigned from the screen; 7 + 5 with the expansion card.
  • Inputs: battery abnormal, battery earth fault, battery switch disconnected, bypass switch disconnected, mains abnormal (generator start), input SPD abnormal.
  • Outputs: inverter output, bypass output, battery output, battery trip, battery under-voltage alarm, battery under-voltage protection, output overload, UPS fault, bypass abnormal, mains abnormal, start generator.
  • Modbus, RS232 · RS485 · SNMP; 2 EPO inputs (NO and NC).

PARALLEL AND DUAL BUS

Parallel systems and dual bus

Parallel cables connect the control cards in a ring: N UPS need N cables, at least two per UPS, which improves parallel reliability.

IST6-120 · parallel cables between UPS units
IST6-120 · parallel cards wiring
  • Dual bus with BSC: two independent systems feed dual-input loads; the BSC keeps their outputs synchronised in frequency and phase, so that the loads can switch between them.
  • Common battery group: all cabinets can share one battery group; the UPS checks that battery parameters match.
  • EPO linkage: enabled, the EPO of any cabinet stops the whole system; disabled, it stops only that cabinet. The system EPO always stops all cabinets.
  • Separate mains and bypass: mains and bypass can come from different sources; the link bars are removed at installation.
  • Parallel commissioning: phase-voltage difference between UPS below 5 V before paralleling; output of each UPS within ± 2 V and ± 0.1 Hz of its setting; same wiring and phase sequence on every cabinet.
  • Redundancy at two levels: N+1 inside each cabinet; at cabinet level, alarms warn if the system has no redundancy or insufficient redundancy. Two control cards in every cabinet.
  • Ring parallel cable topology; BSC dual bus synchronisation; one shared battery group possible; over RS485 one display monitors all UPS.

INSTALLATION AND SERVICE

Quick to install, supported for years

Footprint 600 × 860 mm, height 2000 mm; four Ø14 mm holes to floor or U-steel base.

IST6-120 · Quick to install, supported for years
  • Cables from the bottom as standard; from the top with the top wiring accessory (sections below 120 mm²), mounted on both sides of the cabinet and needing side space.
  • Clearance ≥ 800 mm front and rear, ≥ 500 mm above; keep the front and rear ventilation openings clear.
  • −5 … 40 °C, 0–95% RH non-condensing, up to 2000 m (derating above, IEC 62040-3), IP20, < 65 dB.
  • Optional class C surge protection with its own switch, inside the cabinet.
  • Cables from the IST6 120 kVA user manual; size on site according to local rules and cable length.
  • Sizing: modules, redundancy, battery and parallel system sized by AEC engineers.
  • Commissioning: start-up, settings, dry-contact functions and access passwords.
  • Maintenance: quarterly preventive checks; terminal contacts checked every 6 months; fans checked.
  • Expansion: new power modules added online; further cabinets added with the parallel kit by AEC service.
  • 24/7 AEC technical assistance by phone and WhatsApp; < 30 min WhatsApp reply to technical and commercial questions; 3 years warranty, extendable with a maintenance contract; 21+ countries with spare parts across the Allis Electric group.
  • AEC service: service@aecups.com · +39 393 080 5211 · www.aecups.com
Quick to install, supported for years
LineCurrentCable
Mains input213 A1 × (4 × 120) mm²
Bypass input182 A1 × (4 × 95) mm²
Output182 A1 × (4 × 95) mm²
Battery (±16 blocks)330 A nom. · 377 A max.1 × (3 × 95) mm²

Ordering codes IST6-120

CodeDescription
IST6-120Modular cabinet, max. 4 × 30 kVA power modules, supplied without modules
IST6-30-J30 kVA / 30 kW power module
PAR - IST6Parallel kit

Diagrams

The IST6-120, in diagrams

The path of the power, the ratings, the footprints and the losses, drawn from the figures of the EMEA 2026 catalogue.

How the power flows

Pick an operating mode: the path the power takes to the load lights up.

Power module × NMaintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypassPower module × NMaintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypass

Normal. Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 97%.

The ratings

Every model in the range, in proportion to its power. Each notch is one 30 kVA module.

  1. IST6-120 · 1 × IST6-30-J30 kVA · 30 kW
  2. IST6-120 · 2 × IST6-30-J60 kVA · 60 kW
  3. IST6-120 · 3 × IST6-30-J90 kVA · 90 kW
  4. IST6-120 · 4 × IST6-30-J120 kVA · 120 kW

Modules and redundancy

Move the slider: the modules the load needs light up, and the spare slot holds the N+1 redundancy. Each slot takes one 30 kVA module.

modules working · redundant · free slot

Losses per 100 kW of load

Worked out as P × (1/η − 1) at the stated maximum efficiency, with the load steady all year.

  1. Double conversion 97%3.09 kW27,090 kWh/year
  2. ECO 99%1.01 kW8,850 kWh/year

Phase configurations

Input / output: three-phase (3) or single-phase (1).

UPS
3/3 3~ → 3~

Footprints to scale

Front view of the cabinets, all at the same scale, beside a 2 m rule. W × D × H, mm.

00.5 m1 m1.5 m2 mIST6-120 cabinet600 × 860 × 2,000
  • IST6-120 cabinet, without modules 600 × 860 × 2,000 mm · 180 kg

Questions

Questions people ask

How does the IST6-120 grow with the load?

The cabinet takes 30 kVA / 30 kW power modules (2U, 24 kg): 30, 60, 90 or 120 kVA with 1 to 4 modules, added online in free slots with no new footprint. Beyond 120 kVA, several IST6 cabinets work in parallel with the parallel kit.

How many modules do I need for N+1 redundancy?

Install one module more than the load needs: 2 modules for 30 kVA, 3 for 60 kVA, 4 for 90 kVA, and 4 plus a module in the dedicated fifth redundancy slot for 120 kVA. If a module stops, the others carry the load without transfer to bypass.

Can a power module be replaced without shutting down the UPS?

Yes: power modules are inserted and removed online, a faulty module is isolated automatically, and the 3U bypass module is removable. Wait at least 10 minutes after removal before opening a module; replacement is done by AEC or authorised personnel.

How efficient is the IST6-120?

97% in online double conversion and up to 99% in ECO mode, plus a redundancy sleep function for spare modules at light load. At 96 kW, AEC's indicative calculation gives 2.97 kW of losses in double conversion against 0.97 kW in ECO mode.

Which batteries does the IST6-120 use?

A split battery of ±14 to ±23 × 12 V blocks (±168 to ±276 V DC), default ±16; with fewer than ±16 blocks the load is limited to 80%. Charging current is up to 10 A per power module, lead-acid or lithium with the optional BMS card, and parallel cabinets can share one battery group.

What space does the IST6-120 need?

The cabinet measures 600 × 860 × 2000 mm and weighs 195 kg without power modules. Leave at least 800 mm at the front and rear and 500 mm above; cables enter from the bottom as standard, or from the top with the top wiring accessory.

Which communication options does the IST6-120 offer?

Modbus on RJ45, RS232, RS485, two EPO inputs and 4 dry-contact inputs / 3 outputs are standard (7 + 5 with the expansion card). An SNMP card with a temperature and humidity sensor port and a BMS expansion card are optional.