Modular UPS · 400 V

IST6 400–1200 Modular UPS, 400 V, for data centres

VRLAOnline double conversion

The AEC IST6 400–1200 is a modular online double-conversion UPS for data centres and large 400 V plants: hot-swappable 100 kVA power modules 3U high, from 400 kVA to 1.2 MVA in one cabinet. Efficiency up to 98.1% with PLUS modules and 99.2% in ECO mode, N+1 redundancy, and up to eight UPS in parallel.

400→1200kVA in 100 kVA steps
N+1one extra module
98.1%efficiency, PLUS modules
Hot-swapmodules replaced online
AEC IST6 400–1200, rendered from its 3D modelDrag to turn

In 3D

Look around the IST6 400–1200

Drag it round, swipe on a phone or use the arrow keys. X-ray makes the enclosure see-through, so you can see what sits behind the panels.

Pick a size: the turn and the full 3D view follow it. Rendered from AEC's 3D models; the full 3D view zooms in, opens the unit and names every part.

Hands on

Open the IST6 400–1200 yourself.

Click the unit: the door opens, then a module comes out. Drag to move it by hand. The 3D shows every part.

AEC IST6 400–1200, closed

Every part in 3D

Efficiency

How efficient is the AEC IST6 400–1200 at your load?

AC/AC efficiency of each operating mode against the load: AEC's measured curves where they exist, elsewhere the typical curve derived from the datasheet figure by AEC's method. The losses and their cost follow the curve at the load you choose: drag along the chart or move the slider.

98.1%50% · Typical curve, derived from the datasheet efficiency of 98.1% (AEC method)

Filled points: measured by AEC (AC/AC technical datasheet). Hollow points: a typical curve, the shape of the most similar measured curve (same technology and size) moved to the range's datasheet efficiency: η(load) = reference curve + (datasheet figure − its highest point), AEC's method. Dashed lines: one figure without a load (ECO, W-ECO). Between points the efficiency is read on a straight line; beyond them, the nearest end. Losses = P × (1/η − 1).

Load
—
Lost as heat
—
Energy lost in a year, 24/7
—
Its cost in a year at € per kWh
—
The catalogue's examples use €0.20 per kWh.
Where each figure comes from
ModeEfficiencyKindModelsSource
Online, double conversion25%: 97.5% · 50%: 98.1% · 75%: 97.8% · 100%: 97.5%Typical curve, derived from the datasheet efficiency of 98.1% (AEC method)allAEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape)
ECO99.2%Datasheet figure, load not statedall
W-ECO99%Datasheet figure, load not statedall

EMEA 2026 catalogue figures: Double conversion, General modules up to 97.2% · Double conversion, PLUS modules up to 98.1% · ECO up to 99.2% · W-ECO up to 99%.

The display

The IST6 400–1200 kVA display

The real display, drawn by AEC's own simulator: pick a UPS state (normal, battery, bypass) or a main page.

UPS state
IST6 400–1200 kVA: Normal operation

IST6 400–1200 kVA · the real display

Normal operation

Main pages

What is what

Inside the IST6 400–1200, part by part.

Each number on the picture is named in the list.

Front, door open · 800 kVA

IST6 800 kVA, door open
  1. Battery cold start
  2. System control box
  3. Power modules

Front, doors open · 1000 kVA

IST6 1000 kVA with its distribution cabinet, doors open
From 800 kVA the power switches sit in an optional distribution cabinet, fitted at the factory on the left of the UPS.
  1. Distribution cabinet1000 / 1200 kVA: mains, bypass and output breakers (no maintenance bypass), pre-assembled at the factory.
  2. SPDOptional surge protection device, with its own switch.
  3. Battery cold startStarts the UPS from the battery when there is no mains and no bypass.
  4. System control boxFive hot-swappable cards: expansion (dry contact or BMS) and SNMP (optional), control cards 1 and 2, monitoring card with Modbus, RS232, RS485, EPO1 NO, EPO2 NC, B-Temp input and dry contacts.
  5. Power modules100 kVA in 3U each, in three groups of four slots on 1200 kVA.

Front, doors open · 1200 kVA

IST6 1200 kVA, doors open
  1. SPD
  2. Battery cold start
  3. System control box
  4. Power modules

Overview

Key facts

Power range
400–1200 kVA
Input / output
3/3 · 380 / 400 / 415 V
Efficiency
97.2% (General) / 98.1% (PLUS) · ECO 99.2% · W-ECO 99%
Battery
480 V DC nominal (360–600 V), 30–50 × 12 V blocks, standard 40; neutral optional
Communication
Modbus · RS232 · RS485 · 4 inputs / 3 outputs dry contact
Network card
SNMP card (optional)
Parallel
up to 8 UPS, current imbalance ≤ 5% · BSC dual bus and multi-bus (3 buses)
Warranty
3 years
Dimensions W × D × H
801 × 1000 × 2000 · 1201 × 1000 × 2000 mm

Models

Which IST6 400–1200 fits your load?

Every rating has its own page: that model's technical data, ordering codes, batteries and the questions people ask.

Datasheet

Datasheet IST6 400–1200.

Every model side by side: keep only what differs, take it as CSV or print it.

IST6 400–1200 · Technical data
Model400 kVA500 kVA600 kVA800 kVA1000 kVA1200 kVA
Cabinet
Power modules (100 kVA)45681012
Bypass module3U4.5U4.5U4.5U4.5U4.5U
Input
System · voltage3Ph+N+PE · 380 / 400 / 415 V; 138–485 V (full power 324–485 V, linear derating below)
Frequency · PF · THDi40–70 Hz · ≥ 0.99 · ≤ 3% at full load
Bypass304–438 V; synchronisation 50 / 60 ± 6 Hz; settable window
Battery
Lead-acid480 V DC nominal (360–600 V), 30–50 × 12 V blocks, standard 40; neutral optional
Lithium (with BMS card)512 V DC nominal (384–640 V), 120–200 cells, standard 160
Charging current20 A × number of modules · cold start · shared battery
Output
System · voltage3Ph+N+PE · 380 / 400 / 415 V ± 1%
Power factor · THDvsettable 0.8–1.0 (default 1.0) · ≤ 1% linear, ≤ 3% non-linear
Frequency · phase errortracks the bypass; 50 / 60 ± 0.1 Hz with mains abnormal · ≤ 1° balanced, ≤ 2° unbalanced
Transfermains ↔ battery 0 ms · bypass ↔ inverter < 1 ms synchronised, < 15 ms
Inverter overload (PF ≥ 0.95)≤ 105% continuous · 105–110% 60 min · 110–125% 10 min · 125–150% 1 min · > 150% to bypass
Bypass overload≤ 135% continuous · 135–150% 5 min · 150–200% 1 s · 200–300% 100 ms
System
Efficiency · modes97.2% (General) / 98.1% (PLUS) · ECO 99.2% · W-ECO 99% · energy storage, sleep, generator
Parallelup to 8 UPS, current imbalance ≤ 5% · BSC dual bus and multi-bus (3 buses)
CommunicationModbus · RS232 · RS485 · 4 inputs / 3 outputs dry contact · options: SNMP, expansion, BMS
Environment0 … 40 °C · 0–95% RH · ≤ 2000 m · IP20 · < 80 dB · EMC category C3
W × D × H (mm)801 × 1000 × 2000801 × 1000 × 2000801 × 1000 × 2000801 × 1000 × 20001201 × 1000 × 20001201 × 1000 × 2000
With distribution cabinet———1400 mm wide1800 mm wide1800 mm wide
Weight without modules345 kg434 kg434 kg435 kg662 kg662 kg

Power module 440 × 760 × 130 mm (without ears and handles), 54 kg. Data from the IST6 400–1200 kVA user manual. Specifications are subject to change without notice.

Full technical details22 sections of the EMEA 2026 catalogue: functions, panel, connections, diagrams and ordering codes

Why IST6 400–1200

01400→1200 · Sized to the siteSix cabinets with 4 to 12 power modules of 100 kVA: single column up to 800 kVA, double column for 1000 and 1200 kVA.
0298.1% · High efficiencyUp to 97.2% with General modules and 98.1% with PLUS modules in double conversion; 99.2% in ECO.
031.2 MW · Compact power100 kVA = 100 kW in a 3U module: 800 kW in 0.8 m² and 1.2 MW in 1.2 m² of floor.
04Hot-swap · Continuity firstAll modules hot-swappable, two system control cards backing each other up, dual DSP control.
0540 °C · No deratingNo derating up to 40 °C, redundant fans, conformal-coated boards, dust filter and fuses on frame and modules.
06Storage · Smart energyEnergy storage mode for peak cutting and valley filling, ECO, W-ECO, redundancy sleep and generator mode.

OPERATING COST

What PLUS modules save at 800 kW

From 97.2% to 98.1%: less than one point of efficiency, but at megawatt scale it is heat that is not paid for at the meter and in the cooling.

  • 7.6 kW less losses (23.0 → 15.5 kW)
  • 66,200 kWh saved per year
  • ≈ € 13,200 per year at € 0.20/kWh
  • Basis: IST6 1000 kVA at 80% load (800 kW), 8,760 h/year, cooling excluded. Losses = P × (1/η − 1) with the maximum system efficiencies 97.2% (General) and 98.1% (PLUS). Indicative values.

FEATURE OVERVIEW

The features, group by group

The IST6 400–1200 kVA features, in the catalogue's four groups.

IST6 400–1200 · The features, group by group
  • Reliable: double key combination, two keys for ON / OFF
  • Reliable: power walk-in and sequential rectifier restart
  • Reliable: short-circuit protection, time settable 20–400 ms
  • Reliable: backfeed protection, enabled on site
  • Reliable: system and component redundancy, 40% load with one fan failed
  • Reliable: wide input, 138–485 V, 40–70 Hz
  • Reliable: conformal coating on all PCBs
  • Flexible: lead-acid or lithium batteries, neutral optional
  • Flexible: common battery bank in parallel systems
  • Flexible: frequency converter 50 ↔ 60 Hz
  • Flexible: top entry, bottom entry with side wiring cabinet
  • Flexible: top air outlet kit for installation against the wall
  • Intelligent: start-up guidance and diagnosis
  • Intelligent: maintenance assistant
  • Intelligent: smart integrated display for the parallel system
  • Intelligent: smart files, asset and replacement records
  • Intelligent: W-ECO and redundancy sleep
  • Intelligent: fault trace, 200 ms before and after the fault
  • Intelligent: programmable dry contacts, 10 input, 18 output functions
  • Grid support: energy storage mode, peak cutting, valley filling
  • Efficiency: 97.2% (General) / 98.1% (PLUS)
  • Efficiency: ECO 99.2%, W-ECO 99%
  • Testing: self-load test without external load banks
  • 98.1% efficiency with PLUS modules · 1.2 MVA per cabinet · 20–400 ms short-circuit time · 9.6 MW with 8 UPS in parallel

THE RANGE

Six cabinets, one 100 kVA module

Single-column cabinets from 400 to 800 kVA, double-column cabinets for 1000 and 1200 kVA; the same power module, display and functions.

IST6 400–1200 · single cabinet, front
IST6 400–1200 · cabinet with the display, front
IST6 400–1200 · cabinet with the display, front
IST6 400–1200 · two-door cabinet, front
  • 400 · 500 · 600 · 800 kVA: single column, 801 mm wide
  • 1000 · 1200 kVA: double column, 1201 mm wide
  • 800 kVA + distribution cabinet: 1400 mm wide
  • 1000 · 1200 kVA + distribution cabinet: 1800 mm wide
  • 400–600 kVA: mains, output, maintenance bypass and bypass switches inside; version without switches available
  • With the distribution cabinet fitted on the left side: 800 kVA mains, bypass, maintenance bypass and output switches; 1000 / 1200 kVA mains, bypass and output
  • Height 2000 mm for all cabinets
  • Codes: IST6-400H, IST6-500H, IST6-600H, IST6-800, IST6-1000, IST6-1200 cabinets without modules; IST6-100-J power module

POWER MODULE

100 kVA in 3U, 1.2 MW in 1.2 m²

The same 100 kVA module from 400 kVA to 1.2 MVA: rectifier, inverter and DC/DC converter in a 3U drawer, with output power factor 1 (kVA = kW).

  • Front: limit lock (press to pull the module out), RUN (green), ALARM (yellow) and FAULT (red) LEDs, ready switch (green unlocked, red locked)
  • Rear: output port; input port for AC mains and DC battery
  • Intelligent fan control with redundant design: 100% load with all fans running, 40% with one fan failed, 15% with two
  • Dual DSP control: no single point of failure
  • Fuses on frame and modules
  • Conformal coating on all PCB boards
  • Dust filter: standard, self-dedusting
  • ≈ 1 MW/m²: 800 kW on 0.8 m², 1.2 MW on 1.2 m²
100 kVA in 3U, 1.2 MW in 1.2 m²
ItemValue
Rating100 kVA / 100 kW
W × D × H440 × 760 × 130 mm · 3U
Weight54 kg
Handlingthree installers or a lift truck
Bypass module3U (400 kVA) · 4.5U (500–1200 kVA)

INSIDE THE CABINET

Every module in front, everything in reach

400–600 kVA single column with internal power switches, and 1000–1200 kVA double column (without switches: these are in the optional distribution cabinet).

IST6 400–1200 · cabinet with one door open: switches above the modules
IST6 400–1200 · wide cabinet with both doors open: modules in two columns
  • 400 kVA, 4 modules, with switches: mains switch, output switch, maintenance bypass switch, bypass switch, SPD switch (optional), SPD (optional), system control box with five hot-swappable cards, battery cold start, bypass module (3U, under the control box), fan control switch (optional), power modules of 100 kVA each, switch operating lever
  • 1200 kVA, 12 modules: fan control switch, SPD switch (optional), SPD (optional), battery cold start, system control box with five hot-swappable cards, power modules in three groups of four slots, bypass module (4.5U)
  • 500 / 600 kVA: 4.5U bypass module and 6 module slots
  • 800 kVA: single column with 8 modules and no internal power switches

DISTRIBUTION CABINET

Switchgear on board, factory fitted

For 800, 1000 and 1200 kVA the power switches come in an optional distribution cabinet, fitted at the factory on the left side of the UPS: one line-up, switches pre-assembled.

  • 800 kVA + distribution, 1400 mm: mains, bypass, maintenance bypass and output switches, SPD switch and SPD (optional), system control box, battery cold start, bypass module, fan control switch, 8 × 100 kVA power modules
  • 1200 kVA + distribution, 1800 mm: bypass switch, mains switch, output switch, fan module
  • 1000 / 1200 kVA: mains, bypass and output breakers (no maintenance bypass)
  • Option: side wiring cabinet for bottom cable entry; standard entry is from the top
  • Option: top air outlet kit, hot air out from the top instead of the rear; factory fitted on 800–1200 kVA
  • Option: single power source kit, mains and bypass from one source
  • Option: earthing detection kit, battery earthing detection, 400–600 kVA

HOT-SWAP

Service with the load running

All modules are hot-swappable: power modules, bypass module and the five cards of the system control box.

  • Step 1, unlock: ready switch to unlocked, indication green, the module can be removed
  • Step 2, pull out: remove the fixing screws, pull the module out by its handles, press the limit lock and lift it onto a lift truck; the other modules keep supplying the load
  • Step 3, insert and lock: slide the new module in, fasten the screws and set the ready switch to locked, indication red, the module joins the system
  • Green, yellow and red LEDs (RUN · ALARM · FAULT) on every power and bypass module
  • A faulty module isolates itself from the system automatically; redundancy is reduced until it is replaced
  • Service records: spare part replacements, dates and service people; pre-alarms on key components such as capacitors and fans
  • 54 kg power module: lift truck or three installers
  • 2 system control cards backing each other up; 5 hot-swappable control box cards
  • Wait ≥ 15 min before opening a removed module

ARCHITECTURE

Online double conversion in every module

Power flow in each operating mode: N power modules in parallel and one bypass module.

IST6 400–1200 · power flow in red, mains mode: mains through the modules, battery charging
IST6 400–1200 · power flow in red, battery mode: the battery feeds the inverters
IST6 400–1200 · power flow in red: mains and battery feeding the modules together
IST6 400–1200 · power flow in red, bypass mode: the bypass module feeds the output
  • Mains mode: each module rectifies the mains and the inverter supplies the load; the battery is charged
  • Battery mode: mains abnormal, the DC/DC converter feeds the battery to the inverters, 0 ms
  • Mains and battery source share: mains too low, mains and battery supply the modules together
  • Bypass mode: overload or fault, the bypass module supplies the load
  • Two control cards: primary and secondary system control cards, hot-swappable, backing each other up
  • CAN communication inside and between cabinets for synchronisation and current sharing
  • Load shared equally between power modules within 5%
  • Mains ↔ battery transfer time 0 ms; bypass ↔ inverter < 1 ms synchronised
  • Input power factor ≥ 0.99; input THDi ≤ 3% at full load; 100% unbalanced load

SCALE AND SLEEP

100 kVA steps, up to 9.6 MW with 8 UPS

Add 100 kVA modules or whole UPS as the site grows; set redundancy and redundancy sleep from the screen.

IST6 400–1200 · display: smart mode (module sleep) settings
IST6 400–1200 · display: cabinet settings
IST6 400–1200 · display: system run information
  • Step size 100 kVA: one 3U module at a time, in free slots up to the cabinet rating
  • 4 → 12 modules per cabinet: 400, 500, 600, 800, 1000 or 1200 kVA cabinets
  • × 8 UPS in parallel: up to 9.6 MW, with N+X redundancy between UPS
  • N+X, two redundancy levels: basic and redundant modules per cabinet and per parallel system
  • Redundancy sleep: at light load the spare modules sleep at random, while the basic modules carry the load within the sleep safety load capacity set on screen
  • Smart mode › Sleep redundancy: on / off, sleep cycle period (h), sleep safety load capacity (kVA), parallel basic and redundant UPS, basic and redundant modules inside the cabinet
  • Parallel mode, parallel address and BSC address set in Cabinet setting › Mode manage; parameter match between UPS checked in Running info
  • Alarms: power module without redundancy, redundancy insufficient, cabinet without redundancy, system card without redundancy
  • Power walk-in limits inrush on mains or generator; delayed sequential rectifier restart in multi-UPS sites
  • Firmware online: screen, power units, bypass unit and cards updated online in one step

SMART ENERGY

Modes that save energy and work with the grid

ECO, W-ECO and energy storage modes, plus redundancy sleep, smart generator mode, self-load test and frequency converter.

IST6 400–1200 · display: ECO operation
IST6 400–1200 · display: W-ECO operation
IST6 400–1200 · electricity price over a day: charge and discharge
IST6 400–1200 · display: energy storage settings
  • ECO mode, up to 99.2%: the load runs on the static bypass while the bypass is within the ECO window; the inverter is in standby and the rectifier keeps the battery charged
  • ECO window: voltage ±5 / ±10 / ±15% (default ±15%), frequency ±2 / ±4% (default ±2%); parallel ECO available
  • W-ECO mode, up to 99%: high-efficiency mode with input THDi below 5%; its state is shown live on the home page
  • Energy storage mode: peak cutting and valley filling, the battery supplies part of the load at peak hours and recharges in the valley, following a plan curve set by discharge power or current for each period
  • Energy storage UPS page: plan curve, battery safety SOC (e.g. 40%), discharge power or current for each period, electricity price setting
  • Redundancy sleep: spare modules sleep at light load
  • Smart generator mode: starts and stops the generator by dry contact and can take part of the power from the battery
  • Self-load test at commissioning without costly temporary loads
  • Frequency converter: 60 Hz to 50 Hz or 50 Hz to 60 Hz

PERFORMANCE

Full power from 324 to 485 V

Full power from 324 to 485 V line voltage; from 138 to 323 V the UPS keeps running with linear derating of the load.

  • Input: 40–70 Hz · PF ≥ 0.99 · THDi ≤ 3% at full load
  • Power walk-in to limit inrush on mains or generator; delayed sequential rectifier restart in multi-UPS sites
  • TN-S, TN-C, TN-C-S, TT; RCD breakers upstream not recommended
  • Inverter overload (linear load, PF ≥ 0.95): ≤ 105% continuous · 105–110% 60 min · 110–125% 10 min · 125–150% 1 min; above 150% to bypass at once
  • PF 0.9: 105–110% 60 min, above 110% to bypass; PF 0.8: above 105% to bypass
  • Bypass overload: ≤ 135% continuous · 135–150% 5 min · 150–200% 1 s · 200–300% 100 ms; above 300% immediate protection
  • With the top air outlet kit, overload values apply below 30 °C
  • Backfeed protection: fitted, enabled on site; dry-contact outputs for single UPS and parallel system bypass backfeeding
  • Option: output isolation transformer of the same capacity
  • Settable bypass window: max. +10 … +25% (default +15%), min. −10 … −30% (default −20%), frequency ±2 … ±20% (default ±10%)
  • No derating up to 40 °C
Full power from 324 to 485 V
OutputValue
Voltage380 / 400 / 415 V ± 1%
Power factorsettable 0.8–1.0, default 1.0
THDv≤ 1% linear · ≤ 3% non-linear
Phase error≤ 1° balanced · ≤ 2° unbalanced
Frequency, mains abnormal50 / 60 Hz ± 0.1 Hz
Load step 0↔100%≤ 5%, recovery ≤ 20 ms
DC component−100 … +100 mV
Transfer bypass ↔ inverter< 1 ms synchronised · < 15 ms
Short circuitduration settable 20–400 ms

PROTECTION AND SMART GUIDANCE

Grid protections and service guidance

Advanced protection of the 100 kVA platform, plus the guidance tools that shorten installation and maintenance.

IST6 400–1200 · timing chart: mains, battery and rectifier power
IST6 400–1200 · inputs opened, red arrows
IST6 400–1200 · display: generator source selection
IST6 400–1200 · display: device configuration
  • Power walk-in: decreases the inrush to the mains or the generator; with several UPS the rectifiers restart in sequence when the mains returns
  • Short-circuit protection: high short-circuit capacity for a settable time of 20–400 ms, so the breaker of the faulty load trips while the other loads keep running
  • Backfeed protection: enabled on site; dry-contact outputs for single UPS and parallel system bypass backfeeding open the backfeed device upstream
  • Start-up guidance and diagnosis: first power-on guidance with module self-test, potential risks are cleared before the system is powered on
  • Maintenance assistant: locates the problem easily and quickly, reducing the time for maintenance
  • Smart integrated display: one display checks the status of each UPS of the parallel system
  • Key components pre-alarm and asset records: pre-alarm on capacitors and fans; full record of spare part replacements, dates and service people

BATTERIES

480 V lead-acid or 512 V lithium

480 V DC nominal with 40 blocks of 12 V (360–600 V); 30 to 50 blocks (46–50 on request), with the output factor below for short strings. Battery neutral optional (±240 V).

IST6 400–1200 · display: battery settings, management
IST6 400–1200 · display: battery charge settings
IST6 400–1200 · display: battery test
  • 20 A charging current per power module (specification), three-stage charging
  • Lithium: 512 V nominal, 120–200 cells (standard 160, full power from 160), with the BMS card
  • Battery setting: cell voltages for protection, alarm, equalising and floating charge, charging current, test time
  • Charge management: charge limit coefficient in C, temperature compensation, timed and forced equalising charge
  • Battery test: standard or deep test with mains normal, battery floating and load ≥ 15%
  • Common battery: shared battery pack mode fitted
  • Battery cold start button: hold more than 3 s to start the UPS from the battery
  • Optional BMS expansion card with charge- and discharge-disable inputs
  • Intelligent battery management helps replace only the faulty battery
  • 30–50 × 12 V blocks per string · 480 V lead-acid nominal · 0.05–0.5 C charge limit, lead-acid · 20–30 °C best battery temperature
480 V lead-acid or 512 V lithium
12 V blocks per string (lead-acid)Output factor
300.75
320.8
340.8
360.9
380.9
40 (standard)1
421
441
461
481
501

OPERATOR PANEL

Seven-inch touch screen and status light bar

Seven-inch colour touch screen, five status LEDs, two-key ON / OFF commands and a status light bar.

IST6 400–1200 · display panel: normal operation, blue light bar
IST6 400–1200 · display panel: normal operation, blue light bar
IST6 400–1200 · display panel: input fault in red
IST6 400–1200 · display panel: battery operation, yellow light bar
  • Colour touch screen, seven inches: live power flow, measurements, settings and records
  • Five status LEDs: AC/DC, DC/AC, bypass, battery, load; green when normal or active, red when abnormal
  • ON keys: press both keys for 3 s to power on, no accidental switching; OFF keys: press both keys for 3 s to power off
  • Status light bar: blue normal operation; blue flashing battery mode; yellow abnormal, UPS still running; red abnormal, UPS stopped; alarms also light the yellow or red ambient lamp
  • Screen settings: backlight time, brightness; 10 languages, including Italian; atmosphere light on / off; time zone and NTP time sync

Tap a light: green is normal operation, red an abnormal state, as in the catalogue's table.

AC/DC: green, Rectifier normal

Seven-inch touch screen and status light bar
LEDGreenRed
AC/DCRectifier normalRectifier abnormal
DC/ACInverter normalInverter abnormal
BypassBypass outputBypass abnormal
BatteryBattery outputBattery low voltage
LoadOutput normalOutput overload

TOUCH SCREEN

Touch a block, read its measurements

The home page draws the UPS as it runs: yellow dots trace the active power path, abnormal blocks turn red, and the bottom line shows output voltage and frequency. Touch a block (bypass, mains, battery, rectifier, inverter, output) to open its page.

  • Bypass info: phase and line voltage, current and frequency of the bypass input
  • Mains info: phase and line voltage, current and frequency of the mains
  • Battery info: voltage, charge and discharge current, remaining capacity and time, temperature, state
  • Inverter info: output voltage, current, power and load of each module
  • Information menu: running info, history, user log, smart record, device info, wave capture, running record, battery discharge record
  • Settings menu: cabinet, battery, battery test, output, smart mode, dry contact, screen, password, communication, records, energy storage
  • Running info: UPS info, parameter match between UPS, UPS status, system cards 1 and 2
  • Device info: hardware and software versions of screen, system cards and modules
  • 3 password levels: user, technician and service engineer
  • 10 languages on the screen; 7″ colour touch screen with live single-line diagram
  • Online firmware update of screen, units and cards in one step

RECORDS

10,000 events, 200 ms of fault waveform

10,000 records in the history, newest first; when the record is full, the earliest entry is overwritten.

  • 200 ms of waveform recorded before and after the fault point (fault trace management)
  • User log: user operations listed with date and time
  • Current fault: active faults, time-stamped, from the alarm icon of the menu bar
  • Smart record: maintenance actions such as part replacements
  • Smart wave capture: when a fault occurs, the UPS stores the waveforms 200 ms before and after it, listed with date and time
  • Running record: input voltages and current over time
  • Battery discharge record: every discharge with date and time
  • Record manage: save or clear history, user log, smart record and wave capture

OPERATION

Every operating state, shown live

Real screens of the IST6 400–1200 kVA: the yellow dotted line traces the active power path.

  • Inverter output: mains → rectifier → inverter → load, battery charging
  • Battery: mains abnormal, the battery feeds the inverters, 0 ms
  • Bypass: load on the bypass module, e.g. on overload or fault
  • Maintenance bypass: load on the maintenance bypass for service
  • Grid-tied self-load: load test at commissioning without external load banks
  • Frequency converter: 60 Hz to 50 Hz or 50 Hz to 60 Hz
  • ECO: load on the static bypass within the ECO window, up to 99.2%
  • W-ECO: high-efficiency mode, up to 99%, THDi below 5%
  • Transfers: 0 ms mains ↔ battery; < 1 ms inverter ↔ bypass, synchronised; < 15 ms inverter ↔ bypass, not synchronised
  • Cold start: hold the battery cold start button for more than 3 s to start the UPS from the battery
  • Restart after a long outage: after battery under-voltage protection, the UPS restarts and recharges the battery when the mains returns
  • Two-key ON / OFF: press both ON or both OFF keys for 3 s, no accidental switching

CONNECTIVITY

Five hot-swappable cards in the control box

System control box: all five cards are hot-swappable.

IST6 400–1200 · communication panel with numbered ports
IST6 400–1200 · dry-contact card
IST6 400–1200 · battery temperature sensor and its wires
IST6 400–1200 · control board
  • Slots: expansion card (optional: dry contact or BMS), SNMP card (optional), system control card 1, system control card 2, monitoring card (Modbus, RS232, EPO, dry contacts)
  • 4 inputs (NO), 10 functions: battery abnormal, battery earthing abnormal, battery switch off, bypass switch off, generator mode, SPD abnormal, maintenance bypass open, mains switch off, environment smoke abnormal, strip light switch off
  • 3 outputs (NO / NC, 30 V DC / 2 A), 18 functions: inverter mode, bypass mode, battery trip, battery mode, battery under-voltage alarm, battery under-voltage protection, output overload, UPS abnormal, bypass abnormal, mains abnormal, start generator, ECO mode, inverter abnormal, single UPS bypass backfeeding, parallel system bypass backfeeding, UPS ON, fan abnormal, UPS alarm
  • Standard: Modbus (address 1–247, 2400–19200 baud) · RS232 for an external SNMP card · RS485 linking the displays of a parallel system · EPO1 NO and EPO2 NC · B-Temp input for the battery temperature kit
  • Option: SNMP card, Ethernet, SNMP or Modbus; RS485 port for a T/H sensor
  • Option: dry contact expansion card, +3 inputs, +2 outputs (30 V DC / 2 A)
  • Option: BMS expansion card, BMS port, charge / discharge disable inputs
  • Option: class C SPD with SPD switch, factory fitting recommended
  • Option: battery temperature kit, charge voltage compensated by temperature
  • Option: battery trip kit, trip signal for the external battery breaker

PARALLEL AND MULTI-BUS

Up to eight UPS, up to three buses

Parallel, dual-bus and multi-bus system layouts.

IST6 400–1200 · two UPS in parallel: distribution and monitoring
IST6 400–1200 · parallel system with STS and dual-supply loads
IST6 400–1200 · multi-bus system with STS
IST6 400–1200 · parallel cards wiring
  • Parallel system, up to 8 UPS: mains, bypass and AC outputs of each cabinet connected in parallel; the control modules keep all UPS synchronised and share the load (imbalance ≤ 5%)
  • BSC dual-bus system: two independent UPS systems synchronised by the bus sync controller; an STS supplies single-input loads
  • Multi-bus: three buses
  • Parallel ring: PARALLEL ports of the system control cards in a ring, N UPS need N cables; a 7 m cable is supplied with each UPS
  • Output of each UPS within ± 2 V and ± 0.1 Hz of the system setting
  • Parallel mode, parallel address and BSC address set on the screen
  • EPO linkage: one EPO stops the whole system, or only its UPS (set by AEC service)
  • Shared battery pack and parallel ECO available
  • Up to 8 UPS in parallel · 9.6 MW system power · ≤ 5% current imbalance · 3 buses in multi-bus mode

INSTALLATION AND SERVICE

Site conditions and service

Clearances, airflow, environment, cabling and the AEC service path from sizing to expansion.

IST6 400–1200 · clearances around the cabinet
IST6 400–1200 · airflow: cold in at the front, hot out at the back
IST6 400–1200 · cabinet top with fans
  • Clearances: A front ≥ 800 mm · B rear ≥ 500 mm (400–600 kVA) or ≥ 800 mm (800–1200 kVA) · C top ≥ 500 mm (≥ 650 mm with the top air outlet kit, 400–600 kVA)
  • Front to rear forced air: cold air in at the front, hot air out at the rear; minimum air flow from 3744 m³/h (400 kVA) to 8785 m³/h (1200 kVA)
  • Top air outlet kit: hot air out from the top; factory fitted on 800–1200 kVA, shipped as an accessory for 400–600 kVA
  • 0 … 40 °C without derating, 0–95% RH non-condensing
  • Up to 2000 m · IP20 · noise < 80 dB at 1 m from the front
  • TN-S, TN-C, TN-C-S, TT; RCD breakers not recommended
  • Not for open installations within 3.7 km of the sea
  • Top cable entry; bottom entry with the side wiring cabinet (trench 750 × 300 × 120 mm)
  • M12 expansion bolts to the floor or C-steel base
  • Forklift from the side or two forklifts from the front; tilt ≤ 15°
  • Optional class C SPD with switch, factory fitting recommended
  • Sizing: modules, redundancy, battery and parallel system sized by AEC engineers
  • Commissioning: start-up guidance, settings, dry contacts, parallel addresses and self-load test
  • Maintenance: monthly, quarterly and yearly checks; air filter cleaned or replaced
  • Expansion: power modules added in free slots up to the cabinet rating or for redundancy; further UPS with the parallel kit
  • 24/7 AEC technical assistance by phone and WhatsApp; WhatsApp reply in < 30 min to technical and commercial questions
  • 3 years warranty, extendable with a maintenance contract
  • 21+ countries with spare parts across the Allis Electric group
  • AEC service: service@aecups.com · +39 393 080 5211 · www.aecups.com

Ordering codes IST6 400–1200

CodeDescription
IST6-400HModular cabinet, max. 4 × 100 kVA power modules, without modules
IST6-500HModular cabinet, max. 5 × 100 kVA power modules, without modules
IST6-600HModular cabinet, max. 6 × 100 kVA power modules, without modules
IST6-800Modular cabinet, max. 8 × 100 kVA power modules, without modules
IST6-1000Modular cabinet, max. 10 × 100 kVA power modules, without modules
IST6-1200Modular cabinet, max. 12 × 100 kVA power modules, without modules
IST6-100-J100 kVA / 100 kW power module
PAR - IST6Parallel kit

Diagrams

The IST6 400–1200, in diagrams

The path of the power, the ratings, the footprints and the losses, drawn from the figures of the EMEA 2026 catalogue.

How the power flows

Pick an operating mode: the path the power takes to the load lights up.

Power module × NMaintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypassPower module × NMaintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypass

Normal. Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 98.1% (PLUS modules; 97.2% with General modules).

The ratings

Every model in the range, in proportion to its power. Each notch is one 100 kVA module.

  1. 400 kVA400 kVA · 400 kW
  2. 500 kVA500 kVA · 500 kW
  3. 600 kVA600 kVA · 600 kW
  4. IST6-800800 kVA · 800 kW
  5. IST6-10001,000 kVA · 1,000 kW
  6. IST6-12001,200 kVA · 1,200 kW

Modules and redundancy

Move the slider: the modules the load needs light up, and the spare slot holds the N+1 redundancy. Each slot takes one 100 kVA module.

modules working · redundant · free slot

Losses per 100 kW of load

Worked out as P × (1/η − 1) at the stated maximum efficiency, with the load steady all year. PLUS modules; 97.2% with General modules.

  1. Double conversion 98.1%1.94 kW16,970 kWh/year
  2. ECO 99.2%0.81 kW7,060 kWh/year

Phase configurations

Input / output: three-phase (3) or single-phase (1).

UPS
3/3 3~ → 3~

In parallel Up to 8 units on the same load, for redundancy or for more power.

Footprints to scale

Front view of the cabinets, all at the same scale, beside a 2 m rule. W × D × H, mm.

00.5 m1 m1.5 m2 m400 kVA cabinet801 × 1,000 × 2,000500 kVA cabinet801 × 1,000 × 2,000600 kVA cabinet801 × 1,000 × 2,000800 kVA cabinet801 × 1,000 × 2,0001000 kVA cabinet1,201 × 1,000 × 2,0001200 kVA cabinet1,201 × 1,000 × 2,000
  • 400 kVA cabinet, single column, without modules 801 × 1,000 × 2,000 mm · 345 kg
  • 500 kVA cabinet, single column, without modules 801 × 1,000 × 2,000 mm · 434 kg
  • 600 kVA cabinet, single column, without modules 801 × 1,000 × 2,000 mm · 434 kg
  • 800 kVA cabinet, single column, without modules 801 × 1,000 × 2,000 mm · 435 kg
  • 1000 kVA cabinet, double column, without modules 1,201 × 1,000 × 2,000 mm · 662 kg
  • 1200 kVA cabinet, double column, without modules 1,201 × 1,000 × 2,000 mm · 662 kg

Questions

Questions people ask

Which cabinet sizes does the IST6 400–1200 kVA come in?

Six cabinets with 4 to 12 power modules of 100 kVA (3U, 54 kg each). The 400, 500, 600 and 800 kVA in a single column of 801 × 1000 × 2000 mm, 1000 and 1200 kVA in a double column of 1201 × 1000 × 2000 mm. With the optional distribution cabinet the 800 kVA is 1400 mm wide and the 1000–1200 kVA 1800 mm.

What is the difference between General and PLUS power modules?

System efficiency in double conversion is up to 97.2% with General modules and 98.1% with PLUS modules; ECO mode reaches 99.2%. At 800 kW, AEC's indicative calculation shows PLUS modules saving 7.6 kW of losses, about 66,200 kWh per year.

How far can the system grow in parallel?

Up to eight UPS in parallel, for up to 9.6 MW, with N+X redundancy between UPS and load sharing within 5%. Dual-bus (BSC) and three-bus layouts are supported, and power modules can be added in free slots up to the cabinet rating.

Which battery configuration does it use?

Lead-acid: 480 V DC nominal with 40 × 12 V blocks (360–600 V), 30 to 50 blocks accepted with reduced output below 40 blocks, battery neutral optional (±240 V). Lithium: 512 V nominal with 120–200 cells (standard 160) and the BMS card; charging current is 20 A per power module.

What installation clearances does it need?

At least 800 mm at the front, 500 mm (400–600 kVA) or 800 mm (800–1200 kVA) at the rear and 500 mm on top (650 mm with the top air outlet kit on 400–600 kVA). It runs without derating up to 40 °C, up to 2000 m, with top cable entry as standard and bottom entry via the side wiring cabinet; it is not for open installations within 3.7 km of the sea.

How is service carried out without stopping the load?

All modules are hot-swappable, including the bypass module and the five cards of the system control box, with dual DSP control and two control cards backing each other up. The redundant fans keep a module running at 40% load with one fan failed.

Which communication options does it offer?

Modbus (address 1–247, 2400–19200 baud), RS232 for an external SNMP card, RS485, EPO1 / EPO2 and 4 dry-contact inputs / 3 outputs are standard. Options: SNMP card (Ethernet, SNMP or Modbus), dry-contact expansion and a BMS card for lithium batteries.

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST6 400–1200 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.