CIRRO-IB · 480V three-phase UPS

CIRIB150-2X30 CIRRO-IB 60 kVA, 480V three-phase UPS

VRLA60 kVAOnline double conversion

The AEC CIRRO-IB CIRIB150-2X30 is a 60 kVA / 60 kW online double-conversion UPS for 480 V three-phase loads, built on two 30 kVA power modules, with VRLA batteries on internal trays. Kept at 80 % of its rating, it carries loads up to 48 kW.

Two of the frame's five module slots are fitted and three are free; with one module held as a spare (N+1) it carries 30 kVA. As configured it weighs 2,243.8 lb (1,017.8 kg) net.

4-wire · 3P+N480 V 4-wire, wye: three phases, neutral and ground (277/480 V)

60 kVA / 60 kWRating
23.6 × 39.3 × 78.7 inW × D × H
2,243.8 lbWeight
VRLA, internalBattery

Series picture.

AEC CIRRO-IB 150 kVA · 5 modules, rendered from its 3D modelDrag to turn

In 3D

Look around the CIRIB150-2X30

The turntable shows the 150 kVA · 5 modules configuration; the full 3D view opens on this model.

Load by load

The CIRIB150-2X30 at 25, 50, 75 and 100 % load.

Its 60 kW rating in four steps, worked out from its own catalog figures.

At 25, 50, 75 and 100 % load
LoadOutput current per phase, at 480 VLoad on each of its 2 power modulesEfficiencyHeat to removeHeat to remove (BTU/h)
25 % of the CIRIB150-2X30, 15 kW18.0 A per phase25 % on each module95.0 % efficient789 W of heat2,690 BTU/h to cool
50 % of the CIRIB150-2X30, 30 kW36.1 A per phase50 % on each module95.9 % efficient1.3 kW of heat4,380 BTU/h to cool
75 % of the CIRIB150-2X30, 45 kW54.1 A per phase75 % on each module96.0 % efficient1.9 kW of heat6,400 BTU/h to cool
100 % of the CIRIB150-2X30, 60 kW72.2 A per phase100 % on each module95.8 % efficient2.6 kW of heat8,980 BTU/h to cool

Current = kVA × load ÷ (√3 × volts).

Module load = load ÷ the kVA of the power modules fitted.

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

What is the CIRIB150-2X30?

The code CIRIB150-2X30 orders these catalog items, shipped in 27 cartons:

  • 1 × CIRIB-FRAME: 150 kVA frame, without power modules, 23.6 × 39.4 × 78.7 in (600 × 1,000 × 2,000 mm)
  • 2 × CIRIB-PWR-30: 30 kVA hot-swappable power module, 52 lb (23.6 kg) each
  • 24 × CIRIB-BATTR-10x9A: battery tray of 10 × 12 V 9 Ah VRLA blocks, 63.5 lb (28.8 kg) each
  • Architecture: 2 × 30 kVA hot-swappable power modules in a 150 kVA / 150 kW frame (scalable to 5 modules / 150 kVA); parallel up to 3 cabinets.

The lines every CIRRO-IB shares, from technology to warranty, are in the CIRRO-IB key facts and in the datasheet below.

2 × 30 kVA power modules fitted in a 5-slot frame: 3 free slots to grow or add redundancy.

Size and floor

How big it is

23.6" W × 39.3" D × 78.7" H (599 × 998 × 1,999 mm); 2,243.8 lb (1,017.8 kg) net.

6.4 ft²footprint (0.60 m²)
348 lb/ft²floor load of the cabinet alone
Modularform factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

5′9″ FrontSide 23.6″39.3″78.7″

Datasheet

CIRIB150-2X30 datasheet.

The CIRIB150-2X30 in the AEC 2026 catalog, figure by figure. Compare it with every CIRRO-IB model.

CIRIB150-2X30 datasheet
ParameterCIRIB150-2X30
Power
Rated power (kVA)60
Active power (kW)60
Output power factor1.0
Electrical
Input / output480 V three-phase, 4-wire (3P+N)
TopologyOnline double conversion, modular N+X
Efficiency, up to96%
Battery DC bus480 V DC
Battery and runtime
Battery typeVRLA (sealed lead-acid)
Battery configurationInternal Tray System
Runtime at 50 % load14 min
Runtime at 100 % load6 min
Mechanical
Form factorModular
Dimensions W × D × H23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm)
Net weight2,243.8 lb (1,017.8 kg)
Footprint6.4 ft² (0.60 m²)
Shipping
Cartons27
Common to every CIRRO-IB
Technology3-level IGBT; unity power factor (kVA = kW); 40 A settable charger
Battery, CIRIB150-2X30internal hot-swappable VRLA, up to 240 × 12V 9Ah (240 pcs)
Display7-inch color touchscreen
CommsRS-232, EPO and USB, standard
Network cardSNMP-M (SNMP)
Warranty3 years on UPS · 2 years on VRLA batteries
Quality systemISO 9001:2015, the group's quality system (SGS)

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

CIRIB150-2X30: what people ask

What is the output current of the CIRIB150-2X30?

72.2 A per phase at full load: 60 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the CIRIB150-2X30 from its installation manual and the local electrical code, not from this figure alone.

How much heat does the CIRIB150-2X30 give off?

About 2.6 kW, 8,980 BTU/h, at full load, where it is 95.8% efficient. Plan the room's cooling for a little more than that: the CIRIB150-2X30 is less efficient at part load and while its battery recharges.

Will the CIRIB150-2X30 fit through a standard door?

Yes: 23.6 in (599 mm) across its narrow side and 78.7 in (1,999 mm) high, it passes a standard 36 × 80-inch door upright, with little to spare in height. On the way in, check corridors, elevators and the floor load of the CIRIB150-2X30 (size section above).

The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h

CIRRO-IB

Other CIRRO-IB models

The CIRRO-IB series, with pictures

By power, the CIRIB150-2X30 is number 2 of 5 in the CIRRO-IB series, which runs from 30 to 150 kVA. One size down is the CIRIB150-1X30 (30 kVA less and 52 lb lighter). One size up is the CIRIB150-3X30 (30 kVA more and 52 lb heavier).

Every CIRRO-IB model side by side (5)
CIRRO-IB models side by side
ModelPowerPower against this modelNet weightWeight against this modelRuntime at 50 % load
CIRIB150-1X3030 kVA30 kVA less2,192 lb52 lb lighter45 min at 50 % load
CIRIB150-2X3060 kVAthis page2,244 lbthis page14 min at 50 % load
CIRIB150-3X3090 kVA30 kVA more2,296 lb52 lb heavier10.5 min at 50 % load
CIRIB150-4X30120 kVA60 kVA more2,348 lb104 lb heavier6 min at 50 % load
CIRIB150-5X30150 kVA90 kVA more2,400 lb156 lb heavier6 min at 50 % load

The CIRIB150-2X30 for your project