A VRLA bank's backup time is worked out by the IEEE 485 method: the load divided by the inverter efficiency and the number of blocks gives the watts per block, which the block's constant-power discharge table turns into minutes at 1.70 V per cell; at end of life an ageing factor of 1.25 applies. For the AEC models with their batteries, the backup-time tool.
Loading the battery data…
Constant power from the battery: the UPS load divided by the inverter efficiency, shared by every cell of the bank, read on the block's constant-power table (watts per cell to the end voltage, 25 °C) interpolated on log scales between the maker's published points. AEC's OZ Power blocks carry the same tables as the backup-time tool, which reads between the points on a straight line: the two can differ by a few tenths of a minute. Below 25 °C, the temperature factor of IEEE 485 Table 1. End of life: 80 % of the capacity (ageing factor 1.25). A block known only by its 15-minute rating borrows the average shape of the published high-rate curves and is marked as an estimate. A figure for sizing, not a guarantee.
How it works
From the block to the minutes, in four steps.
- The blockAn AEC OZ Power block, or any 12 V battery's model number.
- The bankBlocks per string and strings, or the UPS's DC bus.
- The loadkW, inverter efficiency and the room temperature.
- The minutesWith new batteries and at end of life, at 80 % capacity.