Three-phase UPS · 400 V

IST7-T Transformer UPS 100–200 kVA

VRLAOnline double conversion

The AEC IST7-T is a three-phase online double-conversion UPS from 100 to 200 kVA with an output isolation transformer built into every model, for loads that need galvanic separation or a neutral of their own. IGBT rectifier with THDi < 5% and PF ≥ 0.99, 0 ms transfer from mains to battery, 100% three-phase unbalanced load.

Δ/Youtput isolation transformer
< 5%input THDi
100%unbalanced three-phase load
0 msmains to battery
AEC IST7-T

Efficiency

AEC IST7-T efficiency

The IST7-T pages of the EMEA 2026 catalogue give no efficiency figure.

Touch screen

The IST7-T touch screen.

A touch screen, five status indicators and paired ON / OFF buttons: on the panel, both buttons are pressed together. Power on and off is also available from the touch screen, with confirmation.

OPERATING PANEL

Status at a glance, paired ON / OFF keys

IST7-T · display panel with paired ON / OFF keys and EPO, numbered
Display panel with paired ON / OFF keys and EPO, numbered
IST7-T · display: single-line diagram, run status
Single-line diagram, run status
  • Touch-screen display: operating parameters and status (voltage, current, load).
  • Rectifier and inverter indicators: green running normally · red abnormal · off not running.
  • Bypass indicator: green bypass output · red bypass abnormal · off no bypass output.
  • Battery indicator: green discharging normally · red undervoltage protection · red blinking battery abnormal · off normal.
  • Load indicator: green load normal · red output overload · off no output.
  • ON and OFF: press both buttons together.
  • EPO: emergency power off under a cover; reserved function, disabled by default, enabled on request.
  • Home page: live single-line diagram; the energy path is drawn in yellow, faulty blocks turn red. Below it, run status and output voltage and frequency per phase.
  • Side bar: home (system output status), information management, setting management, current fault, buzzer on / off, privileged login, power on / off.

TOUCH SCREEN

Touch a block, read its measurements

From the home page every block opens its own page: mains, bypass, battery and output. Settings sit behind the privileged login.

IST7-T · touch screen: information management, with working status, event log, device info and user log
Information management, with working status, event log, device info and user log
IST7-T · touch screen: mains page, line and phase voltage, phase current and frequency
Mains page, line and phase voltage, phase current and frequency
IST7-T · touch screen: bypass page, phase voltage and frequency of the bypass input
Bypass page, phase voltage and frequency of the bypass input
IST7-T · touch screen: battery page, voltage, current, temperature, remaining capacity and time
Battery page, voltage, current, temperature, remaining capacity and time
IST7-T · touch screen: output page, phase voltage and current, load %, kW, kVA, power factor and frequency
Output page, phase voltage and current, load %, kW, kVA, power factor and frequency
IST7-T · touch screen: privileged login, password keypad
Privileged login, password keypad
IST7-T · touch screen: setting management, system, battery, battery test, logs, communication, screen, password, energy storage
Setting management, system, battery, battery test, logs, communication, screen, password, energy storage
  • Information management: working status, event log, device info and user log.
  • Working status: system, capacitor and fan status; mains, bypass, battery, output, load and loops.
  • Log management: event log and user log, export or clear.
  • Mains: line and phase voltage, phase current and frequency. Bypass: phase voltage and frequency of the bypass input.
  • Battery: voltage, current, temperature, remaining capacity and time, battery status and loop.
  • Output: phase voltage and current, load %, kW, kVA, power factor and frequency.
  • Privileged login: password keypad; settings are protected from unauthorised changes.
  • Setting management: system, battery, battery test, logs, communication, screen, password, energy storage.
  • Language selected on the Screen setting page; buzzer silenced from the side bar.

RECORDS AND SETTINGS

Every event recorded, every setting logged

Up to 10,000 historical records; when full, the oldest are overwritten. A separate user log records user actions and setting changes.

IST7-T · display: event log
Event log
IST7-T · display: user log
User log
IST7-T · display: working status
Working status
IST7-T · display: device information
Device information
IST7-T · touch screen: system management, mains and bypass voltage limits, bypass frequency range, ECO and N+x warning
System management, mains and bypass voltage limits, bypass frequency range, ECO and N+x warning
IST7-T · touch screen: communication setting, Modbus or SNMP protocol, Modbus address, baud rate, remote timeout
Communication setting, Modbus or SNMP protocol, Modbus address, baud rate, remote timeout
IST7-T · touch screen: screen setting, date and time, language, screensaver and backlight brightness
Screen setting, date and time, language, screensaver and backlight brightness
  • 10,000 events in the history record, numbered and time-stamped; event log of alarms and faults by time.
  • User log: what changed and when (on / off, mains and bypass limits, ECO, N+x warning, reset to default).
  • Working status: mains, bypass, battery, output, load, AC/DC and DC/AC status, system mode, parallel address.
  • Device information: serial number and rectifier, inverter, hardware, system, protocol and HMI versions.
  • System management: mains and bypass voltage limits, bypass frequency range, ECO mode and limits, N+x warning.
  • Communication: Modbus or SNMP protocol, Modbus address, baud rate, remote timeout.
  • Screen setting: date and time, language, screensaver and backlight brightness.
  • Records exported from Log management.

OPERATING MODES

Every operating state, shown live

Five operating modes: normal, battery, bypass, ECO and maintenance bypass. The home page shows which path is active.

IST7-T · display: single-line diagram, run status
Single-line diagram, run status
IST7-T · display: mains fault in red
Mains fault in red
IST7-T · display: bypass path
Bypass path
IST7-T · display: output fault in red
Output fault in red
  • Normal mode: the rectifier feeds the inverter and charges the battery; the load receives clean AC through the transformer.
  • Battery mode: with the mains abnormal (red), the battery feeds the inverter through the DC/DC circuit, with no break in the output.
  • Bypass mode: on over-temperature, short circuit, abnormal output voltage or overload beyond the inverter limit, the static switch transfers the load to the bypass, provided the mains is normal.
  • Maintenance bypass: for service, the load is fed through the maintenance bypass switch; no residual current inside the UPS except N.
  • ECO mode: when the bypass voltage and frequency are within the ECO range, the load is fed from the bypass and the inverter waits in cold standby. If the bypass goes out of range, the inverter starts and takes the load. ECO limits are set on the System management page.
  • Self-load test (function, not an operating mode): in test mode the UPS simulates the inverter output under load, so the system can be checked on site before the real load is connected.
  • Transfer: 0 ms mains → battery; 1 ms inverter → bypass.

Overview

Key facts

Power range
100–200 kVA
Input / output
380 / 400 / 415 V L-L · 220 / 230 / 240 V L-N
Battery
348–480 V DC
Communication
RS232 / RS485 Modbus RTU · 8 output and 4 input dry contacts (24 V DC / 1 A)
Network card
SNMP card (optional)
Warranty
3 years
Dimensions W × D × H
1000 × 800 × 2000 mm

Hands on

Open the IST7-T.

Pick an operating mode: the power path lights up to the load.

AEC IST7-T · two-door cabinet
Maintenance bypassMainsRectifierDC busBatteryInverterTransformerStatic switchLoadStatic bypassMaintenance bypassMainsRectifierDC busBatteryInverterTransformerStatic switchLoadStatic bypass

Normal. Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge.

Datasheet

Datasheet IST7-T.

Every model side by side: keep only what differs, take it as CSV or print it.

IST7-T · Technical data
ModelIST7T-100IST7T-120IST7T-200
General
Rated power (kVA / kW)100 / 90120 / 108200 / 180
Rectifier input
Technologycurrent-type IGBT rectifier, three-phase PFC · input EMI filter and input contactor
Rated voltage · range380 / 400 / 415 V L-L · ± 25% (full load from −20% to +25%; −25 … −20% current-limited)
Connection · frequency3Φ3W + PE, no neutral needed · 45–55 or 54–66 Hz
Power factor · THDi≥ 0.99 · < 5%
AC input / output current (A)180216355
Bypass input
Rated voltage · connection380 / 400 / 415 V L-L · 3Φ4W + PE · separate bypass input as standard (jumper for single input)
Synchronisation range50 Hz ± 10% (± 5% optional)
Static bypassSCR static switch · manual maintenance bypass built in
Battery
Battery converterbidirectional buck / boost DC/DC on the DC bus · VRLA or lithium
Battery voltage (V DC)348–480
Number of 12 V batteries29–40 (default 32)
Battery current (A)278333499
Battery managementpatented smart charging · equalise / float · temperature compensation · hibernation · standard, depth and constant-current tests · cell data with BMS
Energy functionsbackfeed to grid during the battery test · energy-storage UPS with lithium (plan curve, 8 periods, or EMS over Modbus)
Output
Voltage · power factor220 / 230 / 240 V L-N (380 / 400 / 415 V L-L) · 0.9 (kW / kVA)
Waveform · frequencysine wave, THDv < 1% (linear load) · tracks the bypass in normal mode · 50 Hz ± 0.2% in battery mode
IsolationΔ/Y output transformer built in, between inverter and inverter static switch
Transfer time0 ms mains → battery · 1 ms inverter → bypass
Overload (inverter mode)101–105% alarm, continuous · 106–130% 10 min · 131–155% 1 min · > 155% 1 s, then bypass
Unbalanced · non-linear load100% three-phase unbalanced · full kVA at 100% non-linear load
Operating modesnormal · battery · bypass · ECO (inverter in cold standby) · maintenance bypass · self-load test
Output connectioncopper busbar
System
Control · displayfully digital DSP · touch screen, power-on password, user and administrator levels · 10,000 events, user log
CommunicationRS232 / RS485 Modbus RTU · 8 output and 4 input dry contacts (24 V DC / 1 A) · SNMP card, serial server TCP/IP optional
Parallel · systemsmaster-slave adaptive digital parallel, N+x warning, online exit and add · series hot standby · dual bus with LBS (optional)
Protectionsbattery undervoltage, overload, short circuit, over-temperature, input over- and undervoltage
StandardsCE · EN / IEC 62040-1 (safety) · EN / IEC 62040-2 (EMC), category C3
Environment and mechanics
Temperature · humidity−5 … 40 °C operating · −20 … 55 °C storage · 0–95% RH non-condensing
Altitude without derating · noise1500 m · < 70 dB
Protection degreeIP20 (IP21 with optional top cover)
Dimensions (W × D × H)1000 × 800 × 2000 mm
Weight (kg ± 5%)7207801280

Specifications are subject to change without notice.

Full technical details19 sections of the EMEA 2026 catalogue: functions, panel, connections, diagrams and ordering codes

Why IST7-T

01Isolation · Transformer built inStandard output isolation transformer: complete electrical isolation between input and output, full kVA output at 100% non-linear load.
02±25% · Input voltage windowIGBT rectifier with input PF ≥ 0.99 and THDi < 5%. Full load from −20% to +25% of rated voltage.
03100% · Unbalanced loadsWithstands 100% three-phase unbalanced load, with stronger short-circuit and inductive-load capability.
04Backfeed to grid · Battery test energy returnedDuring the battery test the residual energy is fed back to the grid instead of being wasted.
05Peak shift · Energy storage UPSWith lithium batteries the UPS charges off-peak and discharges at peak hours, on a plan curve or under EMS control.
06Patented · Battery managementPatented smart charging and automatic battery tests, battery hibernation; cell voltage, internal resistance and temperature with the optional BMS.
078 + 4 · Configurable dry contactsRS232 / RS485 Modbus, 8 output and 4 input dry contacts, all configurable. SNMP card optional.

PREDICTIVE MAINTENANCE

The UPS watches its own health

Capacitor health is monitored with early warning, so service can be planned in advance.

  • 10,000 events stored in the history record, oldest overwritten.
  • Capacitor health monitored, with early warning.
  • Fan fault on a dry contact.
  • Self-load: test mode simulates load on the inverter for on-site testing.

ARCHITECTURE

Double conversion, isolated output

The rectifier converts the mains to DC; the inverter rebuilds clean AC, delivered to the load through the output isolation transformer. The battery is charged through the DC/DC converter.

IST7-T · Double conversion, isolated output
  • Battery mode: when the mains fails or the rectifier stops, the DC/DC circuit boosts the battery voltage to feed the inverter; the AC output is not interrupted.
  • Bypass and maintenance: on overload, short circuit, abnormal output voltage or over-temperature beyond the inverter's limit, the static switch transfers the load to the bypass if the mains is normal. The maintenance bypass keeps the load supplied during service.
  • Rated line voltage, input and bypass: 380 / 400 / 415 V; output 220 / 230 / 240 V phase-to-neutral.
  • Rectifier input 3W + PE, without neutral; bypass input 3 phases + N + PE (4W + PE).
  • Inverter control, phase locking and logic fully controlled by the DSP.
  • AC → DC, IGBT rectifier: current-type IGBT rectifier, THDi below 5%, input power factor not less than 0.99; bidirectional protection of the load and the grid.
  • DC → AC, inverter: high-efficiency IGBT inverter, sine wave with THDv < 1% on linear load; zero phase-lag synchronisation between output and grid.
  • Isolation, output transformer: built in as standard and matched to the inverter; isolates the load from the input and the battery.
  • Bypass, static switch: 1 ms transfer from inverter to bypass; manual maintenance bypass to service the UPS with the load supplied.

INSIDE THE CABINET

Every switch behind one door

Mains, bypass, maintenance bypass and output switches and the communication module sit behind the front door; cable terminals are at the bottom, behind a sealing panel.

IST7-T · Every switch behind one door
  • Communication module: terminal block, dry contacts, touch-screen interface, optional SNMP card and parallel interface.
  • Battery cold start switch (optional, for the bus capacitor): starts the UPS from the battery with no mains or bypass.
  • Auxiliary power supply for external low-power instruments.
  • Surge protection device: optional class C SPD for lightning-prone areas, with optional SPD switch for overcurrent protection of the SPD circuit.
  • Battery switch (optional), output switch, maintenance bypass switch, bypass switch and mains switch.
  • 1000 mm cabinet; on 100–120 kVA the communication module sits behind a blanking plate.
  • Output connection on copper busbar.
  • Redundant working power supply of the system (key-circuit redundancy).
  • IP20; IP21 with the optional waterproof top cover.
  • Cable entry from the bottom as standard; top entry optional up to 120 kVA.

ONE FRAME

One cabinet, 1000 × 800 × 2000 mm

Every model AEC offers, 100 to 200 kVA, is 1000 mm wide, 800 mm deep and 2000 mm high.

IST7-T · cabinet, three-quarter view
IST7-T · dimensions of the single-door cabinet, front and side
IST7-T · dimensions of the two-door cabinet, front and side
IST7-T · clearances around the cabinet
  • Installation space: at least 700 mm free at the front and rear for heat dissipation and service; front and rear vents must stay clear. Units can be combined in a row.
  • Handling: electric or hand forklift, kept upright and balanced. Four lifting eyes on the top for hoisting; hook at least 1 m above the cabinet.
  • Install on a concrete or non-flammable level floor.
  • Ground cable up to 2 × 150 mm².
One cabinet, 1000 × 800 × 2000 mm
kVAAC in/out (A)mm² maxBattery (A)mm² max
1001802 × 1502782 × 150
1202162 × 1503332 × 150
2003552 × 1504992 × 150

ISOLATION TRANSFORMER

Full isolation, as standard

The output isolation transformer is built into every IST7-T and matched to the inverter: no external transformer to add, size or install.

  • Where it sits: input EMI filter and contactor → three-phase PFC rectifier → DC bus → three-phase inverter → Δ/Y transformer → output static switch; battery on the DC bus through the bidirectional buck/boost converter; bypass and maintenance bypass outside the inverter path.
  • Complete electrical isolation: the transformer isolates the current between the load and the battery, achieving complete electrical isolation between input and output.
  • Full kVA at 100% non-linear load: the UPS runs heavily unbalanced loads and supplies its full kVA output capacity with 100% non-linear load.
  • No inrush on the inverter: being matched to the inverter, it removes the effect of the excitation inrush current that an external high-power transformer produces at start-up.
  • Stronger against short circuit: resistance to load short circuit is further improved, and so is the capacity for inductive loads.
  • Output voltage THD < 1% on linear load; output frequency tolerance ±0.2% in battery mode, 50 Hz; 100% three-phase unbalanced load; 0 ms transfer from mains to battery.
  • Output: 220 / 230 / 240 V phase-to-neutral (380 / 400 / 415 V line); sine wave, THDv < 1% (linear load); tracks the bypass in normal mode, 50 Hz ± 0.2% in battery mode; 1 ms transfer inverter → bypass; zero phase-lag synchronisation between output and grid.
  • Output on copper busbar.
  • Overload in inverter mode: 105% continuous · 130% 10 min · 155% 1 min · > 155% 1 s; above the time limit the UPS transfers the load to the bypass.

GRID SIDE

Full load from −20% to +25% of rated voltage

A wide input window and an IGBT rectifier keep the UPS on the mains when the voltage moves, and keep the mains clean of harmonics.

  • Full-load output with the mains from −20% to +25% of the rated voltage (320–500 V at 400 V rated). From −25% to −20% (300–320 V) the rectifier supplies power with limited current; the full-load current at −20% is the current-limiting point.
  • Input power factor ≥ 0.99; input current THD (THDi) < 5%; input frequency range 45–55 · 54–66 Hz.
  • IGBT rectifier: the current-type IGBT rectifier provides bidirectional protection of the load and the grid.
  • Precise mains synchronisation: zero phase-lag synchronisation between output and grid makes the bypass transfer more reliable. Bypass tracking range ± 10% (± 5% optional), 50 Hz.
  • EMC tested by authorities and trade bodies; compliant with EN / IEC 62040-2 (EMC, category C3 UPS) and EN / IEC 62040-1 (safety). Tests: conducted and radiated interference, conducted and radiated immunity, sags, fast transient burst, electrostatic discharge, surge.
  • Lightning-prone areas: optional built-in class C SPD with its own protection switch, as part of a multi-stage lightning protection at the grid input.
  • IP20 (IP21 with optional top cover); operating temperature −5…40 °C; relative humidity 0–95%, non-condensing.

SMART FUNCTIONS

Functions that look after the UPS and the battery

Capacitor and fan health monitoring, smart battery management and redundant key circuits.

IST7-T · display: capacitor state
IST7-T · display: working status
  • Capacitor health: the UPS monitors capacitor health, with early warning to prevent potential hazards; status on the capacitor page of Working status.
  • Fan fault: available on output dry contact 8.
  • Smart battery management: professional charge and discharge management with automatic battery testing, for higher battery reliability and longer service life.
  • Battery hibernation: when enabled, after equalised charge the battery floats for a set time, then charging stops; it resumes when the hibernation time expires or the battery discharges.
  • Temperature compensation: with the optional battery temperature sensor, the charging voltage follows the battery temperature.
  • Key-circuit redundancy: redundant working power supply of the system improves operating reliability.
  • Lithium ready: the system can be equipped with a lithium battery system (smaller footprint, lower weight).
  • Self-load test: test mode simulates the inverter output under load for commissioning without load.

ENERGY FUNCTIONS

The battery test that gives energy back

During the battery test the IST7-T feeds the residual energy back to the grid, and with lithium batteries it can shift energy from off-peak to peak hours.

IST7-T · display: battery management
IST7-T · display: battery test
IST7-T · display: energy storage settings
IST7-T · display: energy storage plan
  • Backfeed to grid: during the battery test the residual energy is fed back to the grid without waste.
  • Three battery tests from the screen: standard test, depth-of-discharge test, constant-current discharge test.
  • Constant-current discharge test: discharge current, time and end voltage set on the Battery management page; requires "Backfeed to grid" enabled, the authorisation countdown above 0 days, the UPS powered on and the battery voltage above the end voltage.
  • Battery test page: test status, consumed capacity, battery current and test time; conditions that block a test are listed.
  • Energy storage UPS: with a lithium battery the UPS charges at off-peak hours and discharges at peak hours (peak load shifting), with the yield calculated from the electricity prices set per period.
  • Plan curve: up to 8 periods with start and end time, charge / discharge power or current.
  • EMS mode: the upper computer sets mode, power and current over Modbus.
  • Settings: mode (plan curve or EMS), scheduling mode (current or power) and battery safety SOC; a safe SOC threshold prevents over-discharge in both modes.

SYSTEM ARCHITECTURES

From one UPS to redundant systems

Parallel, series hot standby and dual-bus systems, with a common battery pack when required.

IST7-T · two UPS in parallel, block diagram
IST7-T · two UPS in series, block diagram: the output of UPS2 feeds the bypass input of UPS1
IST7-T · two UPS fed from two mains inputs
IST7-T · two UPS on one common battery cabinet
  • Parallel system: digital master-slave adaptive parallel technology for redundancy. Units connect through the parallel interfaces PALL.1 and PALL.2 with shielded cables; a parallel redundancy (N+x) alarm can be enabled.
  • Series hot standby: the output of UPS 2 feeds the bypass input of UPS 1. If UPS 1 fails, the load stays on the inverter of UPS 2; only if both fail is the load fed from the mains.
  • Dual-bus redundancy (optional): for loads with two power inputs. Two independent systems A and B, single units or parallel systems (two or four UPS in total), phase- and frequency-synchronised through the LBS interface.
  • Common battery pack: UPS units in a parallel system can share one battery pack, with dedicated common-battery cabling.

BATTERY

A battery string sized to the site

External battery: the number of batteries and the battery voltage are chosen per site within the window of each size.

IST7-T · touch screen: cell information from the optional BMS, voltage, internal resistance and temperature of every cell
IST7-T · touch screen: battery management, charge voltages and current, test end voltage, low-voltage warning and protection, temperature compensation
  • 100–200 kVA: 32 batteries by default. Lithium battery systems supported.
  • Cell information (optional BMS): with the battery logger, voltage, internal resistance and temperature of every cell are shown on the UPS screen.
  • Battery management: equalising and floating charge voltage, charge current, test end voltage, low-voltage warning and protection, temperature compensation, forced equalising charge.
  • Battery cold start (optional cold start switch and battery switch): start the UPS from the battery when mains and bypass are absent.
  • Battery switch release (optional): opens the battery switch on battery or bus undervoltage, on EPO or on an external signal.
  • Breaker detector (optional): detects the external battery circuit breaker state, with alarm when it is faulty.
  • Temperature sensor (optional): battery temperature detection on terminal pins 3–4, for charge compensation.
  • BMS link (optional): battery logger on pins 1–2 (9600 bps, slave address 11).
  • Best at 20–30 °C: above 30 °C battery life shortens; below 20 °C backup time shortens.
  • A bipolar disconnect switch must be installed on the external DC distribution circuit.
A battery string sized to the site
SizeBattery voltage (V DC)12 V blocks per string
100–200 kVA348–48029–40

CONNECTIVITY AND OPTIONS

Modbus and 8 + 4 configurable dry contacts

RS232 / RS485 Modbus and 8 + 4 configurable dry contacts as standard; SNMP card, parallel, LBS, BMS link and serial server as options.

  • Each output contact: programmable, NO (1-3) or NC (2-3), with indicator LED. With the optional battery release, OUT.1 is the battery release. OUT.5 is maintenance bypass status or UPS abnormal, depending on the Integrated alarm setting.
  • Configurable output functions: output overload, mains fault, bypass on, inverter fault, inverter on, fan fault, bypass abnormal, battery loop abnormal, ECO power supply, UPS power / maintenance bypass status, sync / async signal, battery trip.
  • Inputs IN.1–IN.4: EPO, maintenance bypass switch closed, mains switch open, bypass switch open, battery charge disable, battery discharge disable, battery ground abnormal, battery charge forbid.
  • Options: SNMP card (remote monitoring and remote on / off); parallel interface (parallel system or dual bus); LBS (dual-bus communication); BMS link (cell data from the battery logger); temperature sensor (charge compensation); class C SPD (with SPD switch); cold start (start from the battery); top cover (IP21 against dripping water); battery switch release (automatic battery disconnect); serial server (TCP/IP to the upper computer); breaker detector (external battery breaker state).
Modbus and 8 + 4 configurable dry contacts
PortSignal (default)
OUT.1Output overload
OUT.2Mains abnormal
OUT.3Bypass output
OUT.4Inverter abnormal
OUT.5Maintenance bypass / UPS abnormal
OUT.6Battery undervoltage protection
OUT.7Inverter on
OUT.8Fan abnormal

AEC SERVICE

Survey, installation, commissioning, maintenance

AEC engineers size, install, commission and maintain the IST7-T. The UPS keeps its own records, and AEC service works from them.

IST7-T · display: event log
IST7-T · display: user log
IST7-T · display: battery test
IST7-T · display: log management
  • 24/7 technical assistance by phone and WhatsApp, also on non-working days.
  • < 30 min WhatsApp reply to technical and commercial questions.
  • 3 years warranty, extendable with a maintenance contract.
  • 21+ countries with spare parts in stock across the Allis Electric group.
  • 01 Consulting and sizing: feasibility study and design for critical and industrial sites; UPS, battery and system architecture sized by the AEC engineering team (IST7-T: parallel, hot standby or dual bus).
  • 02 Survey and installation: site survey, handling, positioning and cabling of the UPS and the battery by AEC technicians (IST7-T: 700 mm free at front and rear).
  • 03 Commissioning: commissioning and verification of every value and parameter, dry-contact functions and communication (IST7-T: self-load test before the load).
  • 04 Maintenance: programmes and contracts written for each site, with battery tests, fan and capacitor checks (IST7-T: capacitor health).
  • 05 Assistance 24/7: call centre 24 hours a day, 7 days a week, by phone and WhatsApp, with an engineer on site when needed (IST7-T: 10,000 events in the history record).
  • 06 Expansion: new units in parallel, dual-bus systems, battery and lithium upgrades, configured by AEC service (IST7-T: energy storage with lithium).
  • Service data straight from the UPS: event log, user log, battery test (standard, depth or constant-current) and log export for the service report.
  • AEC Service: service@aecups.com · +39 393 080 5211 · www.aecups.com · Via Nerviano 55, 20045 Lainate (MI), Italy.

DESIGN DETAILS

The details that count on site

Beyond the transformer and the battery functions: the details that count when the IST7-T is installed, started and run on site.

  • Parallel maintenance online: a faulty unit leaves the parallel system by itself; units are removed or added online and share the load automatically.
  • Redundancy warning: in a parallel system a redundancy (N+x) warning can be enabled, set on the System management page.
  • Input phase sequence: if the mains phases are connected in the wrong order, the phase sequence indicator on the panel goes on and the UPS does not power on normally.
  • Rectifier soft start: at power-on the rectifier starts softly; the inverter output follows once the soft start is complete.
  • Switches on board: mains, bypass, maintenance bypass and output disconnect switches inside the cabinet.
  • Power for instruments: an auxiliary power supply in the cabinet feeds external low-power instruments.
  • Quiet in operation: noise below 70 dB on 100–200 kVA.
  • Storage: up to 6 months; below −20 °C the UPS rests at 0 °C for at least 4 h before power-on.
  • Dual bus: systems of 2 or 4 UPS; altitude up to 1500 m without derating.

Ordering codes IST7-T

CodeDescription
IST7T-100 · -120 · -200IST7-T online UPS with output isolation transformer, 100 / 120 / 200 kVA, 1000 mm cabinet, external battery

Diagrams

The IST7-T, in diagrams

The path of the power, the ratings, the footprints and the losses, drawn from the figures of the EMEA 2026 catalogue.

How the power flows

Pick an operating mode: the path the power takes to the load lights up.

Maintenance bypassMainsRectifierDC busBatteryInverterTransformerStatic switchLoadStatic bypassMaintenance bypassMainsRectifierDC busBatteryInverterTransformerStatic switchLoadStatic bypass

Normal. Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge.

The ratings

Every model in the range, in proportion to its power.

  1. IST7T-100100 kVA · 90 kW
  2. IST7T-120120 kVA · 108 kW
  3. IST7T-200200 kVA · 180 kW

Phase configurations

Input / output: three-phase (3) or single-phase (1).

UPS
3/3 3~ → 3~

Footprints to scale

Front view of the cabinets, all at the same scale, beside a 2 m rule. W × D × H, mm.

00.5 m1 m1.5 m2 m100–200 kVA1,000 × 800 × 2,000
  • 100–200 kVA 1,000 × 800 × 2,000 mm · 720 / 780 / 1280 (± 5%) kg

Questions

Questions people ask

Why choose a UPS with a built-in isolation transformer?

Every IST7-T has an output isolation transformer matched to the inverter, giving complete electrical isolation between input and output, with nothing external to add or size. It delivers full kVA at 100% non-linear load, avoids the inrush of an external transformer and improves short-circuit and inductive-load capability.

What mains voltage variations can the IST7-T handle?

The input range is ±25%, with full load from −20% to +25% of rated voltage (320–500 V at 400 V rated). The IGBT rectifier keeps input power factor at 0.99 or above and THDi below 5%; it takes 3 wires + PE without neutral, while the bypass is 3 phases + N + PE.

What are the IST7-T ratings, dimensions and weights?

Three ratings: 100 kVA / 90 kW, 120 kVA / 108 kW and 200 kVA / 180 kW. Every model is a cabinet 1000 mm wide, 800 mm deep and 2000 mm high, weighing 720, 780 and 1280 kg (± 5%). Leave at least 700 mm free at the front and rear.

Which batteries can the IST7-T use?

An external battery, chosen per site: 348–480 V DC (29–40 × 12 V blocks), 32 batteries by default. Lithium systems are supported, and with lithium the UPS can shift energy from off-peak to peak hours.

Which redundant architectures does the IST7-T support?

Parallel systems with an N+x redundancy alarm, series hot standby (UPS 2 feeds the bypass of UPS 1) and optional dual-bus systems synchronised through the LBS interface. Units in parallel can share one battery pack.

Which communication interfaces does the IST7-T have?

RS232 / RS485 Modbus RTU and 8 output and 4 input configurable dry contacts are standard. Options include an SNMP card for remote monitoring and on / off, a BMS link for cell data, a parallel interface, LBS and a TCP/IP serial server.

What warranty and service are included?

The IST7-T has a 3-year warranty, extendable with a maintenance contract, with 24/7 technical assistance by phone and WhatsApp. AEC engineers size, install, commission and maintain the system, and spare parts are stocked in 21+ countries.