ETHERNO · 208V three-phase UPS
ETH20 ETHERNO 20 kVA, 208V three-phase UPS
The AEC ETHERNO ETH20 is a 20 kVA / 20 kW online double-conversion UPS for 208 V three-phase loads, with room for 50 Ah lithium modules inside, ordered separately. Kept at 80 % of its rating, it carries loads up to 16 kW.
Series picture.
Drag to turnIn 3D
Look around the ETH20
The turntable shows the 30K · 3 modules configuration; the full 3D view opens on this model.
The same on every ETHERNO:Open the ETHERNO: modules and door, from the catalog's photosThe ETHERNO display
Runtime
The ETH20 with its batteries, at your load.
The ETH20 has no batteries of its own: the chart draws in bold the catalog set-ups built on it, the other ETHERNO set-ups faded behind. The same chart as the ETHERNO page. 2026 catalog, new batteries.
At 50 % of the rating
ETHERNO 20 kVA
2 lithium modules27 min3 lithium modules41 minETHERNO 10 kVA
1 lithium module27 min2 lithium modules55 min3 lithium modules82 minETHERNO 30 kVA
3 lithium modules27 minTable: this model at 25, 50, 75 and 100 % load
| Model | 25% load | 50% load | 75% load | 100% load |
|---|---|---|---|---|
| ETHERNO 20 kVA · 2 lithium modulesETH20-2X50A-LI | 55 min | 27 min | 17.5 min | 14 min |
| ETHERNO 20 kVA · 3 lithium modulesETH20-3X50A-LI | 84 min | 41 min | 26.5 min | 20 min |
Load by load
The ETH20 at 25, 50, 75 and 100 % load.
Its 20 kW rating in four steps, worked out from its own catalog figures.
| Load | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|
| 25 % of the ETH20, 5.0 kW | 92.5 % efficient | 405 W of heat | 1,380 BTU/h to cool |
| 50 % of the ETH20, 10 kW | 93.9 % efficient | 650 W of heat | 2,220 BTU/h to cool |
| 75 % of the ETH20, 15 kW | 94.0 % efficient | 957 W of heat | 3,270 BTU/h to cool |
| 100 % of the ETH20, 20 kW | 93.8 % efficient | 1.3 kW of heat | 4,510 BTU/h to cool |
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the ETH20 at your load?
The ETH20 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
Sizing
What load fits the ETH20?
Its minutes on battery depend on the batteries chosen with it: send the load in kW and the minutes you need, and AEC sizes the bank for the ETH20.
From the 2026 catalog
What is the ETH20?
- Output: 20,000 VA / 20,000 W (unity power factor, kVA = kW).
- Battery: accepts hot-swappable LiFePO4 50 Ah modules (ETH-50-LI), ordered separately.
The lines every ETHERNO shares, from technology to warranty, are in the ETHERNO key facts and in the datasheet below.
Size and floor
How big it is
12.6" W × 39.1" D × 49.2" H (320 × 993 × 1,250 mm); 227 lb (103 kg) net. It ships in one carton of 18 × 43.7 × 56.9 in, 279.9 lb (127 kg) gross.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
The ETH20 takes the clearances, wiring, cable entry and breakers of every ETHERNO model, from its AEC US user manual: see them on the ETHERNO page.
Datasheet
ETH20 datasheet.
The ETH20 in the AEC 2026 catalog, figure by figure. Compare it with every ETHERNO model.
| Parameter | ETH20 |
|---|---|
| Power | |
| Rated power (kVA) | 20 |
| Active power (kW) | 20 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 208 V three-phase |
| Topology | Online Double Conversion |
| Efficiency, up to | 94% |
| Battery DC bus | 240 V DC |
| Battery and runtime | |
| Battery type | Not included, ordered separately |
| Battery configuration | Lithium modules inside, ordered separately |
| Mechanical | |
| Form factor | Tower |
| Dimensions W × D × H | 12.6 × 39.1 × 49.2 in (320 × 993 × 1,250 mm) |
| Net weight | 227 lb (103 kg) |
| Footprint | 3.4 ft² (0.32 m²) |
| Shipping | |
| Cartons | 1 |
| Shipping weight | 279.9 lb |
| Common to every ETHERNO | |
| Technology | 3-level IGBT; cold start, self-cleaning and smart functions |
| Display | 4.3-inch color touchscreen |
| Comms | Modbus and dry contacts, standard |
| Battery, ETH20 | accepts hot-swappable LiFePO4 50 Ah modules (ETH-50-LI), ordered separately |
| Network card | SNMP-L (SNMP) |
| Warranty | 5 years |
| Certification | UL 1778 listed, UL file E543003 (AEC UPS USA LLC) |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The ETHERNO documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
Quick answers
ETH20: what people ask
How much heat does the ETH20 give off?
About 1.3 kW, 4,510 BTU/h, at full load, where it is 93.8% efficient. Plan the room's cooling for a little more than that: the ETH20 is less efficient at part load and while its battery recharges.
Will the ETH20 fit through a standard door?
Yes: 12.6 in (320 mm) across its narrow side and 49.2 in (1,250 mm) high, it passes a standard 36 × 80-inch door upright. On the way in, check corridors, elevators and the floor load of the ETH20 (size section above).
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
ETHERNO
Other ETHERNO models
By power, the ETH20 is number 2 of 3 in the ETHERNO series, which runs from 10 to 30 kVA. One size down are the ETH10, ETH10-1X50A-LI, ETH10-2X50A-LI and ETH10-3X50A-LI, all 10 kVA less. One size up are the ETH30 and ETH30-3X50A-LI, all 10 kVA more. The same 20 kVA also comes as the ETH20-2X50A-LI and ETH20-3X50A-LI: the table below gives each one's weight and battery.
Every ETHERNO model side by side (9)
| Model | Power | Power against this model | Net weight | Weight against this model | Runtime at 50 % load | Battery configuration |
|---|---|---|---|---|---|---|
| ETH10 | 10 kVA | 10 kVA less | 216 lb | 11 lb lighter | — | Lithium modules inside, ordered separately |
| ETH10-1X50A-LI | 10 kVA | 10 kVA less | 298 lb | 71 lb heavier | 27 min at 50 % load | Internal |
| ETH10-2X50A-LI | 10 kVA | 10 kVA less | 379 lb | 152 lb heavier | 55 min at 50 % load | Internal |
| ETH10-3X50A-LI | 10 kVA | 10 kVA less | 461 lb | 234 lb heavier | 82 min at 50 % load | Internal |
| ETH20 | 20 kVA | this page | 227 lb | this page | — | Lithium modules inside, ordered separately |
| ETH20-2X50A-LI | 20 kVA | the same power | 390 lb | 163 lb heavier | 27 min at 50 % load | Internal |
| ETH20-3X50A-LI | 20 kVA | the same power | 472 lb | 245 lb heavier | 41 min at 50 % load | Internal |
| ETH30 | 30 kVA | 10 kVA more | 240 lb | 13 lb heavier | — | Lithium modules inside, ordered separately |
| ETH30-3X50A-LI | 30 kVA | 10 kVA more | 485 lb | 258 lb heavier | 27 min at 50 % load | Internal |
Install and run it:ETHERNO operating guideGuide specification, CSI 26 33 53
The ETH20 for your project
Send the load, the voltage and the minutes you need from the ETH20. We reply with the configuration, the batteries and the lead time.