Three-phase UPS · 400 V

IST9 Three-phase rack UPS 10–40 kVA, 3U, 400 V

VRLAOnline double conversion

The AEC IST9 is a three-phase online double-conversion UPS of 10 to 40 kVA in a 19-inch chassis 3U high, for 400 V supplies, also as a tower. 3/3 or 3/1 configuration, 1/1 up to 20 kVA; output power factor 1, efficiency up to 96% and 99% in ECO mode, and a touch screen that turns with the unit.

1.0output power factor
≤ 3%input THDi
3Uone height, five ratings
AEC IST9, rendered from its 3D modelDrag to turn

In 3D

Look around the IST9

Drag it round, swipe on a phone or use the arrow keys. X-ray makes the enclosure see-through, so you can see what sits behind the panels.

Pick a size: the turn and the full 3D view follow it. Rendered from AEC's 3D models; the full 3D view zooms in, opens the unit and names every part.

Efficiency

How efficient is the AEC IST9 at your load?

AC/AC efficiency of each operating mode against the load: AEC's measured curves where they exist, elsewhere the typical curve derived from the datasheet figure by AEC's method. The losses and their cost follow the curve at the load you choose: drag along the chart or move the slider.

96%50% · Typical curve, derived from the datasheet efficiency of 96% (AEC method)

Filled points: measured by AEC (AC/AC technical datasheet). Hollow points: a typical curve, the shape of the most similar measured curve (same technology and size) moved to the range's datasheet efficiency: η(load) = reference curve + (datasheet figure − its highest point), AEC's method. Dashed lines: one figure without a load (ECO, W-ECO). Between points the efficiency is read on a straight line; beyond them, the nearest end. Losses = P × (1/η − 1).

Load
—
Lost as heat
—
Energy lost in a year, 24/7
—
Its cost in a year at € per kWh
—
The catalogue's examples use €0.20 per kWh.
Where each figure comes from
ModeEfficiencyKindModelsSource
Double conversion, high-voltage mode25%: 95.4% · 50%: 96% · 75%: 95.7% · 100%: 95.4%Typical curve, derived from the datasheet efficiency of 96% (AEC method)allAEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape)
Double conversion, low-voltage mode25%: 93.4% · 50%: 94% · 75%: 93.7% · 100%: 93.4%Typical curve, derived from the datasheet efficiency of 94% (AEC method)IST9 10 kVA · IST9 20 kVA · IST9 40 kVAAEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape)
ECO99%Datasheet figure, load not statedall

EMEA 2026 catalogue figures: Double conversion, high-voltage mode up to 96% · Double conversion, low-voltage mode up to 94% · ECO up to 99%.

Touch screen

The IST9 touch screen.

Landscape in the rack, portrait in the tower: the display rotates automatically, or is set by hand. Seven languages, Italian included.

TOUCH SCREEN

A touch screen that turns with the UPS

IST9 · touch screen on the home page, the four indicators and the ON / OFF button under it (rack version)
Touch screen on the home page, the four indicators and the ON / OFF button under it (rack version)
IST9 · touch screen: power flow
Power flow
IST9 · touch screen: real-time monitor
Real-time monitor
IST9 · touch screen: history
History
IST9 · touch screen: user login
User login
  • Front panel: touch screen (working status and settings); mains inverter indicator (green in mains mode); bypass indicator (green when the output is on bypass); battery inverter indicator (green in battery mode); fault indicator (red on UPS fault).
  • ON / OFF button: hold 3 s to switch on or off; hold 5–10 s for a battery cold start.
  • Home page: live single-line diagram; the active energy path is drawn in yellow, abnormal mains, bypass, battery or output turn red.
  • Real-time monitor: run, mains, bypass, output and battery information.
  • History: up to 1,000 records, newest first.
  • Login: user and service passwords for different settings (2 levels).
  • Project management: system, battery, communication, dry contact, calibration, smart management.
  • Readings: mains and bypass voltage, current, frequency; output voltage, current, active and apparent power, load, power factor, frequency; battery group voltages, charge / discharge current, status, remaining capacity and backup time; running status of rectifier, inverter, ECO, fans, temperatures, parallel ID.
  • Languages: English, Italian, Spanish, French, Portuguese, Russian, Chinese.
  • Display: landscape, portrait or automatic; backlight 10–300 s, brightness 1–100; date, time and passwords.

What is what

Inside the IST9, part by part.

Each number is named in the list under its picture: the front and the rear, side by side.

Front

Front of the IST9 20 kVA tower: touch screen, the four indicators and the ON / OFF button
The touch screen turns with the UPS: portrait in the tower, landscape in the rack.
  1. Touch screenWorking status and settings. The home page draws the single-line diagram live: the active energy path in yellow, abnormal mains, bypass, battery or output in red.
  2. Mains inverter indicatorGreen in mains mode.
  3. Bypass indicatorGreen when the output is on bypass.
  4. ON / OFF buttonHold 3 s to switch the UPS on or off; hold 5–10 s for a battery cold start.
  5. Battery inverter indicatorGreen in battery mode.
  6. Fault indicatorRed on a UPS fault.

Rear · 10–20 kVA

Rear panel of the IST9 10–20 kVA, rack position
Option slots closed by their covers until a card is fitted.
  1. Wiring terminalsUnder the terminal box's hood; the layout differs slightly between 3/3 and 3/1 mode.
  2. RS232To a PC, for the monitoring software.
  3. Intelligent slotOptional SNMP card, RS485 + dry-contact card or protocol transfer card.
  4. EPO and input dry contactEPO and IN.1 must stay short-circuited for the UPS to work (4-pin terminal supplied).
  5. SNMP (optional)Second slot for the optional SNMP card.
  6. Parallel port (optional)For the optional parallel kit.

Rear · 30–40 kVA

Rear of the IST9 on its tower stands, three-quarter view
Terminals, communication ports and option slots are all on the rear of the 3U chassis.
  1. Wiring terminalsUnder the terminal box's hood; the layout differs slightly between 3/3 and 3/1 mode.
  2. RS232To a PC, for the monitoring software.
  3. Intelligent slotOptional SNMP card, RS485 + dry-contact card or protocol transfer card.
  4. EPO and input dry contactEPO and IN.1 must stay short-circuited for the UPS to work (4-pin terminal supplied).
  5. SNMP (optional)Second slot for the optional SNMP card.
  6. Parallel port (optional)For the optional parallel kit.
  7. PEProtective earth terminal of the 30-40 kVA chassis.

Overview

Key facts

Power range
10–40 kVA
Input / output
3/3 · 3/1 · 1/1 · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L
Efficiency
up to 96% (high-voltage mode) · 94% (low-voltage mode) · 99% ECO
Display
touch screen
Communication
RS232
Network card
SNMP card (optional)
Warranty
3 years
Dimensions W × D × H
438 × 535 × 130 · 438 × 720 × 130 mm

Datasheet

Datasheet IST9.

Every model side by side: keep only what differs, take it as CSV or print it.

IST9 · Technical data
ModelIST9 10 kVAIST9 15 kVAIST9 20 kVAIST9 30 kVAIST9 40 kVA
General
Rated power (kVA / kW, high-voltage mode)10 / 1015 / 1520 / 2030 / 3040 / 40
Rated power (kVA / kW, low-voltage mode)10 / 10not published10 / 10—20 / 20
Configuration3/3 · 3/1 · 1/13/3 · 3/1
Input
Connection3W + N + PE (settable 1W + N + PE)3W + N + PE
Voltage range (phase)high-voltage mode 176–280 V full load, 80–176 V linear derating · low-voltage mode 90–155 V full load, 70–90 V derating
Frequency · power factor · THDi40–70 Hz · ≥ 0.99 · ≤ 3% resistive, ≤ 5% non-linear full load
Bypass50 / 60 Hz ± 10% · voltage ± 20%
Battery
Voltagehigh-voltage mode ± 96 … ± 240 V DC (± 48 … ± 120 cells of 2 V, default ± 96) · low-voltage mode ± 96 … ± 120 V (± 48 … ± 60 cells, default ± 60)
Full-load derating by cells—± 48 … ± 90 cells: 100 × 0.0625 × N / 6 %
Charging current1–10 A (default 4 A)1–20 A (default 15 A)
Output
Voltage220 / 230 / 240 V L-N, 380 / 400 / 415 V L-L (low-voltage mode 110 / 115 / 120 V); 3W + N + PE, settable 1W + N + PE
Frequencytracks the bypass; 50 ± 0.1 or 60 ± 0.1 Hz in battery mode
Waveform · distortion · power factorsine wave · ≤ 2% resistive full load · 1.0
Transfer inverter ↔ bypass< 1 ms synchronised · < 10 ms not synchronised
Inverter overload≤ 105% continuous · 105–110% 60 min · 110–130% 10 min · 130–155% 1 min · > 155% 200 ms · > 200% immediate
Bypass overload< 130% continuous · 130–155% 1 min · > 155% 200 ms
System
Efficiencyup to 96% (high-voltage mode) · 94% (low-voltage mode) · 99% ECO
Display · cold starttouch screen · battery cold start fitted
CommunicationRS232 · options: SNMP, RS485 + dry contact, protocol card for the approved lithium system, parallel card
Noise (20–25 °C)≤ 50 dB half load · ≤ 55 dB 75% and full load≤ 55 dB half load · ≤ 58 dB 75% · ≤ 60 dB full load
Environment−5 … 40 °C · 0–95% RH non-condensing · ≤ 2000 m
Dimensions (W × D × H)438 × 535 × 130 mm (3U)438 × 720 × 130 mm (3U)
Weight18.4 kg18.4 kg18.4 kg34.1 kg34.2 kg

— not stated in the user manual. Specifications are subject to change without notice.

Full technical details12 sections of the EMEA 2026 catalogue: functions, panel, connections, diagrams and ordering codes

Why IST9

013/3 · 3/1 · 1/1 · Three configurationsThree-phase or single-phase output: 3/3 or 3/1 on every size, 1/1 on 10–20 kVA. Set with connector jumpers and on the touch screen.
0296% · Double-conversion efficiencyThree-level inverter and PFC: up to 96% in double conversion, 99% in ECO mode.
03PF 1 · kVA = kWOutput power factor 1.0; input power factor ≥ 0.99, THDi ≤ 3% at resistive full load.
04Rack · tower · Two ways to install3U in a 19-inch cabinet or upright on its base: the touch screen turns automatically.
05±96…±240 V · Battery voltage set on siteHigh-voltage mode: ±48 to ±120 cells of 2 V (default ±96); lead-acid or the approved lithium system.
06Self-maintenance · Fans, dust, remindersFan speed follows the load, dedust cycles, reminders for capacitors, fans, batteries and filter.

OPERATING COST

What efficiency means at 20 kW

Losses are energy turned into heat: paid once at the meter and again in the room cooling.

  • Online double conversion at 96%: 0.83 kW lost, 7,300 kWh per year, ≈ € 1,460 per year.
  • ECO mode at 99%: 0.20 kW lost, 1,770 kWh per year, ≈ € 350 per year.
  • Assumptions: 20 kW load, 24/7, € 0.20/kWh. Losses = P × (1/η − 1). ECO is for single units, with the bypass within its range. Indicative values.
What efficiency means at 20 kW
ModeLossesEnergy lost / yearCost / year
Online double conversion · 96%0.83 kW7,300 kWh≈ € 1,460
ECO mode · 99%0.20 kW1,770 kWh≈ € 350

FLEXIBILITY

Three-phase or single-phase, set on the terminals

10–20 kVA work in 3/3, 3/1 or 1/1 mode; 30–40 kVA in 3/3 or 3/1 mode. The mode is set with connector jumpers on the rear terminals and on the touch screen.

  • 3/3 mode: three in, three out (10–40 kVA).
  • 3/1 mode: three in, one out (10–40 kVA).
  • 1/1 mode: one in, one out (10–20 kVA only).
  • Connector jumpers, 10–20 kVA: four jumper types (types 1–2 two-pin, 3–4 three-pin) for 3/3, 3/1 or 1/1 mode.
  • Connector jumpers, 30–40 kVA: one 3-pin jumper type, used only in 3/1 mode; it short-circuits the three-phase bypass input and the three-phase output terminals.
  • Set on the screen: work mode on the System management page. Output 3W + N + PE, settable to 1W + N + PE; input 3W + N + PE (on 10–20 kVA settable to 1W + N + PE).
  • High-voltage mode: 220 / 230 / 240 V phase voltage (380 / 400 / 415 V line), default 220 V.
  • Low-voltage mode: 110 / 115 / 120 V (190 / 200 / 208 V line), default 120 V; 20 kVA delivers 10 kVA, 40 kVA delivers 20 kVA.
  • 50 / 60 Hz: the UPS monitors the grid frequency and self-adapts.
  • ±5 V output voltage fine adjustment.

HOW IT WORKS

Online double conversion, five operating modes

Rectifier / PFC, inverter, charger and bypass static switch. Inputs: mains, bypass and battery; outputs: inverter, bypass and maintenance bypass (with the distribution module). On battery, the rectifier / PFC boosts the battery voltage onto the DC bus.

  • Normal mode: rectifier and inverter supply the load; the charger charges the battery.
  • Battery mode: with the mains abnormal, the rectifier switches to the battery input and boosts it onto the DC bus.
  • Bypass mode: with the bypass in range, the load is fed from the bypass when the UPS is off (if enabled) or on a fault.
  • ECO mode: single UPS; the bypass feeds the load while it is normal, at 99% efficiency.
  • Maintenance bypass: with the distribution module, the load stays supplied while the UPS is serviced.
  • Auto restart: after a complete outage the UPS shuts down about 1 min after the battery low-voltage point, then restarts by itself in normal mode when the mains returns.
  • Transfer inverter ↔ bypass: < 1 ms synchronised, < 10 ms not synchronised.

REAR PANEL

Same front and width, two chassis depths

Every IST9 is 438 mm wide and 130 mm (3U) high: 535 mm deep for 10–20 kVA, 720 mm deep for 30–40 kVA. Terminals, communication ports and option slots are on the rear.

IST9 · rear: terminals and ports
IST9 · rear with numbered parts
IST9 · rear: terminals and ports
IST9 · rear with numbered parts
  • 10–20 kVA: 438 × 535 × 130 mm, 18.4 kg.
  • 30–40 kVA: 438 × 720 × 130 mm, 34.1 / 34.2 kg.
  • Wiring terminals: bypass, AC output, AC input, battery.
  • RS232 port, standard.
  • Intelligent slot: SNMP, RS485 + dry contact or lithium protocol card.
  • EPO and input dry contact IN.1 (default: maintenance bypass detection).
  • SNMP and parallel port, optional; PE terminal on 30–40 kVA.
  • Terminal layout differs slightly between 3/3 and 3/1 mode.

INSTALLATION

Rack or tower, with its own modules

UPS, distribution module and battery box all fit a 19-inch cabinet. Rack: distribution module above the UPS, battery box below it. Tower: modules side by side on joint bases.

IST9 · rack front with the touch screen
IST9 · standing as a tower
IST9 · rack units with their modules
  • Rack-mounted, 3U, with 3U handles; tower on a support base, with the screen reading upright.
  • Distribution module (optional): input, bypass and output breakers and the maintenance bypass breaker behind a front panel. Removing the protection plate signals the UPS to transfer to bypass before the maintenance breaker is closed.
  • Battery box (optional): always mounted below the UPS in the rack. A DC battery switch is required between battery and UPS.
  • Backfeed protection: from the distribution module with backfeed contactor, or from a backfeed protection contactor between distribution box and UPS, rated above the UPS operating current and labelled for backfeed risk.
  • 438 × 130 mm (W × H, 3U); depth 535 / 720 mm.
  • Weight 18.4 kg (10–20 kVA) · 34.2 kg (40 kVA).
  • Altitude ≤ 2000 m; operating temperature −5 … 40 °C.

SMART FUNCTIONS

Inrush loads, generators, fixed frequency, site tests

Functions set on the touch screen for inrush loads, generators, fixed-frequency outputs and site testing, plus self-maintenance of fans and dust.

  • Impact load mode: for outputs with inrush loads such as transformers; prevents the excitation current from damaging the UPS. Enabled on the screen before the load is started.
  • Generator mode: when enabled, battery charging is disabled (for operation from a generator).
  • Frequency converter: output frequency fixed at 50 or 60 Hz, independent of the input; bypass not used.
  • Test load: self-aging function, test load rate settable 10–110%.
  • Phase sequence calibration: when enabled, a wrong input phase sequence is tolerated; the output runs normally without derating and the alarm is still reported.
  • Short-circuit time: inverter protection time on output short circuit, settable 10–200 ms.
  • Fan speed follows the load: longer fan life, less noise.
  • Standard dedust (load below 50%): fans at full speed for 2.5 s every 2.5 s, for 1 min.
  • Timed dedust: the same cycle for N minutes (1–60).
  • Regular dedust: 200 s at full speed every 1–720 h.
  • Optional air filter fitted in the right panel; fans reached by removing the right panel.
  • Auto-start at power-on: on, off or non-off. Bypass on or off when the UPS is off, or forced.
  • Smart management reminders: electrolytic capacitor use time 1–84 months; fan use time 1–84 months; battery replacement 1–120 months; dust filter cleaning 1–12 months.

BATTERY AND OVERLOAD

A battery chosen for the site, an inverter that holds

Battery string in high-voltage mode: ±48 to ±120 cells of 2 V (default ±96), i.e. ±96 V to ±240 V DC (±192 V at the default).

  • Charging current 1–10 A (10–20 kVA, default 4 A) · 1–20 A (30–40 kVA, default 15 A).
  • Battery capacity setting 7–999 Ah.
  • 30–40 kVA, ±48 to ±90 cells: full-load point derated to 100 × 0.0625 × N / 6 % (N = cells).
  • Lead-acid or lithium: battery type set on the screen; lead-acid, or the approved lithium battery system via the RS485 protocol card.
  • Battery tests: standard (10 s on battery), deep (to the low-voltage alarm) or regular (set time, 1–255 min).
  • Charge control: average and float charge voltage per cell, temperature compensation 0–5 mV/°C, forced charge, battery resting.
  • Inverter overload: 105% continuous · 110% 60 min · 130% 10 min · 155% 1 min · 200% 200 ms; > 200% immediate protection.
  • Bypass overload: < 130% continuous · 155% 1 min · > 155% 200 ms.
  • Input window, high-voltage mode: full load from 176 to 280 V phase voltage; from 80 to 176 V the output is derated linearly (load 15–100%).
  • Input window, low-voltage mode: full load 90–155 V, 70–90 V linear derating (load 75–100%).
  • Input frequency 40–70 Hz; bypass synchronisation 50 / 60 Hz ± 10%; bypass voltage ± 20%.
  • Battery cold start: the UPS starts from the battery with no mains (hold ON / OFF for 5–10 s). On complete outage it switches off about 1 min after the low-voltage point to protect the battery.
A battery chosen for the site, an inverter that holds
LoadInverterBypass
105%continuous—
< 130%—continuous
110%60 min—
130%10 min—
155%1 min1 min
> 155%—200 ms
200%200 ms—
> 200%immediate protection—

CONNECTIVITY AND PARALLEL

Connected, and ready for redundancy

RS232 as standard; SNMP, RS485 + dry contact and lithium protocol cards in the intelligent slot; parallel card for N+1 redundancy.

  • Parallel system: units started one by one, then joined; voltage difference within 8 V, circulating current below 3 A.
  • A faulty unit leaves the system automatically with an alarm; after the exit procedure it can be serviced or replaced online.
  • New units join online and share the current. N+1: total load up to N times one unit.
  • EPO and IN.1: by default (NC) IN.1 and EPO must be shorted for the UPS to run; both can be set NC or NO.
  • IN.1 open (maintenance bypass detection): the UPS transfers to bypass. EPO open: inverter and bypass output shut down.
  • IN.1 can be programmed as external maintenance bypass, transformer over-temperature, charge disable or discharge disable.
  • Recommended breakers: 1.5–2 times the max. input current, without leakage protection; DC breaker rated above 250 V DC. Cables per user manual for about 5 m; above 20 m increase the section.
Connected, and ready for redundancy
ModelModeAC input (A)Bypass input (A)DC input (A)AC output (A)
10 kVA3/332 × 3P32 × 3P100 × 3P32 × 3P
10 kVA3/132 × 3P63 × 1P100 × 3P63 × 1P
10 kVA1/180 × 1P63 × 1P100 × 3P63 × 1P
20 kVA3/363 × 3P50 × 3P100 × 3P50 × 3P
20 kVA3/163 × 3P125 × 1P100 × 3P125 × 1P
20 kVA1/1150 × 1P125 × 1P100 × 3P125 × 1P
30 kVA3/3100 × 3P100 × 3P160 × 3P100 × 3P
30 kVA3/1100 × 3P200 × 1P160 × 3P200 × 1P
40 kVA3/3100 × 3P100 × 3P200 × 3P100 × 3P
40 kVA3/1100 × 3P250 × 1P200 × 3P250 × 1P

PLANNING AND ORDERING

Currents, codes and options

Maximum steady-state phase current (A). Size breakers and cables on these currents; recommended breakers are on the Connectivity page.

  • Distribution module: input, bypass, output and maintenance bypass breakers; versions for 10–20 and 30–40 kVA.
  • Battery box: mounted below the UPS in the rack; DC battery switch between battery and UPS.
  • Parallel kit: parallel card and 2 m cable, CAN communication between units; not hot-swap.
  • Dry-contact kit: 3 outputs (mains, battery, inverter or bypass) and 2 inputs (battery temperature, battery breaker or remote on / off).
  • Lithium protocol card: RS485 on RJ45 for the approved lithium battery system, plus one RS485 channel for monitoring.
  • SNMP card: remote monitoring via web page.
Currents, codes and options
ModelModeAC input (A)Bypass input (A)DC input (A)AC output (A)
10 kVA3/319155615
10 kVA3/119465646
10 kVA1/157465646
20 kVA3/335—5630
20 kVA3/135915691
20 kVA1/1105915691
30 kVA3/359468346
30 kVA3/15913883138
40 kVA3/3756111161
40 kVA3/175182111182

Ordering codes IST9

CodeDescription
IST9-20IST9 20 kVA, 1:1 · 3:1 · 3:3, external batteries, with power distribution box and maintenance breaker
IST9-20-[n]X9As above with 2, 4, 6, 8 or 10 BBJ2 rack battery cabinets: n = 32, 64, 96, 128 or 160 × 12 V 9 Ah
IST9-10-[n]X9 · IST9-15-[n]X9IST9 10 or 15 kVA in the same way: power distribution box, maintenance breaker and 2, 4, 6, 8 or 10 BBJ2 rack battery cabinets (AEC EMEA product data)
IST9-10 · IST9-30 · IST9-40Code on request
PAR-IST9Parallel board
DRYCNT-IST3/9 · SNMPDry-contact relay board · internal SNMP board
BBJ2Rack battery cabinet, max. 16 × 12 V 9 Ah, 3U

Diagrams

The IST9, in diagrams

The path of the power, the ratings, the footprints and the losses, drawn from the figures of the EMEA 2026 catalogue.

How the power flows

Pick an operating mode: the path the power takes to the load lights up.

Maintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypassMaintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypass

Normal. Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 96% (high-voltage mode; ECO single UPS).

The ratings

Every model in the range, in proportion to its power.

  1. IST9 10 kVA10 kVA · 10 kW
  2. IST9 20 kVA20 kVA · 20 kW
  3. IST9 30 kVA30 kVA · 30 kW
  4. IST9 40 kVA40 kVA · 40 kW

Losses per 100 kW of load

Worked out as P × (1/η − 1) at the stated maximum efficiency, with the load steady all year. high-voltage mode; ECO single UPS.

  1. Double conversion 96%4.17 kW36,500 kWh/year
  2. ECO 99%1.01 kW8,850 kWh/year

Phase configurations

Input / output: three-phase (3) or single-phase (1). 1/1 on 10–20 kVA only.

UPS
3/3 3~ → 3~
UPS
3/1 3~ → 1~
UPS
1/1 1~ → 1~

Questions

Questions people ask

Can the IST9 supply single-phase loads from a three-phase input?

Yes: every IST9 works in 3/3 or 3/1 mode, and the 10–20 kVA models also in 1/1. The mode is set with connector jumpers on the rear terminals and on the touch screen.

What are the IST9 dimensions and weights?

Every IST9 is 438 mm wide and 130 mm (3U) high, for a 19-inch rack or standing as a tower. It measures 438 × 535 × 130 mm and 18.4 kg for 10–20 kVA, 438 × 720 × 130 mm and 34.1 / 34.2 kg for 30–40 kVA. The touch screen turns automatically between landscape and portrait.

How efficient is the IST9?

Up to 96% in online double conversion and 99% in ECO mode, with output power factor 1 (kVA = kW). At a 20 kW load running 24/7, AEC's indicative calculation gives about 7,300 kWh lost per year in double conversion against 1,770 kWh in ECO mode.

Which batteries does the IST9 use, and how is backup time extended?

The battery string is set on site: in high-voltage mode ±48 to ±120 cells of 2 V (default ±96), that is ±96 to ±240 V DC, lead-acid or the approved lithium system via the protocol card. For the IST9 20 kVA, AEC codes combine the UPS with 2, 4, 6, 8 or 10 BBJ2 rack cabinets, from 32 to 160 × 12 V 9 Ah, always mounted below the UPS.

Can IST9 units work in parallel for redundancy?

Yes, with the optional parallel card and port (CAN communication between units) for N+1 redundancy, where the total load stays within N times one unit. A faulty unit leaves the system automatically, and units join or leave online.

Which communication options does the IST9 have?

An RS232 port, the EPO and a programmable input (IN.1) are standard. The intelligent slot takes an SNMP card for web monitoring, an RS485 + dry-contact card (3 outputs, 2 inputs) or the protocol card for the approved lithium battery system.

What should be planned for the IST9 installation?

The IST9 runs at −5 … 40 °C, up to 2000 m. Size breakers at 1.5–2 times the maximum input current without leakage protection, with a DC breaker rated above 250 V DC and a DC battery switch between battery and UPS; the optional distribution module adds input, bypass, output and maintenance bypass breakers.

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST9 10–40 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.