A VRLA bank's backup time is worked out by the IEEE 485 method: the load divided by the inverter efficiency and the number of blocks gives the watts per block, which the block's constant-power discharge table turns into minutes at 1.70 V per cell; at end of life an ageing factor of 1.25 applies. For the AEC models with their batteries, the backup-time tool.

Battery block

    Loading the battery data…

    Constant power from the battery: the UPS load divided by the inverter efficiency, shared by every cell of the bank, read on the block's constant-power table (watts per cell to the end voltage, 25 °C) interpolated on log scales between the maker's published points. AEC's OZ Power blocks carry the same tables as the backup-time tool, which reads between the points on a straight line: the two can differ by a few tenths of a minute. Below 25 °C, the temperature factor of IEEE 485 Table 1. End of life: 80 % of the capacity (ageing factor 1.25). A block known only by its 15-minute rating borrows the average shape of the published high-rate curves and is marked as an estimate. A figure for sizing, not a guarantee.

    How it works

    From the block to the minutes, in four steps.

    1. The blockAn AEC OZ Power block, or any 12 V battery's model number.
    2. The bankBlocks per string and strings, or the UPS's DC bus.
    3. The loadkW, inverter efficiency and the room temperature.
    4. The minutesWith new batteries and at end of life, at 80 % capacity.
    1.70 Vper cell, the starting end voltage
    25 °Cthe makers' tables
    × 1.25ageing factor at end of life
    IEEE 485the method