CIRRO-IB · 480V three-phase UPS
CIRIB150-2X30 CIRRO-IB 60 kVA, 480V three-phase UPS
The AEC CIRRO-IB CIRIB150-2X30 is a 60 kVA / 60 kW online double-conversion UPS for 480 V three-phase loads, built on two 30 kVA power modules, with VRLA batteries on internal trays. Kept at 80 % of its rating, it carries loads up to 48 kW.
Two of the frame's five module slots are fitted and three are free; with one module held as a spare (N+1) it carries 30 kVA. As configured it weighs 2,243.8 lb (1,017.8 kg) net.
4-wire · 3P+N480 V 4-wire, wye: three phases, neutral and ground (277/480 V)
Series picture.
Drag to turnIn 3D
Look around the CIRIB150-2X30
The turntable shows the 150 kVA · 5 modules configuration; the full 3D view opens on this model.
The same on every CIRRO-IB:The CIRRO-IB display
Load by load
The CIRIB150-2X30 at 25, 50, 75 and 100 % load.
Its 60 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current per phase, at 480 V | Load on each of its 2 power modules | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|---|
| 25 % of the CIRIB150-2X30, 15 kW | 18.0 A per phase | 25 % on each module | 95.0 % efficient | 789 W of heat | 2,690 BTU/h to cool |
| 50 % of the CIRIB150-2X30, 30 kW | 36.1 A per phase | 50 % on each module | 95.9 % efficient | 1.3 kW of heat | 4,380 BTU/h to cool |
| 75 % of the CIRIB150-2X30, 45 kW | 54.1 A per phase | 75 % on each module | 96.0 % efficient | 1.9 kW of heat | 6,400 BTU/h to cool |
| 100 % of the CIRIB150-2X30, 60 kW | 72.2 A per phase | 100 % on each module | 95.8 % efficient | 2.6 kW of heat | 8,980 BTU/h to cool |
Current = kVA × load ÷ (√3 × volts).
Module load = load ÷ the kVA of the power modules fitted.
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the CIRIB150-2X30 at your load?
The CIRIB150-2X30 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What is the CIRIB150-2X30?
The code CIRIB150-2X30 orders these catalog items, shipped in 27 cartons:
- 1 × CIRIB-FRAME: 150 kVA frame, without power modules, 23.6 × 39.4 × 78.7 in (600 × 1,000 × 2,000 mm)
- 2 × CIRIB-PWR-30: 30 kVA hot-swappable power module, 52 lb (23.6 kg) each
- 24 × CIRIB-BATTR-10x9A: battery tray of 10 × 12 V 9 Ah VRLA blocks, 63.5 lb (28.8 kg) each
- Architecture: 2 × 30 kVA hot-swappable power modules in a 150 kVA / 150 kW frame (scalable to 5 modules / 150 kVA); parallel up to 3 cabinets.
The lines every CIRRO-IB shares, from technology to warranty, are in the CIRRO-IB key facts and in the datasheet below.
2 × 30 kVA power modules fitted in a 5-slot frame: 3 free slots to grow or add redundancy.
Size and floor
How big it is
23.6" W × 39.3" D × 78.7" H (599 × 998 × 1,999 mm); 2,243.8 lb (1,017.8 kg) net.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
The CIRIB150-2X30 takes the clearances, wiring, cable entry and breakers of every CIRRO-IB model, from its AEC US user manual: see them on the CIRRO-IB page.
Place the CIRIB150-2X30 in your room, to the inch, with Room fit
Datasheet
CIRIB150-2X30 datasheet.
The CIRIB150-2X30 in the AEC 2026 catalog, figure by figure. Compare it with every CIRRO-IB model.
| Parameter | CIRIB150-2X30 |
|---|---|
| Power | |
| Rated power (kVA) | 60 |
| Active power (kW) | 60 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 480 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X |
| Efficiency, up to | 96% |
| Battery DC bus | 480 V DC |
| Battery and runtime | |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | Internal Tray System |
| Runtime at 50 % load | 14 min |
| Runtime at 100 % load | 6 min |
| Mechanical | |
| Form factor | Modular |
| Dimensions W × D × H | 23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm) |
| Net weight | 2,243.8 lb (1,017.8 kg) |
| Footprint | 6.4 ft² (0.60 m²) |
| Shipping | |
| Cartons | 27 |
| Common to every CIRRO-IB | |
| Technology | 3-level IGBT; unity power factor (kVA = kW); 40 A settable charger |
| Battery, CIRIB150-2X30 | internal hot-swappable VRLA, up to 240 × 12V 9Ah (240 pcs) |
| Display | 7-inch color touchscreen |
| Comms | RS-232, EPO and USB, standard |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The CIRRO-IB documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
Quick answers
CIRIB150-2X30: what people ask
What is the output current of the CIRIB150-2X30?
72.2 A per phase at full load: 60 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the CIRIB150-2X30 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the CIRIB150-2X30 give off?
About 2.6 kW, 8,980 BTU/h, at full load, where it is 95.8% efficient. Plan the room's cooling for a little more than that: the CIRIB150-2X30 is less efficient at part load and while its battery recharges.
Will the CIRIB150-2X30 fit through a standard door?
Yes: 23.6 in (599 mm) across its narrow side and 78.7 in (1,999 mm) high, it passes a standard 36 × 80-inch door upright, with little to spare in height. On the way in, check corridors, elevators and the floor load of the CIRIB150-2X30 (size section above).
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
CIRRO-IB
Other CIRRO-IB models
By power, the CIRIB150-2X30 is number 2 of 5 in the CIRRO-IB series, which runs from 30 to 150 kVA. One size down is the CIRIB150-1X30 (30 kVA less and 52 lb lighter). One size up is the CIRIB150-3X30 (30 kVA more and 52 lb heavier).
Every CIRRO-IB model side by side (5)
| Model | Power | Power against this model | Net weight | Weight against this model | Runtime at 50 % load |
|---|---|---|---|---|---|
| CIRIB150-1X30 | 30 kVA | 30 kVA less | 2,192 lb | 52 lb lighter | 45 min at 50 % load |
| CIRIB150-2X30 | 60 kVA | this page | 2,244 lb | this page | 14 min at 50 % load |
| CIRIB150-3X30 | 90 kVA | 30 kVA more | 2,296 lb | 52 lb heavier | 10.5 min at 50 % load |
| CIRIB150-4X30 | 120 kVA | 60 kVA more | 2,348 lb | 104 lb heavier | 6 min at 50 % load |
| CIRIB150-5X30 | 150 kVA | 90 kVA more | 2,400 lb | 156 lb heavier | 6 min at 50 % load |
The CIRIB150-2X30 for your project
Send the load, the voltage and the minutes you need from the CIRIB150-2X30. We reply with the configuration, the batteries and the lead time.