RADIANT-IB · 208V three-phase UPS

RADIB100-4X20 RADIANT-IB 80 kVA, 208V three-phase UPS

VRLA80 kVAOnline double conversion

The AEC RADIANT-IB RADIB100-4X20 is an 80 kVA / 80 kW online double-conversion UPS for 208 V three-phase loads, built on four 20 kVA power modules, with VRLA batteries on internal trays. Kept at 80 % of its rating, it carries loads up to 64 kW.

Four of the frame's five module slots are fitted and one is free; with one module held as a spare (N+1) it carries 60 kVA. As configured it weighs 2,130 lb (966.2 kg) net.

80 kVA / 80 kWRating
23.6 × 39.3 × 78.7 inW × D × H
2,130 lbWeight
VRLA, internalBattery

Series picture.

AEC RADIANT-IB 100 kVA · 5 modules, rendered from its 3D modelDrag to turn

In 3D

Look around the RADIB100-4X20

The turntable shows the 100 kVA · 5 modules configuration; the full 3D view opens on this model.

Load by load

The RADIB100-4X20 at 25, 50, 75 and 100 % load.

Its 80 kW rating in four steps, worked out from its own catalog figures.

At 25, 50, 75 and 100 % load
LoadOutput current per phase, at 208 VLoad on each of its 4 power modulesEfficiencyHeat to removeHeat to remove (BTU/h)
25 % of the RADIB100-4X20, 20 kW55.5 A per phase25 % on each module92.7 % efficient1.6 kW of heat5,370 BTU/h to cool
50 % of the RADIB100-4X20, 40 kW111 A per phase50 % on each module93.9 % efficient2.6 kW of heat8,870 BTU/h to cool
75 % of the RADIB100-4X20, 60 kW167 A per phase75 % on each module94.0 % efficient3.8 kW of heat13,070 BTU/h to cool
100 % of the RADIB100-4X20, 80 kW222 A per phase100 % on each module93.8 % efficient5.3 kW of heat18,040 BTU/h to cool

Current = kVA × load ÷ (√3 × volts).

Module load = load ÷ the kVA of the power modules fitted.

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

What is the RADIB100-4X20?

The code RADIB100-4X20 orders these catalog items, shipped in 29 cartons:

  • 1 × RADIB-FRAME: 100 kVA frame, without power modules, 23.6 × 39.4 × 78.7 in (600 × 1,000 × 2,000 mm)
  • 4 × RADIB-PWR-20: 20 kVA hot-swappable power module, 44 lb (20 kg) each
  • 24 × RADIB-BATTR-10x9A: battery tray of 10 × 12 V 9 Ah VRLA blocks, 63.5 lb (28.8 kg) each
  • Architecture: 4 × 20 kVA hot-swappable power modules in a 100 kVA / 100 kW frame (scalable to 5 modules / 100 kVA); parallel up to 3 cabinets.

The lines every RADIANT-IB shares, from technology to warranty, are in the RADIANT-IB key facts and in the datasheet below.

4 × 20 kVA power modules fitted in a 5-slot frame: 1 free slot to grow or add redundancy.

Size and floor

How big it is

23.6" W × 39.3" D × 78.7" H (599 × 998 × 1,999 mm); 2,130 lb (966.2 kg) net.

6.4 ft²footprint (0.60 m²)
331 lb/ft²floor load of the cabinet alone
Modularform factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

5′9″ FrontSide 23.6″39.3″78.7″

Datasheet

RADIB100-4X20 datasheet.

The RADIB100-4X20 in the AEC 2026 catalog, figure by figure. Compare it with every RADIANT-IB model.

RADIB100-4X20 datasheet
ParameterRADIB100-4X20
Power
Rated power (kVA)80
Active power (kW)80
Output power factor1.0
Electrical
Input / output208 V three-phase, 4-wire (3P+N)
TopologyOnline double conversion, modular N+X
Efficiency, up to94%
Battery DC bus240 V DC
Battery and runtime
Battery typeVRLA (sealed lead-acid)
Battery configurationInternal Tray System
Runtime at 50 % load14 min
Runtime at 100 % load6 min
Mechanical
Form factorModular
Dimensions W × D × H23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm)
Net weight2,130 lb (966.2 kg)
Footprint6.4 ft² (0.60 m²)
Shipping
Cartons29
Common to every RADIANT-IB
Technology3-level IGBT; unity power factor (kVA = kW); 40 A settable charger
Battery, RADIB100-4X20internal hot-swappable VRLA, up to 240 × 12V 9Ah (240 pcs)
Display7-inch color touchscreen
CommsRS-232, EPO and USB, standard
Network cardSNMP-M (SNMP)
Warranty3 years on UPS · 2 years on VRLA batteries
Quality systemISO 9001:2015, the group's quality system (SGS)

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

RADIB100-4X20: what people ask

What is the output current of the RADIB100-4X20?

222.1 A per phase at full load: 80 kVA ÷ (√3 × 208 V). Size the input breaker and the cables of the RADIB100-4X20 from its installation manual and the local electrical code, not from this figure alone.

How much heat does the RADIB100-4X20 give off?

About 5.3 kW, 18,040 BTU/h, at full load, where it is 93.8% efficient. Plan the room's cooling for a little more than that: the RADIB100-4X20 is less efficient at part load and while its battery recharges.

Will the RADIB100-4X20 fit through a standard door?

Yes: 23.6 in (599 mm) across its narrow side and 78.7 in (1,999 mm) high, it passes a standard 36 × 80-inch door upright, with little to spare in height. On the way in, check corridors, elevators and the floor load of the RADIB100-4X20 (size section above).

The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h

RADIANT-IB

Other RADIANT-IB models

The RADIANT-IB series, with pictures

By power, the RADIB100-4X20 is number 4 of 5 in the RADIANT-IB series, which runs from 20 to 100 kVA. One size down is the RADIB100-3X20 (20 kVA less and 44 lb lighter). One size up is the RADIB100-5X20 (20 kVA more and 44 lb heavier).

Every RADIANT-IB model side by side (5)
RADIANT-IB models side by side
ModelPowerPower against this modelNet weightWeight against this modelRuntime at 50 % load
RADIB100-1X2020 kVA60 kVA less1,998 lb132 lb lighter85 min at 50 % load
RADIB100-2X2040 kVA40 kVA less2,042 lb88 lb lighter32 min at 50 % load
RADIB100-3X2060 kVA20 kVA less2,086 lb44 lb lighter21.5 min at 50 % load
RADIB100-4X2080 kVAthis page2,130 lbthis page14 min at 50 % load
RADIB100-5X20100 kVA20 kVA more2,174 lb44 lb heavier12 min at 50 % load

The RADIB100-4X20 for your project

Send the load, the voltage and the minutes you need from the RADIB100-4X20. We reply with the configuration, the batteries and the lead time.