RADIANT · 208 V three-phase UPS
RAD90 RADIANT 90 kVA frame, 15–90 kVA fitted
The AEC RADIANT RAD90 is a 90 kVA modular UPS frame for 208 V three-phase loads with six slots for 15 kVA hot-swappable power modules. The 2026 catalog lists it with 1, 2, 3, 4, 5 or 6 modules fitted, 15–90 kVA in all; each code is a row below.
Series picture.
6 ordering codes
Which RAD90 do you need?
One 90 kVA frame, a row per number of modules fitted. Only what changes from one code to the next is here; what they share is under the table.
| Ordering code | Power | Free slots | With one module spare (N+1) | Net weight | Floor load | Current per phase at 208 V |
|---|---|---|---|---|---|---|
| RAD90-1X151 × 15 kVA power module3DAsk | 15 kVA / 15 kW | 5 of 6 | no spare with one module | 238 lb (108 kg) | 60 lb/ft² | 41.6 A |
| RAD90-2X152 × 15 kVA power modules3DAsk | 30 kVA / 30 kW | 4 of 6 | 15 kVA | 268.5 lb (121.8 kg) | 67 lb/ft² | 83.3 A |
| RAD90-3X153 × 15 kVA power modules3DAsk | 45 kVA / 45 kW | 3 of 6 | 30 kVA | 299 lb (135.7 kg) | 75 lb/ft² | 125 A |
| RAD90-4X154 × 15 kVA power modules3DAsk | 60 kVA / 60 kW | 2 of 6 | 45 kVA | 329.5 lb (149.5 kg) | 82 lb/ft² | 167 A |
| RAD90-5X155 × 15 kVA power modules3DAsk | 75 kVA / 75 kW | 1 of 6 | 60 kVA | 360 lb (163.4 kg) | 90 lb/ft² | 208 A |
| RAD90-6X156 × 15 kVA power modules3DAsk | 90 kVA / 90 kW | none of 6 | 75 kVA | 390.5 lb (177.2 kg) | 98 lb/ft² | 250 A |
This model
What sets the RAD90 apart
The RADIANT is a 90 kVA frame for 208 V three-phase, 17.4 in wide and 59.4 in high, with six slots for 15 kVA power modules and four breakers. The catalog lists it with one to six modules, 15 to 90 kVA, in steps of 15 kVA, the finest steps of any AEC modular frame.
Each module adds 30.5 lb and 41.6 A per phase at full load; with all six it weighs 390.5 lb (177.2 kg). Its batteries stand outside in a bank sized for the minutes needed. Bought at 60 kVA with four modules, it has two slots left for growth, or for N+1 at 60 kVA with a fifth.
Drag to turnThe same on every RADIANT:The RADIANT display
Efficiency
How efficient is the RAD90-6X15 at your load?
The RAD90-6X15 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What every RAD90 code shares
- Each 15 kVA power module, RAD-PWR-15: 30.5 lb (13.9 kg), hot-swappable
- Technology: 3-level IGBT; unity power factor (kVA = kW); 40 A settable charger.
- Input / Output: 208/120 V three-phase.
- Battery: external VRLA (battery bank sized separately).
- Efficiency: up to 94%.
- Display: 7-inch color touchscreen.
- Comms: RS-232, EPO and USB, standard.
- Warranty: 3 years on UPS · 2 years on VRLA batteries.
- Cabinet: 17.4" W × 33.1" D × 59.4" H (442 × 840 × 1,510 mm), the same for every code above
The lines every RADIANT shares, from technology to warranty, are in the RADIANT key facts.
Size and floor
How big it is
17.4" W × 33.1" D × 59.4" H (442 × 840 × 1,510 mm); from 238 lb (108 kg) to 390.5 lb (177.2 kg) net, code by code.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
The RAD90 takes the clearances, wiring, cable entry and breakers of every RADIANT model, from its AEC US user manual: see them on the RADIANT page.
Datasheet
RAD90 datasheet, code by code.
Every figure of the 6 codes in the AEC 2026 catalog. Compare them with every RADIANT model.
| Model | RAD90-1X15 | RAD90-2X15 | RAD90-3X15 | RAD90-4X15 | RAD90-5X15 | RAD90-6X15 |
|---|---|---|---|---|---|---|
| Power | ||||||
| Rated power (kVA) | 15 | 30 | 45 | 60 | 75 | 90 |
| Active power (kW) | 15 | 30 | 45 | 60 | 75 | 90 |
| Output power factor | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
| Electrical | ||||||
| Input / output | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X | Online double conversion, modular N+X | Online double conversion, modular N+X | Online double conversion, modular N+X | Online double conversion, modular N+X | Online double conversion, modular N+X |
| Efficiency, up to | 94% | 94% | 94% | 94% | 94% | 94% |
| Battery DC bus | 240 V DC | 240 V DC | 240 V DC | 240 V DC | 240 V DC | 240 V DC |
| Battery and runtime | ||||||
| Battery type | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) |
| Battery configuration | External battery bank | External battery bank | External battery bank | External battery bank | External battery bank | External battery bank |
| Mechanical | ||||||
| Form factor | Modular Rack 19" | Modular Rack 19" | Modular Rack 19" | Modular Rack 19" | Modular Rack 19" | Modular Rack 19" |
| Dimensions W × D × H | 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm) | 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm) | 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm) | 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm) | 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm) | 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm) |
| Net weight | 238 lb (108 kg) | 268.5 lb (121.8 kg) | 299 lb (135.7 kg) | 329.5 lb (149.5 kg) | 360 lb (163.4 kg) | 390.5 lb (177.2 kg) |
| Footprint | 4.0 ft² (0.37 m²) | 4.0 ft² (0.37 m²) | 4.0 ft² (0.37 m²) | 4.0 ft² (0.37 m²) | 4.0 ft² (0.37 m²) | 4.0 ft² (0.37 m²) |
From the AEC 2026 catalog. Efficiency is the catalog's “up to” figure; weights are the unit alone, without batteries outside it. Figures may change; the order confirmation governs.
Downloads
The RADIANT manuals and catalogs cover every model of the series, these codes included: download them from the RADIANT page.
RADIANT
Other RADIANT models
The RADIANT has this one model page; its datasheet sets every code side by side.
The figures above, explained:How many amps does a UPS draw?Which VRLA batteries and cabinets does AEC supply?
The RAD90 for your project
Send the load, the voltage and the minutes you need from the RAD90. We reply with the code, the batteries and the lead time.