Double conversion · 120 V to 480 V · 1 to 1,600 kVA
Online UPS: double conversion, 1 kVA to 1,600 kVA
An online UPS converts the utility to DC and back to clean AC, so the load runs on the inverter all the time and sees no transfer when the power fails. Every AEC UPS is online double conversion: 13 series for 120 V, 120/240 V, 208 V and 480 V, from 1 kVA rack units to 1,600 kVA modular frames.
From the 2026 catalog
Every AEC online range, by phase and power
Efficiency in double conversion, as the catalog gives each series. ECO-mode figures are in the user manuals, set out in ECO mode on a UPS.
| Series | Power | Supply, in and out | Form | Double conversion | Battery | Listing |
|---|---|---|---|---|---|---|
| LUMINA | 1–3 kVA | 120 V single-phase | Rack | up to 92.6% | Lithium inside | ETL Listed to UL 1778 and CSA C22.2 No. 107.3 |
| FERRUS | 1–3 kVA | 120 V single-phase | Tower | up to 93% | VRLA inside | Built to UL 1778 |
| FERRUS RT | 1–3 kVA | 120 V single-phase | Rack | up to 93% | VRLA inside | Built to UL 1778 |
| FERRUS SP RT | 6–10 kVA | 120/240 V split-phase | Rack | up to 93% | VRLA, 16 blocks in its 3U cabinet | Built to UL 1778 |
| FERRUS SP | 6–20 kVA | 120/240 V split-phase | Tower | up to 93% | VRLA inside; 20 kVA also on an external cabinet | Built to UL 1778 |
| ETHERNO | 10–30 kVA | 208 V three-phase | Tower | up to 94% | Lithium modules inside | UL 1778 listed, UL file E543003 (AEC UPS USA LLC) |
| AUREON | 10–30 kVA | 208 V three-phase | Tower | up to 94% | VRLA modules inside | UL 1778 listed, UL file E543003 (AEC UPS USA LLC) |
| RADIANT | 15–90 kVA | 208 V three-phase | Modular, N+X | up to 94% | External VRLA bank | Built to UL 1778 |
| RADIANT-IB | 20–100 kVA | 208 V three-phase | Modular, N+X | up to 94% | VRLA inside | Built to UL 1778 |
| CIRRO-IB | 30–150 kVA | 480 V three-phase, 4-wire | Modular, N+X | up to 96% | VRLA inside | Built to UL 1778 |
| CIRRO | 60–1,600 kVA | 480 V three-phase, 4-wire | Modular, N+X | up to 97% | External VRLA bank | Built to UL 1778 |
| INFINITE | 100–600 kVA | 480 V three-phase, 3-wire | Modular, N+1 | up to 97.3% | External: L6 lithium or VRLA | Built to UL 1778 |
| INFINITE 1.5MW | 750–1,500 kVA | 480 V three-phase, 3-wire | Modular, N+1 | up to 97.5% | External: L6 lithium or VRLA | UL 1778 listed, UL file E543003 (AEC UPS USA LLC) |
By supply: 120 V single-phase · 120/240 V split-phase · 208 V three-phase · 480 V three-phase · all three-phase. Listing as stated on the legal notice.
Online or line-interactive
What the inverter changes
A line-interactive UPS passes the utility to the load and corrects its voltage; when the supply fails, it switches to the inverter. An online UPS makes its output from the DC bus all the time, so the switch never happens and the frequency is always its own. On a generator, whose frequency wanders under load, the inverter keeps the output at 60 Hz.
Efficiency and heat
What double conversion costs in heat
The losses are the load times (1 ÷ efficiency − 1): at 100 kW, 97.3% leaves about 2.8 kW of heat for the cooling to remove. Read each series at your own load: UPS efficiency curves · UPS heat output in BTU · ECO mode.
Online UPS
Questions people ask
What is an online UPS?
A UPS that feeds the load from its own inverter all the time: the rectifier turns the utility into DC, the inverter makes new AC from it, and the battery sits on the DC bus between them. When the utility fails there is no transfer to make. Every AEC UPS works this way.
Is double conversion the same as online?
Yes. Online double conversion (VFI in IEC 62040-3) names the two conversions, AC to DC and DC to AC, that every watt goes through. The terms are used for the same design.
Online or line-interactive?
A line-interactive UPS feeds the load from the utility through a voltage regulator and starts its inverter only when the supply fails. An online UPS keeps the load on its inverter, so sags, surges and frequency drift never reach it. AEC makes online UPS only.
What efficiency does an online UPS reach?
From 92.6% on the 120 V LUMINA to 97.5% on INFINITE 1.5MW, in double conversion, as the 2026 catalog gives each series. ECO mode runs the load on the bypass for a higher figure, with less protection: see the ECO-mode guide.
Which online UPS for a 30 kVA load at 208 V?
ETHERNO 30 kVA with lithium modules inside, AUREON 30 kVA with VRLA modules inside, or a modular RADIANT. The sizing tool gives the minutes of each for your load.
Single-phase or three-phase online UPS?
Single-phase 120 V up to 3 kVA, 120/240 V split-phase from 6 to 20 kVA; three-phase from 10 kVA, at 208 V or 480 V. The panel the UPS connects to decides.
Before you choose: size the UPS · how to choose a UPS · 208 V or 480 V · lithium UPS
Which online UPS?
Send the supply, the load in kW and the minutes you need: we answer with the series, the model and the batteries.