Modular UPS · 400 V

IST6 200–500 Hot-swappable modular UPS, 400 V

VRLAOnline double conversion

The AEC IST6 200–500 is a modular online double-conversion UPS for 400 V supplies with hot-swappable 50 kVA power modules, in cabinets of 200, 300, 400 and 500 kVA. One extra module gives N+1 redundancy; efficiency up to 98.1%, THDi ≤ 1.5%, and up to eight UPS in parallel.

50→500kVA in 50 kVA steps
N+1one extra module
98.1%efficiency, 50 kVA module
Hot-swapmodules replaced online
AEC IST6 200–500, rendered from its 3D modelDrag to turn

In 3D

Look around the IST6 200–500

Drag it round, swipe on a phone or use the arrow keys. X-ray makes the enclosure see-through, so you can see what sits behind the panels.

Pick a size: the turn and the full 3D view follow it. Rendered from AEC's 3D models; the full 3D view zooms in, opens the unit and names every part.

Hands on

Open the IST6 200–500 yourself.

Click the unit: the door opens, then a module comes out. Drag to move it by hand. The 3D shows every part.

AEC IST6 200–500, closed

Every part in 3D

Efficiency

How efficient is the AEC IST6 200–500 at your load?

AC/AC efficiency of each operating mode against the load: AEC's measured curves where they exist, elsewhere the typical curve derived from the datasheet figure by AEC's method. The losses and their cost follow the curve at the load you choose: drag along the chart or move the slider.

98.1%50% · Typical curve, derived from the datasheet efficiency of 98.1% (AEC method)

Filled points: measured by AEC (AC/AC technical datasheet). Hollow points: a typical curve, the shape of the most similar measured curve (same technology and size) moved to the range's datasheet efficiency: η(load) = reference curve + (datasheet figure − its highest point), AEC's method. Dashed lines: one figure without a load (ECO, W-ECO). Between points the efficiency is read on a straight line; beyond them, the nearest end. Losses = P × (1/η − 1). ECO and W-ECO modes are listed without an efficiency figure.

Load
—
Lost as heat
—
Energy lost in a year, 24/7
—
Its cost in a year at € per kWh
—
The catalogue's examples use €0.20 per kWh.
Where each figure comes from
ModeEfficiencyKindModelsSource
Online, double conversion25%: 97.5% · 50%: 98.1% · 75%: 97.8% · 100%: 97.5%Typical curve, derived from the datasheet efficiency of 98.1% (AEC method)allAEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape)
ECO99.2%Datasheet figure, load not statedallAEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape)

EMEA 2026 catalogue figures: Online, double conversion up to 98.1%.

The display

The IST6 modular display

The real display, drawn by AEC's own simulator: pick a UPS state (normal, battery, bypass) or a main page.

UPS state
IST6 modular: Normal operation

IST6 modular · the real display

Normal operation

Main pages
IST6 300 kVA in 3D, the displayThe camera moves in to the display. · 0:06

What is what

Inside the IST6 200–500, part by part.

Each number on the picture is named in the list.

Front, door open · 200–300 kVA

IST6 300 kVA with the front door open: switches, control box, bypass and power modules
200 / 300 kVA frame, 607 mm wide: the four switches at the top, then the system control box, the bypass module and the power modules, all from the front.
  1. Bypass switchThe static bypass supply.
  2. Maintenance bypass switchFeeds the load directly while the UPS is serviced.
  3. Mains switchThe rectifier's mains supply.
  4. Output switchTo the load.
  5. Battery cold startStarts the UPS from the battery when there is no mains and no bypass.
  6. System control boxFive hot-swappable cards: expansion and SNMP positions (optional), control cards 1 and 2, monitoring card. 4 inputs and 3 outputs (7 + 5 with the expansion card), Modbus, RS232, RS485, 2 EPO inputs (NO and NC).
  7. Bypass moduleCentralised static bypass, at the top of the module column.
  8. Power modules50 kVA in 3U each, replaced with the load running; 6 slots on 300 kVA, 4 on 200 kVA.

Front, doors open · 400–500 kVA

IST6 500 kVA with both doors open: switches and system control box on the left, power modules on the right
400 / 500 kVA frame, 1203 mm wide: the four switches and the system control box on the left, the 50 kW power modules on the right.
  1. Output switch
  2. Maintenance bypass switch
  3. Bypass switch
  4. Mains switch
  5. System control box
  6. Battery cold start
  7. Power modules50 kVA in 3U each, replaced with the load running.
IST6 300 kVA in 3D, door openThe door opens on what is inside. · 0:06

Overview

Key facts

Power range
200–500 kVA
Input / output
3/3 · 380 / 400 / 415 V
Efficiency
up to 98.1% · ECO, WECO, source share, redundancy sleep
Battery
±240 V DC nominal (±180 … ±300 V), 30–50 × 12 V blocks, standard 40
Communication
Modbus · RS232 · RS485 · 4 inputs / 3 outputs dry contact
Network card
SNMP card (optional)
Parallel
up to 8 UPS, current imbalance ≤ 5% · BSC dual bus and multi-bus (3 buses)
Warranty
3 years
Dimensions W × D × H
607 × 860 × 2000 · 1203 × 864 × 2000 mm

Datasheet

Datasheet IST6 200–500.

Every model side by side: keep only what differs, take it as CSV or print it.

IST6 200–500 · Technical data
Model200 kVA300 kVA400 kVA500 kVA
Cabinet
Power modules · rating4 × 50 kVA6 × 50 kVA8 × 50 kVA10 × 50 kVA
Bypass module200 kVA · 3U300 kVA · 3U400 kVA · 3U500 kVA · 4.5U
Input
System · voltage3Ph+N+PE · 380 / 400 / 415 V; 138–485 V (full power 324–485 V, linear derating below)
Frequency · PF · THDi40–70 Hz · ≥ 0.99 · ≤ 1.5% at full load
Bypass304–438 V; synchronisation 50 ± 5 / 60 ± 6 Hz; settable window
Battery
Lead-acid±240 V DC nominal (±180 … ±300 V), 30–50 × 12 V blocks, standard 40
Lithium (with BMS card)±256 V DC nominal (±192 … ±294.4 V), 120–200 cells, standard 160
Charging currentup to 30 A × number of modules · cold start · shared battery
Output
System · voltage3Ph+N+PE (3Ph+PE optional) · 380 / 400 / 415 V ± 1%
Power factor · THDvsettable 0.8–1.0 (default 1.0) · ≤ 1% linear, ≤ 4% non-linear
Frequency · phase errortracks the bypass; 50 / 60 ± 0.1 Hz with mains abnormal · ≤ 1° balanced, ≤ 3° unbalanced
Transfermains ↔ battery 0 ms · bypass ↔ inverter < 1 ms synchronised, < 15 ms
Inverter overload (PF 1)≤ 105% continuous · 105–110% 60 min · 110–125% 10 min · 125–150% 1 min · > 150% to bypass
Bypass overload≤ 130% continuous · 130–150% 5 min · 150–200% 1 min · 200–300% 100 ms
System
Efficiency · modesup to 98.1% · ECO, WECO, source share, redundancy sleep
Parallelup to 8 UPS, current imbalance ≤ 5% · BSC dual bus and multi-bus (3 buses)
CommunicationModbus · RS232 · RS485 · 4 inputs / 3 outputs dry contact · options: SNMP, expansion, BMS
Environment0 … 40 °C · 0–95% RH · ≤ 2000 m (derating to 4000 m) · IP20 · < 70 dB · EMC C3
W × D × H (mm)607 × 860 × 2000607 × 860 × 20001203 × 864 × 20001203 × 864 × 2000
Weight without power modules224 kg236 kg459 kg506 kg

Power module 500 × 650 × 130 mm, 39 kg. Data from the IST6 200–500 kVA user manual. Specifications are subject to change without notice.

Full technical details20 sections of the EMEA 2026 catalogue: functions, panel, connections, diagrams and ordering codes

Why IST6 200–500

01200→500 · Sized to the siteFour cabinets with 4, 6, 8 or 10 power modules of 50 kVA; modules added when the load grows.
0298.1% · High efficiencyUp to 98.1% in double conversion, plus ECO and WECO modes and redundancy sleep for spare modules.
03≤ 1.5% · Clean for the gridInput power factor ≥ 0.99 and THDi ≤ 1.5% at full load: smaller upstream cables, transformers and generators.
04Hot-swap · Continuity firstPower modules and the five cards of the system control box are hot-swappable; two control cards back each other up.
0530–50 · Battery set on site30 to 50 blocks of 12 V per string, lead-acid or lithium; charging current up to 30 A per module.
06Touch · Easy to runTouch screen with live power flow, 10,000 events, wave capture of faults and monthly energy records.

OPERATING COST

What 98.1% means at 240 kW

Every point of efficiency is heat that is not paid for at the meter and in the room cooling.

  • 4.65 kW losses at 98.1% efficiency; 40,700 kWh per year; ≈ € 8,100 per year at € 0.20/kWh.
  • Each additional point of efficiency at this load saves about 2.5 kW, that is about 22,100 kWh per year.
  • IST6 300 kVA at 80% load (240 kW), 8,760 h/year, cooling excluded; losses = P × (1/η − 1). Indicative values.

FEATURE OVERVIEW

The features, group by group

The IST6 200–500 kVA features, in the catalogue's four groups.

IST6 200–500 · The features, group by group
  • Reliable: system redundancy (components, modules and UPS); power walk-in, a smooth transfer from battery to the rectifier; short-circuit protection with settable trip time; backfeed protection for upstream maintenance staff; smart charge scheme, single module up to 30 A; wide input 138–485 V, 40–70 Hz; anti-corrosion coating on all PCBs.
  • Flexible: lead-acid or lithium batteries; common battery bank in parallel systems; frequency converter 50 ↔ 60 Hz; fan dedusting function; parallel up to 8 UPS, dual and multi-bus.
  • Intelligent: W-ECO mode; fault trace with smart wave capture; programmable dry contacts with 10 input and 17 output functions; intelligent redundancy sleep; smart generator mode; live single-line diagram on the touch screen.
  • Efficiency and grid: up to 98.1% efficiency in double conversion; ECO and W-ECO modes; input THDi ≤ 1.5%, power factor ≥ 0.99; self-load test without external load banks.
  • Power walk-in, short-circuit protection and backfeed protection are advanced protection functions of the 50 kVA power module.
  • Up to 98.1% efficiency; input THDi ≤ 1.5%; 30 A charging per module; 8 UPS in parallel.

THE RANGE

Four cabinets, one 50 kVA module

Single-column cabinets for 200 and 300 kVA, double-column cabinets for 400 and 500 kVA: the same power module, the same display, the same functions.

IST6 200–500 · single cabinet, front
IST6 200–500 · cabinet with the display, front
  • 200 · 300 kVA: single column, 607 mm wide; 400 · 500 kVA: double column, 1203 mm wide; height 2000 mm.
  • Power module 500 × 650 × 130 mm, 39 kg.
  • Codes: IST6-200 cabinet for up to 4 × 50 kVA modules; IST6-300 for up to 6 × 50 kVA; IST6-400 for up to 8 × 50 kVA; IST6-500 for up to 10 × 50 kVA, all without modules; IST6-50-J 50 kVA / 50 kW power module.
Four cabinets, one 50 kVA module
Cabinet200 kVA300 kVA400 kVA500 kVA
Power modules (50 kVA)46810
Bypass module200 kVA · 3U300 kVA · 3U400 kVA · 3U500 kVA · 4.5U
W × D × H (mm)607 × 860 × 2000607 × 860 × 20001203 × 864 × 20001203 × 864 × 2000
Weight without power modules224 kg236 kg459 kg506 kg
Mains input current345 A518 A690 A863 A
Cooling air flow (min.)2420 m³/h3630 m³/h4840 m³/h6050 m³/h

MODULES AND HOT-SWAP

50 kVA in 3U, replaced with the load running

Rectifier, inverter and DC/DC converter in each 3U power module; the bypass module carries the static switch. Power modules and control cards are hot-swappable.

IST6 200–500 · power module
IST6 200–500 · power module
IST6 200–500 · power module, front and rear connectors
  • 50 kVA power module: 500 × 650 × 130 mm, 39 kg. Bypass module: 3U (200–400 kVA), 4.5U (500 kVA).
  • Front: 1 RUN (green), 2 ALARM (yellow), 3 FAULT (red), 4 ready switch (green unlocked, red locked). Rear: 5 communication port, 6 output port, 7 input port (AC input and DC battery).
  • Step 1, unlock: ready switch to unlocked, indication green, the module can be removed.
  • Step 2, pull out: remove the fixing screws and pull the module out by its handles onto a lift truck; the other modules keep supplying the load.
  • Step 3, insert and lock: slide the new module in, fasten the screws and lock; indication red, the module joins the system.
  • 2 system control cards backing each other up; 5 hot-swappable control box cards; wait ≥ 15 min before opening a removed module.

INSIDE THE CABINET

Every module in front, switches in reach

300 kVA and 500 kVA with the door open, next to their structure layouts from the user manual.

IST6 200–500 · cabinet open: modules in front
IST6 200–500 · cabinet front: bypass module and power modules, numbered
IST6 200–500 · cabinet open, switches
IST6 200–500 · cabinet front with numbered parts
  • 200 / 300 kVA: 1 bypass switch, 2 maintenance bypass switch, 3 output switch, 4 mains switch, 5 battery cold start button, 6 system control box with five hot-swappable cards, 7 bypass module, 8 power modules 1–6 (200 kVA: 4 module slots).
  • Module sequence (200 / 300 kVA), from the top: bypass module, then power modules 1 to 6.
  • 400 / 500 kVA: 1 output switch, 2 system control box, 3 maintenance bypass switch, 4 bypass switch, 5 mains switch, 6 SPD (optional), 7 SPD switch (optional), 8 power modules (even above, odd below), 9 bypass module 4.5U, 10 battery cold start button.
  • 500 kVA: 10 × 50 kVA power modules; 400 kVA: 8 module slots.

ARCHITECTURE

Online double conversion in every module

Power flow in each operating mode, as drawn in the user manual: N power modules in parallel and one bypass module.

IST6 200–500 · power flow in red: normal mode, through rectifier and inverter
IST6 200–500 · power flow in red: battery mode
IST6 200–500 · power flow in red: static bypass
IST6 200–500 · power flow in red: maintenance bypass
  • Mains mode: each module rectifies the mains and the inverter supplies the load; the battery is charged.
  • Battery mode: mains abnormal, the DC/DC converter boosts the battery to the inverters, 0 ms.
  • Bypass mode: on overload or fault the bypass module supplies the load.
  • Maintenance bypass mode: bypass, mains and output switches open; the load stays on the maintenance bypass for service.
  • Two control cards: primary and secondary system control cards, hot-swappable, backing each other up.
  • Synchronised modules: CAN communication inside and between cabinets for synchronisation and current sharing.
  • Current sharing: load shared equally between power modules within 5%.
  • No break: mains ↔ battery transfer time 0 ms; bypass ↔ inverter < 1 ms synchronised.
  • Input power factor ≥ 0.99; input THDi ≤ 1.5% at full load; 100% unbalanced load.

SCALE AND SLEEP

50 kVA steps, up to 8 UPS in parallel

Add 50 kVA modules or whole UPS as the site grows; set redundancy and redundancy sleep from the screen.

IST6 200–500 · display: smart mode (module sleep) settings
IST6 200–500 · display: system run information
  • Step size 50 kVA: one 3U module at a time, in free slots up to the cabinet rating.
  • 4 → 10 modules per cabinet: 200, 300, 400 or 500 kVA cabinets.
  • × 8 UPS in parallel, with N+X redundancy between UPS.
  • N+X, two redundancy levels: basic and redundant modules per cabinet and per parallel system.
  • Redundancy sleep (Smart mode › Sleep redundancy): spare modules can be put to sleep at light load, with a sleep cycle period (h) and a sleep safety load capacity (kVA) set on screen; settings also include parallel basic and redundant UPS and basic and redundant modules inside the cabinet.
  • Running info shows the parameter match between UPS and the state of both system cards.
  • Alarms when module or cabinet redundancy is missing or insufficient.
  • Over RS485, one display can show the whole parallel system.
  • Modules and further UPS are added and configured by AEC service.

SMART ENERGY

Modes that save energy and protect the grid

Power flow of each mode as drawn in the user manual.

IST6 200–500 · power flow in red: ECO mode, load on the bypass
IST6 200–500 · power flow in red: mains and bypass feeding the output, battery charging
IST6 200–500 · power flow in red: mains and battery feeding the modules together
IST6 200–500 · display: ECO operation
  • ECO mode: with the bypass within the ECO window, the static bypass supplies the load and the inverter is in standby; the rectifier keeps the battery charged. Window ±5 / ±10 / ±15% (default ±15%), ±2 / ±4% (default ±2%).
  • WECO mode: grid-tied operation on top of ECO; the inverter compensates the harmonics of the input current, raising the power factor and lowering THDi.
  • Mains and battery source share: when the mains is too low to support the load, mains and battery supply the power modules together; when the mains recovers, the UPS returns to mains mode and recharges the battery.
  • Generator mode: generator start output and generator-mode input; charging can be prohibited on generator.
  • Grid-tied self-load: load test shown live on the home page, with its own alarms (self-load switch, time-out).
  • Frequency converter: output state available on the home page.
  • Up to 98.1% efficiency; ECO window ±5 … ±15%; WECO harmonic compensation; mains + battery source share.

PERFORMANCE

Full power from 324 to 485 V

Full power from 324 to 485 V line voltage; below, the load capacity is derated linearly down to 10% at 173 V, and the UPS still runs down to 138 V.

  • 40–70 Hz · PF ≥ 0.99 · THDi ≤ 1.5% at full load · TN-S, TN-C, TN-C-S, TT; RCD breakers upstream not recommended.
  • Inverter overload (linear load, PF 1): ≤ 105% continuous, 105–110% 60 min, 110–125% 10 min, 125–150% 1 min; above 150% to bypass at once. PF 0.9: 105–110% 60 min, above 110% to bypass; PF 0.8: above 105% to bypass.
  • Bypass overload: ≤ 130% continuous, 130–150% 5 min, 150–200% 1 min, 200–300% 100 ms; above 300% immediate protection.
  • Backfeed protection: a dry-contact output signals "bypass SCR abnormal" for the backfeed device.
  • Option: an output isolation transformer of the same capacity is available.
  • Settable bypass window: max. +10 … +25% (default +15%), min. −10 … −30% (default −20%), frequency ±2 … ±20%.
  • Input line voltage 138–485 V; THDi ≤ 1.5% at full load; output voltage accuracy ≤ 1%; bypass 300% for 100 ms.
Full power from 324 to 485 V
OutputValue
Voltage380 / 400 / 415 V ± 1%
Power factorsettable 0.8–1.0, default 1.0
THDv≤ 1% linear · ≤ 4% non-linear
Phase error≤ 1° balanced · ≤ 3° unbalanced
Frequency, mains abnormal50 / 60 Hz ± 0.1 Hz
Load step 0↔100%< 5%, recovery ≤ 20 ms
DC component−200 … +200 mV
Transfer bypass ↔ inverter< 1 ms synchronised · < 15 ms
System3Ph+N+PE · 3Ph+PE optional

ADVANCED PROTECTION

Protection that keeps the load and the people safe

Three functions of the 50 kVA power module that protect the grid, the load and the maintenance staff.

IST6 200–500 · timing chart: mains, battery and rectifier power
IST6 200–500 · short-circuit trip on one output, the others keep running
IST6 200–500 · inputs opened, red arrows
  • Power walk-in, no step on the mains or the generator: when the mains returns after an outage, the rectifier waits a delay t1, then takes the power over from the battery gradually during t2; a smooth transfer from battery mode to double conversion, with no impact on the input grid or on a generator.
  • Short-circuit protection, settable trip time up to 200 ms: on an output short circuit the UPS supplies a high current for a set time, from 20 to 200 ms, so that the breaker of the faulty load trips quickly while the other loads keep running.
  • Backfeed protection, safe upstream maintenance: if the static bypass fails, the UPS detects it and a dry-contact output (bypass SCR abnormal) opens the backfeed device on the bypass input, so no voltage returns towards the upstream switchboard. Enabled from the settings.
  • t1 + t2 delay and walk-in time; 20–200 ms short-circuit trip time; SCR bypass fault detected; 17 dry-contact output functions.

BATTERIES

±240 V lead-acid or ±256 V lithium

Split battery +/N/−, ±240 V DC nominal (40 blocks of 12 V); 30 to 50 blocks accepted, with the output factor below for short strings.

IST6 200–500 · display: battery settings, management
IST6 200–500 · display: battery charge settings
IST6 200–500 · display: battery test
  • Charging current max. 30 A per power module (system default 20 A).
  • Lithium: ±256 V nominal, 120–200 cells (standard 160), with the BMS card.
  • Battery setting: cell voltages for protection, alarm, equalising and floating charge, charging current, test time.
  • Charge management: charge limit coefficient in C, temperature compensation, timed and forced equalising charge.
  • Battery test: standard or depth test with mains normal, battery floating and load ≥ 15%.
  • Common battery: shared battery pack mode available for parallel systems.
  • Start from battery: hold the battery cold start button for more than 3 s to start the UPS from the battery.
  • Lithium: optional BMS expansion card with charge- and discharge-disable inputs.
  • Options: battery temperature kit for charge compensation; battery trip kit (24 V DC) for the DC breaker.
  • 30–50 blocks of 12 V per string; ±240 V lead-acid nominal; 0.05–0.5 C charge limit, lead-acid; best battery temperature 20–30 °C.
±240 V lead-acid or ±256 V lithium
12 V blocks per string (lead-acid)3032343638404244464850
Output factor0.750.80.80.90.9111111

OPERATOR PANEL

Touch screen, five LEDs and a light bar

A colour touch screen, five status LEDs, two-key ON / OFF commands and a status light bar.

IST6 200–500 · display panel: normal operation, blue light bar
IST6 200–500 · display panel: normal operation, blue light bar
IST6 200–500 · display panel: input fault in red
IST6 200–500 · display panel: battery operation, yellow light bar
  • Colour touch screen: live power flow, measurements, settings and records.
  • Five status LEDs (AC/DC, DC/AC, bypass, battery, load): green when normal or active, red when abnormal.
  • ON keys: press both keys for 3 s to power on, no accidental switching; OFF keys: press both keys for 3 s to power off.
  • Status light bar, four states: blue, normal operation; blue flashing, battery mode; yellow, abnormal with UPS still running; red, abnormal with UPS stopped. Alarms also light the yellow or red ambient lamp.
  • Screen settings: date and time, backlight time, language, brightness.

Tap a light: green is normal operation, red an abnormal state, as in the catalogue's table.

AC/DC: green, Rectifier normal

Touch screen, five LEDs and a light bar
LEDGreenRed
AC/DCRectifier normalRectifier abnormal
DC/ACInverter normalInverter abnormal
BypassBypass outputBypass abnormal
BatteryBattery outputBattery low voltage
LoadOutput normalOutput overload

TOUCH SCREEN

Touch a block, read its measurements

The home page draws the UPS as it runs: yellow dots trace the active power path, abnormal blocks turn red, and the bottom line shows output voltage and frequency. Touch a block (bypass, mains, battery, rectifier, inverter, output) to open its page.

  • Bypass info: phase and line voltage, current and frequency of the bypass input.
  • Mains info: phase and line voltage, current and frequency of the mains.
  • Battery info: voltage, charge and discharge current, remaining capacity and time, temperature, state.
  • Inverter info: output voltage, current, power and load of each module.
  • Information menu: running info, history, user log, smart record, device info, wave capture, energy info.
  • Settings menu: cabinet, battery, battery test, output, smart mode, dry contact, screen, password, communication, records.
  • Running info: UPS info, parameter match between UPS, UPS status, system cards 1 and 2.
  • Output info: voltage, current, active, reactive and apparent power, load, PF and frequency.
  • 10,000 records in the history, newest first; 6 live info pages (mains, bypass, rectifier, inverter, battery, output); live single-line diagram with the active power path; 3 s two-key ON / OFF commands.

RECORDS

10,000 events and monthly energy records

10,000 records in the history, newest first. When the record is full, the earliest entry is overwritten.

  • Input and output energy (MWh) recorded month by month (energy info).
  • User log: user operations listed with date and time.
  • Current fault: active faults, time-stamped, from the alarm icon of the menu bar.
  • Smart record: maintenance actions such as part replacements.
  • Smart wave capture: when a fault occurs, the UPS stores the voltage and current waveforms of the event, listed with date and time.
  • Record manage: save or clear history, user log, smart record and wave capture. Battery test screen.

OPERATION

Every operating state, shown live

Real screens of the IST6 200–500 kVA: the yellow dotted line traces the active power path.

  • Inverter output: mains → rectifier → inverter → load, battery charging.
  • Battery: mains abnormal, the battery feeds the inverters, 0 ms.
  • Bypass: load on the bypass module, e.g. on overload or fault.
  • Maintenance bypass: load on the maintenance bypass for service.
  • Grid-tied self-load: load test at commissioning, shown live on the home page.
  • Frequency converter: output frequency independent of the input.
  • ECO: load on the static bypass within the ECO window. WECO: the bypass supplies the load, the inverter compensates harmonics.
  • Transfers: mains ↔ battery 0 ms; inverter ↔ bypass < 1 ms synchronised, < 15 ms not synchronised; 3 s two-key ON / OFF commands.
  • Start from battery: hold the battery cold start button for more than 3 s to start the UPS from the battery.
  • After a long outage: after battery under-voltage protection, the UPS restarts and recharges the battery when the mains returns.
  • Two-key ON / OFF: press both ON or both OFF keys for 3 s; no accidental switching.

CONNECTIVITY

4 + 3 dry contacts, 7 + 5 with the expansion card

System control box: all five cards are hot-swappable. 1 expansion card position (optional), 2 system control card 1, 3 SNMP card position (optional), 4 system control card 2, 5 system monitoring card.

IST6 200–500 · communication panel with numbered ports
IST6 200–500 · dry-contact card
IST6 200–500 · battery temperature sensor and its wires
IST6 200–500 · control board
  • 4 inputs (NO) with 10 functions: battery abnormal, battery earthing abnormal, battery switch off, bypass switch off, generator mode, SPD abnormal, maintenance bypass open, mains switch off, environment smoke abnormal, lamp belt switch off.
  • 3 outputs (NO / NC, 30 V DC / 2 A) with 17 functions: inverter mode, bypass mode, battery mode, battery trip, battery under-voltage alarm, battery under-voltage protection, output overload, UPS abnormal, bypass abnormal, mains abnormal, start generator, ECO mode, inverter abnormal, UPS ON, fan abnormal, UPS alarm, bypass SCR abnormal.
  • 4 + 3 inputs + outputs as standard; 7 + 5 with the expansion card; Modbus, RS232 · RS485 · SNMP; 2 EPO inputs (NO and NC).

PARALLEL AND MULTI-BUS

Up to eight UPS, up to three buses

System layouts from the user manual.

IST6 200–500 · two UPS in parallel: distribution and monitoring
IST6 200–500 · parallel system with STS and dual-supply loads
IST6 200–500 · multi-bus system with STS
IST6 200–500 · parallel cards wiring
  • Parallel system, up to 8 UPS: mains, bypass and AC outputs of the UPS connected in parallel; the control modules keep all UPS synchronised and share the load (imbalance ≤ 5%).
  • BSC dual-bus system: two independent UPS systems synchronised by the bus sync controller; an STS supplies single-input loads.
  • Multi-bus: three buses.
  • Parallel ring: PARALLEL ports of the system control cards in a ring; N UPS need N cables. A 7 m cable is supplied with each UPS.
  • Output of each UPS within ± 2 V and ± 0.1 Hz of the system setting.
  • Parallel mode, parallel address and BSC address set on the screen.
  • EPO linkage: one EPO stops the whole system, or only its UPS (set by AEC service).
  • Shared battery pack and parallel ECO available.

INSTALLATION AND SERVICE

Site conditions and service

0–40 °C, 0–95% RH non-condensing, up to 2000 m, vertical inclination ≤ 5°, good ventilation.

IST6 200–500 · site conditions: temperature, humidity, altitude, inclination, ventilation
IST6 200–500 · clearances around the cabinet
IST6 200–500 · airflow: cold in at the front, hot out at the back
IST6 200–500 · moving the cabinet: right and wrong
  • Clearances: A front ≥ 800, B rear ≥ 500, C top ≥ 500 mm.
  • Airflow front to rear: 2420 m³/h (200 kVA) to 6050 m³/h (500 kVA).
  • Handling: forklift from the short side, or two forklifts from the front.
  • Currents in A, cables in mm² (copper, 90 °C). Breakers valid for short-circuit current below 65 kA. TN-S, TN-C, TN-C-S, TT; RCD breakers not recommended. M12 expansion bolts (by customer); tilt ≤ 15°.
  • Sizing: modules, redundancy, battery and parallel system sized by AEC engineers.
  • Commissioning: start-up, settings, dry contacts and parallel addresses.
  • Maintenance: monthly, quarterly and yearly checks; air filter cleaned or replaced.
  • Expansion: power modules added in free slots; further UPS with the parallel kit.
  • 24/7 AEC technical assistance by phone and WhatsApp; < 30 min WhatsApp reply to technical and commercial questions; 3 years warranty, extendable with a maintenance contract; 21+ countries with spare parts across the Allis Electric group.
  • AEC service: service@aecups.com · +39 393 080 5211 · www.aecups.com
Site conditions and service
Line200 kVA300 kVA400 kVA500 kVA
Mains input345 A · 2×(4×120)518 A · 2×(4×185)690 A · 2×(4×185)863 A · 2×(4×240)
Bypass / output303 A · 2×(4×120)455 A · 2×(4×185)606 A · 2×(4×185)758 A · 2×(4×240)
Battery (40 blocks)434 A · 2×(3×120)651 A · 2×(3×185)868 A · 3×(3×185)1085 A · 3×(3×240)
Mains breaker400 A 3P630 A 3P800 A 3P1000 A 3P

Ordering codes IST6 200–500

CodeDescription
IST6-200Modular cabinet, max. 4 × 50 kVA power modules, without modules
IST6-300Modular cabinet, max. 6 × 50 kVA power modules, without modules
IST6-400Modular cabinet, max. 8 × 50 kVA power modules, without modules
IST6-500Modular cabinet, max. 10 × 50 kVA power modules, without modules
IST6-50-J50 kVA / 50 kW power module
PAR - IST6Parallel kit

Diagrams

The IST6 200–500, in diagrams

The path of the power, the ratings, the footprints and the losses, drawn from the figures of the EMEA 2026 catalogue.

How the power flows

Pick an operating mode: the path the power takes to the load lights up.

Power module × NMaintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypassPower module × NMaintenance bypassMainsRectifierDC busBatteryInverterStatic switchLoadStatic bypass

Normal. Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 98.1% (double conversion, up to; ECO and WECO modes stated without a figure).

The ratings

Every model in the range, in proportion to its power. Each notch is one 50 kVA module.

  1. IST6-200200 kVA · 200 kW
  2. IST6-300300 kVA · 300 kW
  3. IST6-400400 kVA · 400 kW
  4. 500 kVA500 kVA · 500 kW

Modules and redundancy

Move the slider: the modules the load needs light up, and the spare slot holds the N+1 redundancy. Each slot takes one 50 kVA module.

modules working · redundant · free slot

Phase configurations

Input / output: three-phase (3) or single-phase (1).

UPS
3/3 3~ → 3~

In parallel Up to 8 units on the same load, for redundancy or for more power.

Footprints to scale

Front view of the cabinets, all at the same scale, beside a 2 m rule. W × D × H, mm.

00.5 m1 m1.5 m2 m200 kVA cabinet607 × 860 × 2,000300 kVA cabinet607 × 860 × 2,000400 kVA cabinet1,203 × 864 × 2,000500 kVA cabinet1,203 × 864 × 2,000
  • 200 kVA cabinet, single column, without power modules 607 × 860 × 2,000 mm · 224 kg
  • 300 kVA cabinet, single column, without power modules 607 × 860 × 2,000 mm · 236 kg
  • 400 kVA cabinet, double column, without power modules 1,203 × 864 × 2,000 mm · 459 kg
  • 500 kVA cabinet, double column, without power modules 1,203 × 864 × 2,000 mm · 506 kg

Questions

Questions people ask

Which IST6 cabinet sizes are available from 200 to 500 kVA?

Four cabinets with 4, 6, 8 or 10 power modules of 50 kVA. The 200 and 300 kVA are in a single column of 607 × 860 × 2000 mm (224 / 236 kg without modules), 400 and 500 kVA in a double column of 1203 × 864 × 2000 mm (459 / 506 kg). Each 3U power module weighs 39 kg.

How efficient is it, and what does THDi ≤ 1.5% mean in practice?

Efficiency reaches 98.1% in double conversion, with ECO and W-ECO modes and redundancy sleep. Input power factor of 0.99 or above and THDi ≤ 1.5% at full load allow smaller upstream cables, transformers and generators.

How many UPS can be connected in parallel?

Up to eight UPS, with N+X redundancy between UPS and load sharing within 5%. BSC dual-bus and three-bus layouts are supported, and a 7 m parallel cable is supplied with each UPS.

How many batteries does the IST6 200–500 kVA need?

The lead-acid nominal is ±240 V DC with 40 × 12 V blocks; 30 to 50 blocks are accepted, with an output factor of 0.75 at 30 blocks, 0.8 at 32–34, 0.9 at 36–38 and 1 from 40. Lithium runs at ±256 V nominal with 120–200 cells (standard 160) and the BMS card; charging current is up to 30 A per module.

Can modules be replaced with the load running?

Yes: the power modules and the five cards of the system control box are hot-swappable, and two control cards back each other up. A module is unlocked, pulled out and replaced while the others keep supplying the load; wait at least 15 minutes before opening a removed module.

What installation clearances and cooling does it need?

Leave at least 800 mm at the front, 500 mm at the rear and 500 mm on top, with front-to-rear airflow of 2420 m³/h (200 kVA) up to 6050 m³/h (500 kVA). It works at 0 … 40 °C up to 2000 m on TN-S, TN-C, TN-C-S or TT systems; upstream RCD breakers are not recommended.

Which communication options are available?

Modbus, RS232, RS485, two EPO inputs and 4 dry-contact inputs / 3 outputs with programmable functions are standard. Options: SNMP card (Ethernet, SNMP or Modbus), dry-contact expansion to 7 + 5 and a BMS card for lithium batteries.