LiFePO4 · 120 V, 208 V and 480 V · 1 to 1,500 kVA

Lithium-ion (LiFePO4) UPS from 1 kVA to 1,500 kVA

A lithium UPS stores its backup energy in lithium-ion cells instead of lead-acid blocks. AEC builds three lithium lines for US supplies, all LiFePO4: LUMINA 1–3 kVA, 120 V, battery inside a 2U rack unit; ETHERNO 10–30 kVA, 208 V three-phase, modules inside the tower; INFINITE 100–600 kVA and INFINITE 1.5MW 750–1,500 kVA, 480 V, with L6 lithium cabinets.

From the 2026 catalog

Every AEC lithium configuration sold in the US

Runtime with new batteries at full and half load. LUMINA and ETHERNO: the catalog's published tables. INFINITE sets: the modules' usable energy over the load, as on INFINITE with L6 cabinets.

LUMINA

120 V single-phase in and out, the battery inside a 2U rack unit. Recharge 5 h or less (user manual); 12–15 years, 3,000 cycles; 5 years incl. lithium batteries; ETL Listed to UL 1778 and CSA C22.2 No. 107.3.

AEC LUMINA lithium UPS configurations, US catalog 2026
CodePowerBattery, energyRuntime full / half loadSize, weight
LUM1000RT-2U-LILUMINA1 kVA / 0.9 kWLiFePO4, 10.2 Ah, 244.8 Wh11 min / 27 min17.2 × 16.5 × 3.4 in, 19.6 lb
LUM1500RT-2U-LILUMINA1.5 kVA / 1.35 kWLiFePO4, 10.2 Ah, 489.6 Wh11 min / 27 min (AEC estimate)17.2 × 22.6 × 3.4 in, 32.4 lb
LUM2000RT-2U-LILUMINA2 kVA / 1.8 kWLiFePO4, 10.2 Ah, 489.6 Wh11 min / 27 min17.2 × 22.4 × 3.4 in, 30 lb
LUM2200RT-2U-LILUMINA2.2 kVA / 1.98 kWLiFePO4, 13.6 Ah, 979.2 Wh23 min / 46 min17.2 × 24.2 × 3.4 in, 42.1 lb
LUM3000RT-2U-LILUMINA3 kVA / 2.7 kWLiFePO4, 10.2 Ah, 734.4 Wh11 min / 27 min17.2 × 22.4 × 3.4 in, 37.7 lb

ETHERNO

208 V three-phase in and out, 50 Ah modules inside the tower, hot-swap. Recharge under 2 h; 15-year module life, 5,000+ cycles; 5 years incl. lithium batteries; UL 1778 listed, UL file E543003 (AEC UPS USA LLC). The 50 Ah LiFePO4 battery modules are certified to UL 1973 and UL 9540A tested.

AEC ETHERNO lithium UPS configurations, US catalog 2026
CodePowerBattery, energyRuntime full / half loadSize, weight
ETH10-1X50A-LIETHERNO10 kVA / 10 kW1 × 50 Ah module, 2.88 kWh14 min / 27 min12.6 × 39.1 × 49.2 in, 297.6 lb
ETH10-2X50A-LIETHERNO10 kVA / 10 kW2 × 50 Ah modules, 5.76 kWh27 min / 55 min12.6 × 39.1 × 49.2 in, 379.2 lb
ETH10-3X50A-LIETHERNO10 kVA / 10 kW3 × 50 Ah modules, 8.64 kWh41 min / 82 min12.6 × 39.1 × 49.2 in, 460.8 lb
ETH20-2X50A-LIETHERNO20 kVA / 20 kW2 × 50 Ah modules, 5.76 kWh14 min / 27 min12.6 × 39.1 × 49.2 in, 390.2 lb
ETH20-3X50A-LIETHERNO20 kVA / 20 kW3 × 50 Ah modules, 8.64 kWh20 min / 41 min12.6 × 39.1 × 49.2 in, 471.8 lb
ETH30-3X50A-LIETHERNO30 kVA / 30 kW3 × 50 Ah modules, 8.64 kWh14 min / 27 min12.6 × 39.1 × 49.2 in, 485 lb

INFINITE

480 V three-phase, 3-wire, external L6 lithium cabinets. L6: 15 years, 5,000+ cycles; 3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries; built to UL 1778. The 50 Ah LiFePO4 battery modules are certified to UL 1973 and UL 9540A tested. INFINITE 1.5MW, 750–1,500 kVA, takes L6 cabinets sized to order.

AEC INFINITE lithium UPS configurations, US catalog 2026
CodePowerBattery, energyRuntime full / half loadSize, weight
INF-100+L6-CAB-10x50LIINFINITE100 kVA / 100 kW1 L6 cabinet, 10 × 50 Ah, 28.8 kWh15 min / 30 min1,808 lb for the set
INF-100+L6-CAB-20x50LIINFINITE100 kVA / 100 kW1 L6 cabinet, 20 × 50 Ah, 57.6 kWh30 min / 60 min2,623.8 lb for the set
INF-100+1+L6-CAB-20x50LIINFINITE100 kVA / 100 kW, N+11 L6 cabinet, 20 × 50 Ah, 57.6 kWh30 min / 60 min2,742.8 lb for the set
INF-200+L6-CAB-20x50LIINFINITE200 kVA / 200 kW1 L6 cabinet, 20 × 50 Ah, 57.6 kWh15 min / 30 min2,762.9 lb for the set
INF-200+1+L6-CAB-20x50LIINFINITE200 kVA / 200 kW, N+11 L6 cabinet, 20 × 50 Ah, 57.6 kWh15 min / 30 min2,881.9 lb for the set
INF-400+2xL6-CAB-20x50LIINFINITE400 kVA / 400 kW2 L6 cabinets, 40 × 50 Ah, 115.2 kWh15 min / 30 min5,525.7 lb for the set
INF-600+3xL6-CAB-20x50LIINFINITE600 kVA / 600 kW3 L6 cabinets, 60 × 50 Ah, 172.8 kWh15 min / 30 min8,597.2 lb for the set
INFINITE 1.5MW3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries; UL 1778 listed, UL file E543003 (AEC UPS USA LLC)750–1,500 kVAL6 cabinets through the L6 combiner (up to 8 cabinets each), or VRLA; 57.6 kWh per full L6 cabinetsized to order70.9 × 39.4 × 78.7 in frame, 4,673.8 lb

Energy is nominal: 2.88 kWh per 50 Ah module. Recharge: 2026 catalog for ETHERNO, LUMINA user manual for LUMINA; the catalog gives none for the L6 sets. Listing as stated on the legal notice; "built to UL 1778" means the series follows the standard and does not carry a listing mark.

Choose by load

Which one carries your load?

Up to 2.7 kW on 120 V in a rack: LUMINA. From 10 to 30 kW on 208Y/120 V: ETHERNO. From 100 kW on 480 V three-wire: INFINITE with L6 cabinets, or INFINITE 1.5MW from 750 kVA. The UPS sizing tool gives the model and the minutes for your load; lithium or VRLA counts the battery sets over the years you plan.

Rack

Lithium in a 19-inch rack

LUMINA is a 2U rack unit, 16.5 in deep on the 1 kVA, 24.2 in on the 2.2 kVA with its larger battery, 23 minutes at full load against 11 on the others. Online double conversion at 120 V, up to 92.6% efficient.

Three-phase tower

Lithium in a 208 V tower

ETHERNO stands 12.6 in wide and takes one to three 50 Ah modules inside, each 81.6 lb. Two modules carry 20 kW and three carry 30 kW; a third module on the 10 kVA brings full-load runtime from 14 to 41 minutes.

Modular, 480 V

Lithium cabinets beside a modular UPS

INFINITE uses 100 kVA silicon carbide power modules and L6 cabinets of 10 or 20 modules. One full cabinet holds 57.6 kWh nominal and runs 200 kW for 15 minutes. The containerized UPS puts INFINITE, L6 and switchgear in one container from 200 kW to 1.2 MW.

The room

What changes in the room

Weight. A full L6 cabinet weighs 2,171.6 lb on 23.6 × 33.5 in: about 396 lb/ft² (1,931 kg/m²) over its own footprint, the figure for the structural engineer. With 10 modules it weighs 1,355.8 lb.

Floor. ETHERNO keeps the lithium inside its 12.6 × 39.1 in footprint; the ETH10-2X50A-LI weighs 379.2 lb against 699 lb for the VRLA AUR10-80X9A, 14.9 in wide.

Temperature. ETHERNO runs at 32–104 °F (0–40 °C) and its battery works best at 68–86 °F (ETHERNO user manual). LUMINA gives full output at 32–104 °F and runs up to 140 °F (60 °C) with reduced output (LUMINA user manual and 2026 LUMINA catalog).

Fire code

Lithium and the fire code

NFPA 855 and the International Fire Code, Section 1207, set rules for stationary lithium-ion batteries above 20 kWh in a room. One ETHERNO holds 2.88 to 8.64 kWh; one full L6 cabinet 57.6 kWh. AEC's 50 Ah LiFePO4 battery modules are certified to UL 1973 and UL 9540A tested: that is the module, not a UL 9540 listing of the cabinet or of the system. What applies to your room is the authority's decision: lithium UPS and the fire code goes through the codes and the documents to ask for.

More: lithium-ion or VRLA for a UPS · UPS runtime explained · sizing L6 cabinets · LiFePO4 and the BMS

Lithium UPS

Questions people ask

What is a lithium UPS?

A UPS whose battery is lithium-ion instead of lead-acid. Every AEC lithium UPS uses lithium iron phosphate (LiFePO4), with a battery management system in the battery: inside the unit on LUMINA and ETHERNO, in external L6 cabinets on INFINITE.

Is there a 208 V three-phase UPS with the lithium inside?

Yes: ETHERNO, 10 to 30 kVA, takes one to three 50 Ah modules inside the tower. The ETH20-3X50A-LI runs 20 minutes at its full 20 kW.

How long does a lithium UPS battery last?

The 2026 catalog gives the 50 Ah module of ETHERNO and L6 a 15-year life and 5,000+ cycles, and LUMINA 12 to 15 years and 3,000 cycles. AEC's user manuals give VRLA 3 to 5 years of service at 77 °F: the battery-set count sets the two side by side.

Is the ETHERNO module the same as the L6 module?

Yes. The catalog lists ETH-50-LI for ETHERNO and L6-MOD-50LI for the L6 cabinet as physically identical and fully interchangeable: one 50 Ah, 2.88 kWh module, 81.6 lb, so one spare fits both. The 50 Ah LiFePO4 battery modules are certified to UL 1973 and UL 9540A tested: the module's own certification, not a listing of the cabinet or of the system.

How fast does it recharge?

ETHERNO's modules recharge in under 2 hours (2026 catalog). LUMINA takes 5 hours or less (LUMINA user manual, Table A-1).

What warranty comes with AEC lithium?

5 years incl. lithium batteries on LUMINA and ETHERNO; INFINITE: 3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries.

Can lithium be added later?

ETHERNO's modules slide in with the UPS running. An L6 cabinet ordered with 10 modules takes 10 more, added with the load on.

Which lithium UPS for your load?

Send the supply, the load in kW and the minutes you need: we answer with the model, the modules and the cabinets.