Products · choosing a range

Which AEC range for your load

Supply (single or three-phase), power in kVA, monolithic or modular, lead-acid or lithium: the eleven AEC UPS ranges for EMEA side by side, and the models that cover each load band, from the EMEA 2026 catalogue.

Range selector

The ranges side by side

Input / output configuration as the catalogue writes it: 3/3 is three-phase in and out, 3/1 three-phase in and single-phase out, 1/1 single-phase in and out.

The ranges side by side
RangeRatingsInput / outputArchitectureBatteryFormatChoose it when
IST31–10 kVA1/1, 230 Vmonolithic, online double conversionVRLA 9 Ah inside, or external (long backup models)towera single-phase load up to 10 kW sits on the floor and the batteries should be inside
IST3-J1–10 kVA1/1, 230 Vmonolithic, online double conversionVRLA inside (1–3 kVA) or external in rack cabinets (6–10 kVA)19-inch rack, 2U; tower on 1–3 kVAthe UPS must fit two rack units of a 19-inch cabinet
IST81–3 kVA1/1, 230 Vmonolithic, online double conversionLFP lithium inside19-inch rack, 2U, or towera rack load up to 3 kW, warm cabinets (0–60 °C; long periods at 40–60 °C may reduce the output power), no lead-acid replacement cycle
All-in-One20 kVA3/3 · 3/1 (20 kVA, IST9 inside)rack UPS, switches and lithium modules in one cabinetLFP lithium modules, 2–8 × 50 Ah or 4 × 100 Ah, hot-swap600 × 1000 mm cabinet on castorsUPS, distribution and lithium battery should arrive as one cabinet, wired at the factory
IST910–40 kVA3/3 · 3/1; 1/1 on 10–20 kVAmonolithic, online double conversionexternal VRLA (BBJ2 rack cabinets) or the approved lithium system19-inch rack, 3U, or towerthree-phase power up to 40 kW must go in a rack
IST7 10–4010–40 kVA3/3 · 3/1; 1/1 on 10–20 kVAmonolithic, online double conversionVRLA inside (S models) and / or in BB4–BB8 cabinetsfloor-standing, 250 or 300 mm wide10–40 kW on the floor, with internal batteries and the battery voltage set on site
IST7 60–20060–200 kVA3/3, 400 Vmonolithic; IST7-80, -100, -160 upgradable from the displayexternal VRLA (BB5–BB8) or lithium with the BMS cardfloor-standing, 400 or 600 mm wide60–200 kW per unit, up to 1.6 MW in parallel, growth by setting a higher rating
IST7-T100–200 kVA3/3, 400 V, isolated outputmonolithic with built-in output isolation transformerexternal VRLA or lithium1000 × 800 × 2000 mm cabinetindustrial or harsh grids, loads that need galvanic isolation, heavily unbalanced or non-linear loads
IST6-12030–120 kVA3/3, 400 Vmodular, 30 kVA hot-swap modules, N+1 slotexternal VRLA or lithium with the BMS card600 × 860 × 2000 mm cabinet30–120 kW that will grow, with redundancy inside one cabinet
IST6 200–500200–500 kVA3/3, 400 Vmodular, 50 kVA hot-swap modulesexternal VRLA or lithium with the BMS card607 or 1203 mm wide, 2000 mm high200–500 kW in 50 kVA steps, up to eight UPS in parallel, THDi ≤ 1.5%
IST6 400–1200400–1200 kVA3/3, 400 Vmodular, 100 kVA hot-swap modulesexternal VRLA or lithium with the BMS card801 or 1201 mm wide, 2000 mm high400 kW to 1.2 MW per cabinet, up to 9.6 MW, up to 98.1% efficiency with PLUS modules

Range selector

The models for each load

Every model page has its own data, ordering codes and questions. Size on the load in kW with spare capacity (load within about 80% of the rating), and on the supply the site has.

Load and supplyModelsHow to choose
1–3 kVA, 230 VIST3-1 · IST3-2 · IST3-3 · IST3-J 1 kVA · IST3-J 2 kVA · IST3-J 3 kVA · IST8-1 · IST8-2 · IST8-3Tower: IST3. Rack: IST3-J (lead-acid, extendable) or IST8 (lithium, 1 kW per kVA).
6–10 kVA, single-phase supplyIST3-6 · IST3-10 · IST3-J 6 kVA · IST3-J 10 kVA · IST9 10 kVA · IST7-10IST3 tower with internal batteries; IST3-J in 2U with external batteries; IST9 10 kVA and IST7-10 work 1/1 too.
10–20 kVA, three-phase supplyIST9 10 kVA · IST9 15 kVA · IST9 20 kVA · IST7-10 · IST7-20 · All-in-One 20 kVARack: IST9. Floor: IST7 10–40 kVA, with internal batteries. Lithium in one cabinet: All-in-One 20 kVA.
20 kVA on a single-phase supplyIST9 20 kVA · IST7-20The largest models that still accept 1/1: input current about 105 A, so check the supply first.
30–40 kVA, three-phaseIST9 30 kVA · IST9 40 kVA · IST7-30 · IST7-40 · IST6-120, 1 × 30 kVA3/3 or 3/1 only. Rack: IST9. Floor: IST7 30–40 kVA. Modular start: IST6-120 with one module.
60–120 kVA, three-phaseIST7-60 · IST7-80 · IST7-100 · IST7-120 · IST7T-100 · IST7T-120 · IST6-120, 2 × 30 kVA · IST6-120, 3 × 30 kVA · IST6-120, 4 × 30 kVAMonolithic: IST7 60–200 (IST7-80 and -100 upgradable to 120 kVA). Isolated: IST7T-100 and -120. Modular with N+1 in one cabinet: IST6-120.
160–200 kVA, three-phaseIST7-160 · IST7-200 · IST7T-200 · IST6-200, 4 × 50 kVAIST7-160 (upgradable to 200 kVA) and IST7-200, IST7T-200 with isolation, or the modular IST6-200.
300–500 kVA, three-phaseIST6-300, 6 × 50 kVA · IST6-400, 8 × 50 kVA · IST6-500, 10 × 50 kVA · IST6-400H, 4 × 100 kVA · IST6-500H, 5 × 100 kVAModular only: 50 kVA modules (IST6 200–500) for finer steps, 100 kVA modules (IST6 400–1200) for less floor space.
600 kVA–1.2 MVA, three-phaseIST6-600H, 6 × 100 kVA · IST6-800, 8 × 100 kVA · IST6-1000, 10 × 100 kVA · IST6-1200, 12 × 100 kVAIST6 400–1200 cabinets; up to eight UPS in parallel for 9.6 MW.
Lithium beside an IST7 or IST6L6-40 · L6-50 · L6-100L6 cabinets: 40 Ah for 10 / 20 minutes, 50 Ah for 15 / 30 minutes, 100 Ah for 1 to 4 hours.
Lead-acid beside an IST7BB4 · BB5 · BB6 · BB7 · BB8BB4 (9 Ah, 10–40 kVA), BB5 (24 / 40 Ah, up to 60 kW), BB6 (60 Ah, up to 120 kW), BB7 and BB8 (80 / 100 Ah, up to 200 kW).

Single-phase or three-phase?

Start from the supply the site has. Up to 10 kVA most sites are single-phase and the IST3, IST3-J and IST8 cover them. From 10 to 20 kVA the IST9 and the IST7 10–20 kVA also work 1/1, but the input current is about three times that of 3/3. From 30 kVA every AEC UPS needs a three-phase input; 3/1 still feeds single-phase loads.

Monolithic or modular?

A monolithic UPS (IST7, IST7-T) is one power unit sized for the load; redundancy means a second unit in parallel. A modular UPS (IST6) is a cabinet of hot-swap power modules of 30, 50 or 100 kVA: you buy the modules the load needs, add one for N+1 and replace them with the load running. Between the two, the IST7-80, -100 and -160 grow by a setting on the display.

Lead-acid or lithium?

VRLA AGM blocks (OZ Power, 9 to 200 Ah) suit every AEC UPS and have a design life of 6–8 years (9–24 Ah) or 12 years (40–200 Ah) in float at 25 °C. Lithium comes built in (IST8), in one cabinet with the UPS (All-in-One) or as L6 cabinets: LFP cells rated for 5,000 cycles at 50% depth of discharge, modules replaced online, old and new modules together.

Backup time

The backup is set by the battery, not by the UPS. The catalogue gives tables for the All-in-One (minutes per module), the L6 (cabinets and modules per UPS power) and the OZ Power blocks (watts per block). Tell AEC the load and the minutes you need: AEC sizes the battery, the cabinets and the cables.

Questions

Choosing a range: questions

Which AEC UPS for a 10 kVA load on a single-phase supply?

IST3-10 (tower, internal batteries, 10 kW), IST3-J 10 kVA (2U rack, external batteries, 10 kW), or IST9 10 kVA and IST7-10 set to 1/1 (10 kW). Keep the load within about 80% of the rating: a steady 10 kW load wants the next size up or two units.

When is a modular UPS worth it?

When the load will grow, when redundancy (N+1) is required without a second UPS, or when service must not stop the load: IST6 modules are added and replaced online. For a fixed load, a monolithic IST7 does the job with one unit.

Which AEC UPS has an isolation transformer?

The IST7-T, 100 to 200 kVA, with the output isolation transformer built in on every model. For IST6 200–1200 kVA the catalogue lists an output isolation transformer of the same capacity as an option.

Which AEC UPS fit a 19-inch rack?

IST3-J (1–10 kVA, 2U), IST8 (1–3 kVA lithium, 2U) and IST9 (10–40 kVA, 3U), with BBJ and BBJ2 rack battery cabinets.

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need: we answer with the model and the batteries that fit.