Central power supply (CPSS) · EN 50171

CPSS 10–200 Central power supply (CPSS) to EN 50171

VRLA

The AEC CPSS7 is a three-phase central power supply system designed to EN 50171 and built on the IST7 platform: ten ratings from 10 to 200 kVA (8 to 160 kW) in four frames, online double conversion with 0 ms transfer to battery, 120% constant overload without time limit, and recharge in under 12 hours.

EN 50171central supply for safety services
8–160 kWten ratings, four frames
0 mstransfer to battery
THD < 1%sine wave on linear loads
AEC CPSS 10–200

Overview

Key facts

Ratings
10–200 kVA
Voltage
L-N 220 / 230 / 240 V · L-L 380 / 400 / 415 V
Power factor · THDi
≥ 0.99 · ≤ 3%
Voltage · frequency
L-N 220 / 230 / 240 V ± 1% · L-L 380 / 400 / 415 V ± 1% · 50 / 60 Hz ± 0.1%
Power factor · waveform
0.8 · pure sine wave, THD < 1% linear
Efficiency · overload
96% · constant up to 120%
Battery life · recharge
10–12 years · < 12 hours
Noise · temperature · humidity
< 65 dB · 0–40 °C · 0–95%
Standards
CE · EN 50171 · EN 62040-1 · EN 62040-2 · EN 62040-3
Connectivity
·

Models

Choose your CPSS 10–200.

Central power supply system to EN 50171, 10–200 kVA

CPSS7-108±96 … ±240Battery voltage (V DC)1–10Max. charging current (A)
CPSS7-2016±144 … ±240Battery voltage (V DC)1–10Max. charging current (A)
CPSS7-3024±144 … ±240Battery voltage (V DC)1–20Max. charging current (A)
CPSS7-4032±144 … ±240Battery voltage (V DC)1–20Max. charging current (A)
CPSS7-6048±168 … ±288Battery voltage (V DC)1–30Max. charging current (A)
CPSS7-8064±168 … ±288Battery voltage (V DC)1–30Max. charging current (A)
CPSS7-10080±168 … ±288Battery voltage (V DC)1–30Max. charging current (A)
CPSS7-12096±168 … ±288Battery voltage (V DC)1–30Max. charging current (A)
CPSS7-160128±168 … ±288Battery voltage (V DC)1–40Max. charging current (A)
CPSS7-200160±168 … ±288Battery voltage (V DC)1–40Max. charging current (A)
CPSS 10–200 Models
ModelOutput power (kW)Battery voltage (V DC)Max. charging current (A)W × D × H (mm)Weight (kg), without / with internal batteries
CPSS7-108±96 … ±2401–10250 × 806 × 88064 / 95
CPSS7-2016±144 … ±2401–10250 × 806 × 88064 / 137.6
CPSS7-3024±144 … ±2401–20300 × 842 × 1250102.5 / 249.7
CPSS7-4032±144 … ±2401–20300 × 842 × 1250102.5 / 249.7
CPSS7-6048±168 … ±2881–30400 × 960 × 1193153
CPSS7-8064±168 … ±2881–30400 × 960 × 1193163
CPSS7-10080±168 … ±2881–30400 × 960 × 1193165
CPSS7-12096±168 … ±2881–30400 × 960 × 1193167
CPSS7-160128±168 … ±2881–40600 × 1000 × 1600294
CPSS7-200160±168 … ±2881–40600 × 1000 × 1600296

Datasheet

Datasheet CPSS 10–200.

Every model side by side: keep only what differs, take it as CSV or print it.

CPSS 10–200 · Technical data
ModelCPSS7-10 · 20CPSS7-30 · 40CPSS7-60 … 120CPSS7-160 · 200
Model
Output power (kW)8 · 1624 · 3248 · 64 · 80 · 96128 · 160
FrameTowerCabinet
Input
Voltage · frequency80–280 V L-N / 138–485 V L-L · 40–70 Hz380 / 400 / 415 V (138–485 V L-L) · 40–70 Hz
Power factor · THDi≥ 0.99 · ≤ 3%
Configurations3:3 · 3:1 · 1:13-4W + PE
Output
Voltage · frequencyL-N 220 / 230 / 240 V ± 1% · L-L 380 / 400 / 415 V ± 1% · 50 / 60 Hz ± 0.1%
Power factor · waveform0.8 · pure sine wave, THD < 1% linear
Efficiency · overload96% · constant up to 120%
Battery
Voltage (V DC)±96 … ±240 (10) · ±144 … ±240 (20)±144 … ±240±168 … ±288, external
Charging current1–10 A1–20 A1–30 A1–40 A
Battery life · recharge10–12 years · < 12 hours
General
W × D × H (mm)250 × 806 × 880300 × 842 × 1250400 × 960 × 1193600 × 1000 × 1600
Weight (kg)64 · with internal batteries 95 (10 kVA), 137.6 (20 kVA)102.5 · with internal batteries 249.7153 · 163 · 165 · 167294 · 296
Noise · temperature · humidity< 65 dB · 0–40 °C · 0–95%
StandardsCE · EN 50171 · EN 62040-1 · EN 62040-2 · EN 62040-3

From the AEC UPS Catalogue EMEA 2026, CPSS7 pages. Weights as the AEC IST7 of the same rating (same body): without internal batteries, and with them where the 10–40 kVA towers carry them. All information is indicative and may be modified by AEC at any time.

Full technical details5 sections of the EMEA 2026 catalogue: functions, panel, connections, diagrams and ordering codes

Why CPSS 10–200

01InverterThree-level, digital. Pure sine wave, THD ≤ 1% on linear loads; output 220 / 230 / 240 V L-N, 50 / 60 Hz ± 0.1%.
02OverloadConstant 120%: lamps and drives start together after a blackout, and the inverter carries 120% without time limit.
03ChargerCharging current set to the battery: 1–10 A on 10–20 kVA, 1–20 A on 30–40 kVA, 1–30 A on 60–120 kVA, 1–40 A on 160–200 kVA.
04InputClean for the grid: input PF ≥ 0.99, THDi ≤ 3%, wide input window: works with generators and weak grids.

WHAT A CPSS IS

Safety services, powered from one battery

A central power supply system feeds the safety services of a building from one battery, during a fire, an earthquake or a blackout. It must comply with EN 50171, which calls for a CPSS in crowded areas and public places.

  • It supplies emergency lighting, smoke extraction, fire-fighting equipment, alarm systems, CO detection and exit signs.
  • Required in hospitals, schools, museums, cinemas and theatres, hotels, shopping centres, offices and workplaces, car parks and tunnels.
  • What the CPSS7 provides: batteries with 10–12 years expected life, 120% constant overload, recharge from low battery in under 12 h, casing resistant to heat and fire.
  • UPS and CPSS are not interchangeable: same components, different standards and uses. The installation of the safety system remains the responsibility of the installer.

HOW IT WORKS

Built on the AEC IST7 platform

CPSS7 uses the IST7 three-level inverter and digital control, with ratings, overload and charging set for safety services. With mains present the safety loads run on the inverter and the battery charges; in a blackout the battery takes over with no break (0 ms).

  • Overload or fault: load on the static bypass, < 1 ms synchronised; service: maintenance bypass, the load stays on the mains.
  • Colour touch screen with live single-line diagram, two access levels, battery test and event records with time stamp.
  • RS485 standard, dry contacts OUT.1–OUT.5, input contacts for battery ground fault, EPO and IN.1; SNMP and relay cards in the intelligent slots.

THE RANGE

Four frames, 10 to 200 kVA

CPSS7 10–40 kVA in two compact towers with internal or external batteries, CPSS7 60–200 kVA in two cabinets with external batteries. Output power factor 0.8 (kW = 0.8 × kVA).

  • CPSS7-10 · 20: 8 · 16 kW, tower 250 × 806 × 880 mm.
  • CPSS7-30 · 40: 24 · 32 kW, tower 300 × 842 × 1250 mm.
  • CPSS7-60 · 80 · 100 · 120: 48 · 64 · 80 · 96 kW, cabinet 400 × 960 × 1193 mm.
  • CPSS7-160 · 200: 128 · 160 kW, cabinet 600 × 1000 × 1600 mm.
  • Input 40–70 Hz; configurations 3:3 · 3:1 · 1:1 on 10–40 kVA; 96% efficiency in double conversion; noise < 65 dB, 0–40 °C, 0–95% RH.

ORDERING AND SYSTEMS

Sized on the project, up to four in parallel

AEC sizes a CPSS in three steps: the load (safety loads in kW with their starting peaks; the 120% overload covers simultaneous starts), the backup time set by the fire-safety design of the building, and the site (ventilated battery room or cabinet, periodic function and duration tests, event records kept by the CPSS).

  • Codes: CPSS7-10 · 20, CPSS7-30 · 40, CPSS7-60 · 80 · 100 · 120, CPSS7-160 · 200; battery cabinets BB4 … BB8 with fuses and Q1 disconnector, empty or with OZ Power batteries.
  • Options: SNMP card, relay / RS485 card, parallel kit, battery temperature sensor.
  • Up to four CPSS7 in parallel, redundant or for more power; a unit with a fault leaves the system by itself, with an alarm; batteries can be shared.
  • Fire-safety rules and required backup time depend on the building and the country: AEC sizes each CPSS on the project data.

Diagrams

The CPSS 10–200, in diagrams

The path of the power, the ratings, the footprints and the losses, drawn from the figures of the EMEA 2026 catalogue.

The ratings

Every model in the range, in proportion to its power.

  1. CPSS7-1010 kVA · 8 kW
  2. CPSS7-2020 kVA · 16 kW
  3. CPSS7-3030 kVA · 24 kW
  4. CPSS7-4040 kVA · 32 kW
  5. CPSS7-6060 kVA · 48 kW
  6. CPSS7-8080 kVA · 64 kW
  7. CPSS7-100100 kVA · 80 kW
  8. CPSS7-120120 kVA · 96 kW
  9. CPSS7-160160 kVA · 128 kW
  10. CPSS7-200200 kVA · 160 kW

Phase configurations

Input / output: three-phase (3) or single-phase (1). 3/1 · 1/1 on 10–40 kVA; 60–200 kVA 3-4W + PE.

UPS
3/3 3~ → 3~
UPS
3/1 3~ → 1~
UPS
1/1 1~ → 1~

Footprints to scale

Front view of the cabinets, all at the same scale, beside a 2 m rule. W × D × H, mm.

00.5 m1 m1.5 m2 m10–20 kVA250 × 806 × 88030–40 kVA300 × 842 × 1,25060–120 kVA400 × 960 × 1,193160–200 kVA600 × 1,000 × 1,600
  • 10–20 kVA 250 × 806 × 880 mm · 64 kg · 95 kg (10 kVA) / 137.6 kg (20 kVA) with internal batteries
  • 30–40 kVA 300 × 842 × 1,250 mm · 102.5 kg · 249.7 kg with internal batteries
  • 60–120 kVA 400 × 960 × 1,193 mm · 153 (60) · 163 (80) · 165 (100) · 167 (120) kg
  • 160–200 kVA 600 × 1,000 × 1,600 mm · 294 (160) · 296 (200) kg

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC CPSS 10–200 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.