CIRRO-IB · 480V three-phase UPS

CIRIB150-1X30 CIRRO-IB 30 kVA, 480V three-phase UPS

VRLA30 kVAOnline double conversion

The AEC CIRRO-IB CIRIB150-1X30 is a 30 kVA / 30 kW online double-conversion UPS for 480 V three-phase loads, built on one 30 kVA power module, with VRLA batteries on internal trays. Kept at 80 % of its rating, it carries loads up to 24 kW.

One of the frame's five module slots is fitted, so no module is spare at this size; four more modules take the frame to 150 kVA. As configured it weighs 2,191.8 lb (994.2 kg) net.

4-wire · 3P+N480 V 4-wire, wye: three phases, neutral and ground (277/480 V)

30 kVA / 30 kWRating
23.6 × 39.3 × 78.7 inW × D × H
2,191.8 lbWeight
VRLA, internalBattery

Series picture.

AEC CIRRO-IB 150 kVA · 5 modules, rendered from its 3D modelDrag to turn

In 3D

Look around the CIRIB150-1X30

The turntable shows the 150 kVA · 5 modules configuration; the full 3D view opens on this model.

Load by load

The CIRIB150-1X30 at 25, 50, 75 and 100 % load.

Its 30 kW rating in four steps, worked out from its own catalog figures.

At 25, 50, 75 and 100 % load
LoadOutput current per phase, at 480 VEfficiencyHeat to removeHeat to remove (BTU/h)
25 % of the CIRIB150-1X30, 7.5 kW9.0 A per phase95.0 % efficient395 W of heat1,350 BTU/h to cool
50 % of the CIRIB150-1X30, 15 kW18.0 A per phase95.9 % efficient641 W of heat2,190 BTU/h to cool
75 % of the CIRIB150-1X30, 23 kW27.1 A per phase96.0 % efficient938 W of heat3,200 BTU/h to cool
100 % of the CIRIB150-1X30, 30 kW36.1 A per phase95.8 % efficient1.3 kW of heat4,490 BTU/h to cool

Current = kVA × load ÷ (√3 × volts).

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

What is the CIRIB150-1X30?

The code CIRIB150-1X30 orders these catalog items, shipped in 26 cartons:

  • 1 × CIRIB-FRAME: 150 kVA frame, without power modules, 23.6 × 39.4 × 78.7 in (600 × 1,000 × 2,000 mm)
  • 1 × CIRIB-PWR-30: 30 kVA hot-swappable power module, 52 lb (23.6 kg)
  • 24 × CIRIB-BATTR-10x9A: battery tray of 10 × 12 V 9 Ah VRLA blocks, 63.5 lb (28.8 kg) each
  • Architecture: 1 × 30 kVA hot-swappable power module in a 150 kVA / 150 kW frame (scalable to 5 modules / 150 kVA); parallel up to 3 cabinets.

The lines every CIRRO-IB shares, from technology to warranty, are in the CIRRO-IB key facts and in the datasheet below.

1 × 30 kVA power modules fitted in a 5-slot frame: 4 free slots to grow or add redundancy.

Size and floor

How big it is

23.6" W × 39.3" D × 78.7" H (599 × 998 × 1,999 mm); 2,191.8 lb (994.2 kg) net.

6.4 ft²footprint (0.60 m²)
340 lb/ft²floor load of the cabinet alone
Modularform factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

5′9″ FrontSide 23.6″39.3″78.7″

Datasheet

CIRIB150-1X30 datasheet.

The CIRIB150-1X30 in the AEC 2026 catalog, figure by figure. Compare it with every CIRRO-IB model.

CIRIB150-1X30 datasheet
ParameterCIRIB150-1X30
Power
Rated power (kVA)30
Active power (kW)30
Output power factor1.0
Electrical
Input / output480 V three-phase, 4-wire (3P+N)
TopologyOnline double conversion, modular N+X
Efficiency, up to96%
Battery DC bus480 V DC
Battery and runtime
Battery typeVRLA (sealed lead-acid)
Battery configurationInternal Tray System
Runtime at 50 % load45 min
Runtime at 100 % load14 min
Mechanical
Form factorModular
Dimensions W × D × H23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm)
Net weight2,191.8 lb (994.2 kg)
Footprint6.4 ft² (0.60 m²)
Shipping
Cartons26
Common to every CIRRO-IB
Technology3-level IGBT; unity power factor (kVA = kW); 40 A settable charger
Battery, CIRIB150-1X30internal hot-swappable VRLA, up to 240 × 12V 9Ah (240 pcs)
Display7-inch color touchscreen
CommsRS-232, EPO and USB, standard
Network cardSNMP-M (SNMP)
Warranty3 years on UPS · 2 years on VRLA batteries
Quality systemISO 9001:2015, the group's quality system (SGS)

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

CIRIB150-1X30: what people ask

What is the output current of the CIRIB150-1X30?

36.1 A per phase at full load: 30 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the CIRIB150-1X30 from its installation manual and the local electrical code, not from this figure alone.

How much heat does the CIRIB150-1X30 give off?

About 1.3 kW, 4,490 BTU/h, at full load, where it is 95.8% efficient. Plan the room's cooling for a little more than that: the CIRIB150-1X30 is less efficient at part load and while its battery recharges.

How much power do 3 CIRIB150-1X30 give in parallel?

90 kVA: up to 3 units of the same model run in parallel, by the AEC US user manual of the CIRRO-IB. Kept as N+1, with one unit spare, 3 CIRIB150-1X30 carry 60 kVA (60 kW).

Will the CIRIB150-1X30 fit through a standard door?

Yes: 23.6 in (599 mm) across its narrow side and 78.7 in (1,999 mm) high, it passes a standard 36 × 80-inch door upright, with little to spare in height. On the way in, check corridors, elevators and the floor load of the CIRIB150-1X30 (size section above).

The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h

CIRRO-IB

Other CIRRO-IB models

The CIRRO-IB series, with pictures

By power, the CIRIB150-1X30 is the smallest in the CIRRO-IB series, which runs from 30 to 150 kVA. One size up is the CIRIB150-2X30 (30 kVA more and 52 lb heavier).

Every CIRRO-IB model side by side (5)
CIRRO-IB models side by side
ModelPowerPower against this modelNet weightWeight against this modelRuntime at 50 % load
CIRIB150-1X3030 kVAthis page2,192 lbthis page45 min at 50 % load
CIRIB150-2X3060 kVA30 kVA more2,244 lb52 lb heavier14 min at 50 % load
CIRIB150-3X3090 kVA60 kVA more2,296 lb104 lb heavier10.5 min at 50 % load
CIRIB150-4X30120 kVA90 kVA more2,348 lb156 lb heavier6 min at 50 % load
CIRIB150-5X30150 kVA120 kVA more2,400 lb208 lb heavier6 min at 50 % load

The CIRIB150-1X30 for your project