Modular UPS · 400 V
IST6 200–500 Hot-swappable modular UPS, 400 V
The AEC IST6 200–500 is a modular online double-conversion UPS for 400 V supplies with hot-swappable 50 kVA power modules, in cabinets of 200, 300, 400 and 500 kVA. One extra module gives N+1 redundancy; efficiency up to 98.1%, THDi ≤ 1.5%, and up to eight UPS in parallel.
Drag to turnIn 3D
Look around the IST6 200–500
Drag it round, swipe on a phone or use the arrow keys. X-ray makes the enclosure see-through, so you can see what sits behind the panels.
Pick a size: the turn and the full 3D view follow it. Rendered from AEC's 3D models; the full 3D view zooms in, opens the unit and names every part.
Hands on
Open the IST6 200–500 yourself.
Click the unit: the door opens, then a module comes out. Drag to move it by hand. The 3D shows every part.
Efficiency
How efficient is the AEC IST6 200–500 at your load?
AC/AC efficiency of each operating mode against the load: AEC's measured curves where they exist, elsewhere the typical curve derived from the datasheet figure by AEC's method. The losses and their cost follow the curve at the load you choose: drag along the chart or move the slider.
Filled points: measured by AEC (AC/AC technical datasheet). Hollow points: a typical curve, the shape of the most similar measured curve (same technology and size) moved to the range's datasheet efficiency: η(load) = reference curve + (datasheet figure − its highest point), AEC's method. Dashed lines: one figure without a load (ECO, W-ECO). Between points the efficiency is read on a straight line; beyond them, the nearest end. Losses = P × (1/η − 1). ECO and W-ECO modes are listed without an efficiency figure.
- Load
- —
- Lost as heat
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at € per kWh
- —
- The catalogue's examples use €0.20 per kWh.
Where each figure comes from
| Mode | Efficiency | Kind | Models | Source |
|---|---|---|---|---|
| Online, double conversion | 25%: 97.5% · 50%: 98.1% · 75%: 97.8% · 100%: 97.5% | Typical curve, derived from the datasheet efficiency of 98.1% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99.2% | Datasheet figure, load not stated | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
EMEA 2026 catalogue figures: Online, double conversion up to 98.1%.
The display
The IST6 modular display
The real display, drawn by AEC's own simulator: pick a UPS state (normal, battery, bypass) or a main page.

IST6 modular · the real display
Normal operation
What is what
Inside the IST6 200–500, part by part.
Each number on the picture is named in the list.
Front, door open · 200–300 kVA

- Bypass switchThe static bypass supply.
- Maintenance bypass switchFeeds the load directly while the UPS is serviced.
- Mains switchThe rectifier's mains supply.
- Output switchTo the load.
- Battery cold startStarts the UPS from the battery when there is no mains and no bypass.
- System control boxFive hot-swappable cards: expansion and SNMP positions (optional), control cards 1 and 2, monitoring card. 4 inputs and 3 outputs (7 + 5 with the expansion card), Modbus, RS232, RS485, 2 EPO inputs (NO and NC).
- Bypass moduleCentralised static bypass, at the top of the module column.
- Power modules50 kVA in 3U each, replaced with the load running; 6 slots on 300 kVA, 4 on 200 kVA.
Front, doors open · 400–500 kVA
1234567- Output switch
- Maintenance bypass switch
- Bypass switch
- Mains switch
- System control box
- Battery cold start
- Power modules50 kVA in 3U each, replaced with the load running.
Overview
Key facts
- Power range
- 200–500 kVA
- Input / output
- 3/3 · 380 / 400 / 415 V
- Efficiency
- up to 98.1% · ECO, WECO, source share, redundancy sleep
- Battery
- ±240 V DC nominal (±180 … ±300 V), 30–50 × 12 V blocks, standard 40
- Communication
- Modbus · RS232 · RS485 · 4 inputs / 3 outputs dry contact
- Network card
- SNMP card (optional)
- Parallel
- up to 8 UPS, current imbalance ≤ 5% · BSC dual bus and multi-bus (3 buses)
- Warranty
- 3 years
- Dimensions W × D × H
- 607 × 860 × 2000 · 1203 × 864 × 2000 mm
Applications:Data centresTelecomBanking & financeNetworks & IT roomsTransportPublic buildings
Models
Which IST6 200–500 fits your load?
Every rating has its own page: that model's technical data, ordering codes, batteries and the questions people ask.


IST6-400, 8 × 50 kVA400 kVAThe IST6-400 is a double-column modular online UPS cabinet for up to eight 50 kVA power modules: 400 kVA / 400 kW in 1203 × 864 × 2000 mm.1203 × 864 × 2000 mmSize459 kg without modulesWeightSee the model
IST6-500, 10 × 50 kVA500 kVAThe IST6 500 kVA is the largest cabinet of the 50 kVA platform: ten 50 kVA power modules and a 4.5U bypass module in a 1203 × 864 × 2000 mm double column.1203 × 864 × 2000 mmSize506 kg without modulesWeightSee the model Datasheet
Datasheet IST6 200–500.
Every model side by side: keep only what differs, take it as CSV or print it.
| Model | 200 kVA | 300 kVA | 400 kVA | 500 kVA |
|---|---|---|---|---|
| Cabinet | ||||
| Power modules · rating | 4 × 50 kVA | 6 × 50 kVA | 8 × 50 kVA | 10 × 50 kVA |
| Bypass module | 200 kVA · 3U | 300 kVA · 3U | 400 kVA · 3U | 500 kVA · 4.5U |
| Input | ||||
| System · voltage | 3Ph+N+PE · 380 / 400 / 415 V; 138–485 V (full power 324–485 V, linear derating below) | |||
| Frequency · PF · THDi | 40–70 Hz · ≥ 0.99 · ≤ 1.5% at full load | |||
| Bypass | 304–438 V; synchronisation 50 ± 5 / 60 ± 6 Hz; settable window | |||
| Battery | ||||
| Lead-acid | ±240 V DC nominal (±180 … ±300 V), 30–50 × 12 V blocks, standard 40 | |||
| Lithium (with BMS card) | ±256 V DC nominal (±192 … ±294.4 V), 120–200 cells, standard 160 | |||
| Charging current | up to 30 A × number of modules · cold start · shared battery | |||
| Output | ||||
| System · voltage | 3Ph+N+PE (3Ph+PE optional) · 380 / 400 / 415 V ± 1% | |||
| Power factor · THDv | settable 0.8–1.0 (default 1.0) · ≤ 1% linear, ≤ 4% non-linear | |||
| Frequency · phase error | tracks the bypass; 50 / 60 ± 0.1 Hz with mains abnormal · ≤ 1° balanced, ≤ 3° unbalanced | |||
| Transfer | mains ↔ battery 0 ms · bypass ↔ inverter < 1 ms synchronised, < 15 ms | |||
| Inverter overload (PF 1) | ≤ 105% continuous · 105–110% 60 min · 110–125% 10 min · 125–150% 1 min · > 150% to bypass | |||
| Bypass overload | ≤ 130% continuous · 130–150% 5 min · 150–200% 1 min · 200–300% 100 ms | |||
| System | ||||
| Efficiency · modes | up to 98.1% · ECO, WECO, source share, redundancy sleep | |||
| Parallel | up to 8 UPS, current imbalance ≤ 5% · BSC dual bus and multi-bus (3 buses) | |||
| Communication | Modbus · RS232 · RS485 · 4 inputs / 3 outputs dry contact · options: SNMP, expansion, BMS | |||
| Environment | 0 … 40 °C · 0–95% RH · ≤ 2000 m (derating to 4000 m) · IP20 · < 70 dB · EMC C3 | |||
| W × D × H (mm) | 607 × 860 × 2000 | 607 × 860 × 2000 | 1203 × 864 × 2000 | 1203 × 864 × 2000 |
| Weight without power modules | 224 kg | 236 kg | 459 kg | 506 kg |
Power module 500 × 650 × 130 mm, 39 kg. Data from the IST6 200–500 kVA user manual. Specifications are subject to change without notice.
Full technical details20 sections of the EMEA 2026 catalogue: functions, panel, connections, diagrams and ordering codes
Why IST6 200–500
OPERATING COST
What 98.1% means at 240 kW
Every point of efficiency is heat that is not paid for at the meter and in the room cooling.
- 4.65 kW losses at 98.1% efficiency; 40,700 kWh per year; ≈ € 8,100 per year at € 0.20/kWh.
- Each additional point of efficiency at this load saves about 2.5 kW, that is about 22,100 kWh per year.
- IST6 300 kVA at 80% load (240 kW), 8,760 h/year, cooling excluded; losses = P × (1/η − 1). Indicative values.
FEATURE OVERVIEW
The features, group by group
The IST6 200–500 kVA features, in the catalogue's four groups.

- Reliable: system redundancy (components, modules and UPS); power walk-in, a smooth transfer from battery to the rectifier; short-circuit protection with settable trip time; backfeed protection for upstream maintenance staff; smart charge scheme, single module up to 30 A; wide input 138–485 V, 40–70 Hz; anti-corrosion coating on all PCBs.
- Flexible: lead-acid or lithium batteries; common battery bank in parallel systems; frequency converter 50 ↔ 60 Hz; fan dedusting function; parallel up to 8 UPS, dual and multi-bus.
- Intelligent: W-ECO mode; fault trace with smart wave capture; programmable dry contacts with 10 input and 17 output functions; intelligent redundancy sleep; smart generator mode; live single-line diagram on the touch screen.
- Efficiency and grid: up to 98.1% efficiency in double conversion; ECO and W-ECO modes; input THDi ≤ 1.5%, power factor ≥ 0.99; self-load test without external load banks.
- Power walk-in, short-circuit protection and backfeed protection are advanced protection functions of the 50 kVA power module.
- Up to 98.1% efficiency; input THDi ≤ 1.5%; 30 A charging per module; 8 UPS in parallel.
THE RANGE
Four cabinets, one 50 kVA module
Single-column cabinets for 200 and 300 kVA, double-column cabinets for 400 and 500 kVA: the same power module, the same display, the same functions.


- 200 · 300 kVA: single column, 607 mm wide; 400 · 500 kVA: double column, 1203 mm wide; height 2000 mm.
- Power module 500 × 650 × 130 mm, 39 kg.
- Codes: IST6-200 cabinet for up to 4 × 50 kVA modules; IST6-300 for up to 6 × 50 kVA; IST6-400 for up to 8 × 50 kVA; IST6-500 for up to 10 × 50 kVA, all without modules; IST6-50-J 50 kVA / 50 kW power module.
| Cabinet | 200 kVA | 300 kVA | 400 kVA | 500 kVA |
|---|---|---|---|---|
| Power modules (50 kVA) | 4 | 6 | 8 | 10 |
| Bypass module | 200 kVA · 3U | 300 kVA · 3U | 400 kVA · 3U | 500 kVA · 4.5U |
| W × D × H (mm) | 607 × 860 × 2000 | 607 × 860 × 2000 | 1203 × 864 × 2000 | 1203 × 864 × 2000 |
| Weight without power modules | 224 kg | 236 kg | 459 kg | 506 kg |
| Mains input current | 345 A | 518 A | 690 A | 863 A |
| Cooling air flow (min.) | 2420 m³/h | 3630 m³/h | 4840 m³/h | 6050 m³/h |
MODULES AND HOT-SWAP
50 kVA in 3U, replaced with the load running
Rectifier, inverter and DC/DC converter in each 3U power module; the bypass module carries the static switch. Power modules and control cards are hot-swappable.



- 50 kVA power module: 500 × 650 × 130 mm, 39 kg. Bypass module: 3U (200–400 kVA), 4.5U (500 kVA).
- Front: 1 RUN (green), 2 ALARM (yellow), 3 FAULT (red), 4 ready switch (green unlocked, red locked). Rear: 5 communication port, 6 output port, 7 input port (AC input and DC battery).
- Step 1, unlock: ready switch to unlocked, indication green, the module can be removed.
- Step 2, pull out: remove the fixing screws and pull the module out by its handles onto a lift truck; the other modules keep supplying the load.
- Step 3, insert and lock: slide the new module in, fasten the screws and lock; indication red, the module joins the system.
- 2 system control cards backing each other up; 5 hot-swappable control box cards; wait ≥ 15 min before opening a removed module.
INSIDE THE CABINET
Every module in front, switches in reach
300 kVA and 500 kVA with the door open, next to their structure layouts from the user manual.




- 200 / 300 kVA: 1 bypass switch, 2 maintenance bypass switch, 3 output switch, 4 mains switch, 5 battery cold start button, 6 system control box with five hot-swappable cards, 7 bypass module, 8 power modules 1–6 (200 kVA: 4 module slots).
- Module sequence (200 / 300 kVA), from the top: bypass module, then power modules 1 to 6.
- 400 / 500 kVA: 1 output switch, 2 system control box, 3 maintenance bypass switch, 4 bypass switch, 5 mains switch, 6 SPD (optional), 7 SPD switch (optional), 8 power modules (even above, odd below), 9 bypass module 4.5U, 10 battery cold start button.
- 500 kVA: 10 × 50 kVA power modules; 400 kVA: 8 module slots.
ARCHITECTURE
Online double conversion in every module
Power flow in each operating mode, as drawn in the user manual: N power modules in parallel and one bypass module.




- Mains mode: each module rectifies the mains and the inverter supplies the load; the battery is charged.
- Battery mode: mains abnormal, the DC/DC converter boosts the battery to the inverters, 0 ms.
- Bypass mode: on overload or fault the bypass module supplies the load.
- Maintenance bypass mode: bypass, mains and output switches open; the load stays on the maintenance bypass for service.
- Two control cards: primary and secondary system control cards, hot-swappable, backing each other up.
- Synchronised modules: CAN communication inside and between cabinets for synchronisation and current sharing.
- Current sharing: load shared equally between power modules within 5%.
- No break: mains ↔ battery transfer time 0 ms; bypass ↔ inverter < 1 ms synchronised.
- Input power factor ≥ 0.99; input THDi ≤ 1.5% at full load; 100% unbalanced load.
SCALE AND SLEEP
50 kVA steps, up to 8 UPS in parallel
Add 50 kVA modules or whole UPS as the site grows; set redundancy and redundancy sleep from the screen.


- Step size 50 kVA: one 3U module at a time, in free slots up to the cabinet rating.
- 4 → 10 modules per cabinet: 200, 300, 400 or 500 kVA cabinets.
- × 8 UPS in parallel, with N+X redundancy between UPS.
- N+X, two redundancy levels: basic and redundant modules per cabinet and per parallel system.
- Redundancy sleep (Smart mode › Sleep redundancy): spare modules can be put to sleep at light load, with a sleep cycle period (h) and a sleep safety load capacity (kVA) set on screen; settings also include parallel basic and redundant UPS and basic and redundant modules inside the cabinet.
- Running info shows the parameter match between UPS and the state of both system cards.
- Alarms when module or cabinet redundancy is missing or insufficient.
- Over RS485, one display can show the whole parallel system.
- Modules and further UPS are added and configured by AEC service.
SMART ENERGY
Modes that save energy and protect the grid
Power flow of each mode as drawn in the user manual.




- ECO mode: with the bypass within the ECO window, the static bypass supplies the load and the inverter is in standby; the rectifier keeps the battery charged. Window ±5 / ±10 / ±15% (default ±15%), ±2 / ±4% (default ±2%).
- WECO mode: grid-tied operation on top of ECO; the inverter compensates the harmonics of the input current, raising the power factor and lowering THDi.
- Mains and battery source share: when the mains is too low to support the load, mains and battery supply the power modules together; when the mains recovers, the UPS returns to mains mode and recharges the battery.
- Generator mode: generator start output and generator-mode input; charging can be prohibited on generator.
- Grid-tied self-load: load test shown live on the home page, with its own alarms (self-load switch, time-out).
- Frequency converter: output state available on the home page.
- Up to 98.1% efficiency; ECO window ±5 … ±15%; WECO harmonic compensation; mains + battery source share.
PERFORMANCE
Full power from 324 to 485 V
Full power from 324 to 485 V line voltage; below, the load capacity is derated linearly down to 10% at 173 V, and the UPS still runs down to 138 V.
- 40–70 Hz · PF ≥ 0.99 · THDi ≤ 1.5% at full load · TN-S, TN-C, TN-C-S, TT; RCD breakers upstream not recommended.
- Inverter overload (linear load, PF 1): ≤ 105% continuous, 105–110% 60 min, 110–125% 10 min, 125–150% 1 min; above 150% to bypass at once. PF 0.9: 105–110% 60 min, above 110% to bypass; PF 0.8: above 105% to bypass.
- Bypass overload: ≤ 130% continuous, 130–150% 5 min, 150–200% 1 min, 200–300% 100 ms; above 300% immediate protection.
- Backfeed protection: a dry-contact output signals "bypass SCR abnormal" for the backfeed device.
- Option: an output isolation transformer of the same capacity is available.
- Settable bypass window: max. +10 … +25% (default +15%), min. −10 … −30% (default −20%), frequency ±2 … ±20%.
- Input line voltage 138–485 V; THDi ≤ 1.5% at full load; output voltage accuracy ≤ 1%; bypass 300% for 100 ms.
| Output | Value |
|---|---|
| Voltage | 380 / 400 / 415 V ± 1% |
| Power factor | settable 0.8–1.0, default 1.0 |
| THDv | ≤ 1% linear · ≤ 4% non-linear |
| Phase error | ≤ 1° balanced · ≤ 3° unbalanced |
| Frequency, mains abnormal | 50 / 60 Hz ± 0.1 Hz |
| Load step 0↔100% | < 5%, recovery ≤ 20 ms |
| DC component | −200 … +200 mV |
| Transfer bypass ↔ inverter | < 1 ms synchronised · < 15 ms |
| System | 3Ph+N+PE · 3Ph+PE optional |
ADVANCED PROTECTION
Protection that keeps the load and the people safe
Three functions of the 50 kVA power module that protect the grid, the load and the maintenance staff.



- Power walk-in, no step on the mains or the generator: when the mains returns after an outage, the rectifier waits a delay t1, then takes the power over from the battery gradually during t2; a smooth transfer from battery mode to double conversion, with no impact on the input grid or on a generator.
- Short-circuit protection, settable trip time up to 200 ms: on an output short circuit the UPS supplies a high current for a set time, from 20 to 200 ms, so that the breaker of the faulty load trips quickly while the other loads keep running.
- Backfeed protection, safe upstream maintenance: if the static bypass fails, the UPS detects it and a dry-contact output (bypass SCR abnormal) opens the backfeed device on the bypass input, so no voltage returns towards the upstream switchboard. Enabled from the settings.
- t1 + t2 delay and walk-in time; 20–200 ms short-circuit trip time; SCR bypass fault detected; 17 dry-contact output functions.
BATTERIES
±240 V lead-acid or ±256 V lithium
Split battery +/N/−, ±240 V DC nominal (40 blocks of 12 V); 30 to 50 blocks accepted, with the output factor below for short strings.



- Charging current max. 30 A per power module (system default 20 A).
- Lithium: ±256 V nominal, 120–200 cells (standard 160), with the BMS card.
- Battery setting: cell voltages for protection, alarm, equalising and floating charge, charging current, test time.
- Charge management: charge limit coefficient in C, temperature compensation, timed and forced equalising charge.
- Battery test: standard or depth test with mains normal, battery floating and load ≥ 15%.
- Common battery: shared battery pack mode available for parallel systems.
- Start from battery: hold the battery cold start button for more than 3 s to start the UPS from the battery.
- Lithium: optional BMS expansion card with charge- and discharge-disable inputs.
- Options: battery temperature kit for charge compensation; battery trip kit (24 V DC) for the DC breaker.
- 30–50 blocks of 12 V per string; ±240 V lead-acid nominal; 0.05–0.5 C charge limit, lead-acid; best battery temperature 20–30 °C.
| 12 V blocks per string (lead-acid) | 30 | 32 | 34 | 36 | 38 | 40 | 42 | 44 | 46 | 48 | 50 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Output factor | 0.75 | 0.8 | 0.8 | 0.9 | 0.9 | 1 | 1 | 1 | 1 | 1 | 1 |
OPERATOR PANEL
Touch screen, five LEDs and a light bar
A colour touch screen, five status LEDs, two-key ON / OFF commands and a status light bar.




- Colour touch screen: live power flow, measurements, settings and records.
- Five status LEDs (AC/DC, DC/AC, bypass, battery, load): green when normal or active, red when abnormal.
- ON keys: press both keys for 3 s to power on, no accidental switching; OFF keys: press both keys for 3 s to power off.
- Status light bar, four states: blue, normal operation; blue flashing, battery mode; yellow, abnormal with UPS still running; red, abnormal with UPS stopped. Alarms also light the yellow or red ambient lamp.
- Screen settings: date and time, backlight time, language, brightness.
Tap a light: green is normal operation, red an abnormal state, as in the catalogue's table.
AC/DC: green, Rectifier normal
| LED | Green | Red |
|---|---|---|
| AC/DC | Rectifier normal | Rectifier abnormal |
| DC/AC | Inverter normal | Inverter abnormal |
| Bypass | Bypass output | Bypass abnormal |
| Battery | Battery output | Battery low voltage |
| Load | Output normal | Output overload |
TOUCH SCREEN
Touch a block, read its measurements
The home page draws the UPS as it runs: yellow dots trace the active power path, abnormal blocks turn red, and the bottom line shows output voltage and frequency. Touch a block (bypass, mains, battery, rectifier, inverter, output) to open its page.
- Bypass info: phase and line voltage, current and frequency of the bypass input.
- Mains info: phase and line voltage, current and frequency of the mains.
- Battery info: voltage, charge and discharge current, remaining capacity and time, temperature, state.
- Inverter info: output voltage, current, power and load of each module.
- Information menu: running info, history, user log, smart record, device info, wave capture, energy info.
- Settings menu: cabinet, battery, battery test, output, smart mode, dry contact, screen, password, communication, records.
- Running info: UPS info, parameter match between UPS, UPS status, system cards 1 and 2.
- Output info: voltage, current, active, reactive and apparent power, load, PF and frequency.
- 10,000 records in the history, newest first; 6 live info pages (mains, bypass, rectifier, inverter, battery, output); live single-line diagram with the active power path; 3 s two-key ON / OFF commands.
RECORDS
10,000 events and monthly energy records
10,000 records in the history, newest first. When the record is full, the earliest entry is overwritten.
- Input and output energy (MWh) recorded month by month (energy info).
- User log: user operations listed with date and time.
- Current fault: active faults, time-stamped, from the alarm icon of the menu bar.
- Smart record: maintenance actions such as part replacements.
- Smart wave capture: when a fault occurs, the UPS stores the voltage and current waveforms of the event, listed with date and time.
- Record manage: save or clear history, user log, smart record and wave capture. Battery test screen.
OPERATION
Every operating state, shown live
Real screens of the IST6 200–500 kVA: the yellow dotted line traces the active power path.
- Inverter output: mains → rectifier → inverter → load, battery charging.
- Battery: mains abnormal, the battery feeds the inverters, 0 ms.
- Bypass: load on the bypass module, e.g. on overload or fault.
- Maintenance bypass: load on the maintenance bypass for service.
- Grid-tied self-load: load test at commissioning, shown live on the home page.
- Frequency converter: output frequency independent of the input.
- ECO: load on the static bypass within the ECO window. WECO: the bypass supplies the load, the inverter compensates harmonics.
- Transfers: mains ↔ battery 0 ms; inverter ↔ bypass < 1 ms synchronised, < 15 ms not synchronised; 3 s two-key ON / OFF commands.
- Start from battery: hold the battery cold start button for more than 3 s to start the UPS from the battery.
- After a long outage: after battery under-voltage protection, the UPS restarts and recharges the battery when the mains returns.
- Two-key ON / OFF: press both ON or both OFF keys for 3 s; no accidental switching.
CONNECTIVITY
4 + 3 dry contacts, 7 + 5 with the expansion card
System control box: all five cards are hot-swappable. 1 expansion card position (optional), 2 system control card 1, 3 SNMP card position (optional), 4 system control card 2, 5 system monitoring card.




- 4 inputs (NO) with 10 functions: battery abnormal, battery earthing abnormal, battery switch off, bypass switch off, generator mode, SPD abnormal, maintenance bypass open, mains switch off, environment smoke abnormal, lamp belt switch off.
- 3 outputs (NO / NC, 30 V DC / 2 A) with 17 functions: inverter mode, bypass mode, battery mode, battery trip, battery under-voltage alarm, battery under-voltage protection, output overload, UPS abnormal, bypass abnormal, mains abnormal, start generator, ECO mode, inverter abnormal, UPS ON, fan abnormal, UPS alarm, bypass SCR abnormal.
- 4 + 3 inputs + outputs as standard; 7 + 5 with the expansion card; Modbus, RS232 · RS485 · SNMP; 2 EPO inputs (NO and NC).
PARALLEL AND MULTI-BUS
Up to eight UPS, up to three buses
System layouts from the user manual.




- Parallel system, up to 8 UPS: mains, bypass and AC outputs of the UPS connected in parallel; the control modules keep all UPS synchronised and share the load (imbalance ≤ 5%).
- BSC dual-bus system: two independent UPS systems synchronised by the bus sync controller; an STS supplies single-input loads.
- Multi-bus: three buses.
- Parallel ring: PARALLEL ports of the system control cards in a ring; N UPS need N cables. A 7 m cable is supplied with each UPS.
- Output of each UPS within ± 2 V and ± 0.1 Hz of the system setting.
- Parallel mode, parallel address and BSC address set on the screen.
- EPO linkage: one EPO stops the whole system, or only its UPS (set by AEC service).
- Shared battery pack and parallel ECO available.
INSTALLATION AND SERVICE
Site conditions and service
0–40 °C, 0–95% RH non-condensing, up to 2000 m, vertical inclination ≤ 5°, good ventilation.




- Clearances: A front ≥ 800, B rear ≥ 500, C top ≥ 500 mm.
- Airflow front to rear: 2420 m³/h (200 kVA) to 6050 m³/h (500 kVA).
- Handling: forklift from the short side, or two forklifts from the front.
- Currents in A, cables in mm² (copper, 90 °C). Breakers valid for short-circuit current below 65 kA. TN-S, TN-C, TN-C-S, TT; RCD breakers not recommended. M12 expansion bolts (by customer); tilt ≤ 15°.
- Sizing: modules, redundancy, battery and parallel system sized by AEC engineers.
- Commissioning: start-up, settings, dry contacts and parallel addresses.
- Maintenance: monthly, quarterly and yearly checks; air filter cleaned or replaced.
- Expansion: power modules added in free slots; further UPS with the parallel kit.
- 24/7 AEC technical assistance by phone and WhatsApp; < 30 min WhatsApp reply to technical and commercial questions; 3 years warranty, extendable with a maintenance contract; 21+ countries with spare parts across the Allis Electric group.
- AEC service: service@aecups.com · +39 393 080 5211 · www.aecups.com
| Line | 200 kVA | 300 kVA | 400 kVA | 500 kVA |
|---|---|---|---|---|
| Mains input | 345 A · 2×(4×120) | 518 A · 2×(4×185) | 690 A · 2×(4×185) | 863 A · 2×(4×240) |
| Bypass / output | 303 A · 2×(4×120) | 455 A · 2×(4×185) | 606 A · 2×(4×185) | 758 A · 2×(4×240) |
| Battery (40 blocks) | 434 A · 2×(3×120) | 651 A · 2×(3×185) | 868 A · 3×(3×185) | 1085 A · 3×(3×240) |
| Mains breaker | 400 A 3P | 630 A 3P | 800 A 3P | 1000 A 3P |
Ordering codes IST6 200–500
| Code | Description |
|---|---|
IST6-200 | Modular cabinet, max. 4 × 50 kVA power modules, without modules |
IST6-300 | Modular cabinet, max. 6 × 50 kVA power modules, without modules |
IST6-400 | Modular cabinet, max. 8 × 50 kVA power modules, without modules |
IST6-500 | Modular cabinet, max. 10 × 50 kVA power modules, without modules |
IST6-50-J | 50 kVA / 50 kW power module |
PAR - IST6 | Parallel kit |
Diagrams
The IST6 200–500, in diagrams
The path of the power, the ratings, the footprints and the losses, drawn from the figures of the EMEA 2026 catalogue.
How the power flows
Pick an operating mode: the path the power takes to the load lights up.
Normal. Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 98.1% (double conversion, up to; ECO and WECO modes stated without a figure).
Battery. The mains fails: the battery feeds the DC bus and the inverter carries on without a break. The load does not notice. Transfer: mains ↔ battery 0 ms.
Bypass. Overload or internal fault: the static switch moves the load to the bypass line, fed by the mains.
ECO. The load runs on the bypass and the inverter stands ready: if the mains leaves the set window, the load goes back to the inverter. Higher efficiency, less protection.
Maintenance. The maintenance bypass feeds the load straight from the mains, so the UPS can be isolated for service without switching the load off.
Frequency converter. Output at 50 or 60 Hz whatever the input: the load always runs on the inverter and the bypass is not used.
The ratings
Every model in the range, in proportion to its power. Each notch is one 50 kVA module.
Modules and redundancy
Move the slider: the modules the load needs light up, and the spare slot holds the N+1 redundancy. Each slot takes one 50 kVA module.
modules working · redundant · free slot
Phase configurations
Input / output: three-phase (3) or single-phase (1).
In parallel Up to 8 units on the same load, for redundancy or for more power.
Footprints to scale
Front view of the cabinets, all at the same scale, beside a 2 m rule. W × D × H, mm.
- 200 kVA cabinet, single column, without power modules 607 × 860 × 2,000 mm · 224 kg
- 300 kVA cabinet, single column, without power modules 607 × 860 × 2,000 mm · 236 kg
- 400 kVA cabinet, double column, without power modules 1,203 × 864 × 2,000 mm · 459 kg
- 500 kVA cabinet, double column, without power modules 1,203 × 864 × 2,000 mm · 506 kg
Documents
IST6 200–500 documents.
IST6 200–500 catalogue pages and manuals in English, as PDF.
Questions
Questions people ask
Which IST6 cabinet sizes are available from 200 to 500 kVA?
Four cabinets with 4, 6, 8 or 10 power modules of 50 kVA. The 200 and 300 kVA are in a single column of 607 × 860 × 2000 mm (224 / 236 kg without modules), 400 and 500 kVA in a double column of 1203 × 864 × 2000 mm (459 / 506 kg). Each 3U power module weighs 39 kg.
How efficient is it, and what does THDi ≤ 1.5% mean in practice?
Efficiency reaches 98.1% in double conversion, with ECO and W-ECO modes and redundancy sleep. Input power factor of 0.99 or above and THDi ≤ 1.5% at full load allow smaller upstream cables, transformers and generators.
How many UPS can be connected in parallel?
Up to eight UPS, with N+X redundancy between UPS and load sharing within 5%. BSC dual-bus and three-bus layouts are supported, and a 7 m parallel cable is supplied with each UPS.
How many batteries does the IST6 200–500 kVA need?
The lead-acid nominal is ±240 V DC with 40 × 12 V blocks; 30 to 50 blocks are accepted, with an output factor of 0.75 at 30 blocks, 0.8 at 32–34, 0.9 at 36–38 and 1 from 40. Lithium runs at ±256 V nominal with 120–200 cells (standard 160) and the BMS card; charging current is up to 30 A per module.
Can modules be replaced with the load running?
Yes: the power modules and the five cards of the system control box are hot-swappable, and two control cards back each other up. A module is unlocked, pulled out and replaced while the others keep supplying the load; wait at least 15 minutes before opening a removed module.
What installation clearances and cooling does it need?
Leave at least 800 mm at the front, 500 mm at the rear and 500 mm on top, with front-to-rear airflow of 2420 m³/h (200 kVA) up to 6050 m³/h (500 kVA). It works at 0 … 40 °C up to 2000 m on TN-S, TN-C, TN-C-S or TT systems; upstream RCD breakers are not recommended.
Which communication options are available?
Modbus, RS232, RS485, two EPO inputs and 4 dry-contact inputs / 3 outputs with programmable functions are standard. Options: SNMP card (Ethernet, SNMP or Modbus), dry-contact expansion to 7 + 5 and a BMS card for lithium batteries.