N+1 · hot-swap · 208 V and 480 V · 15 to 125 kVA modules
Modular UPS: hot-swap power modules, 15 kVA to 1,500 kVA per frame
A modular UPS is a frame of slots filled with identical power modules: it grows by adding modules and keeps the load on the inverter while one is swapped. AEC builds 11 modular frames for US supplies, from the 15 kVA modules of RADIANT at 208 V to the 125 kVA silicon carbide modules of INFINITE 1.5MW at 480 V.
From the 2026 catalog
Every AEC modular frame, with N+1 worked out
N+1 here is the frame with every slot filled and one module held spare. INFINITE 100 and 200 are sold with their spare slot: 1 + 1 and 2 + 1 modules. kVA = kW on every series (unity power factor).
| Frame | Supply | Module, weight | Slots | Frame rating | N+1, frame full | In parallel, up to |
|---|---|---|---|---|---|---|
| RADIANT 90 | 208Y/120 V | 15 kVA, 30.5 lb | 6 | 90 kVA | 75 kW | 4 frames |
| RADIANT-IB 100 | 208Y/120 V | 20 kVA, 44 lb | 5 | 100 kVA | 80 kW | 3 cabinets |
| CIRRO-IB 150 | 480Y/277 V, 4-wire | 30 kVA, 52 lb | 5 | 150 kVA | 120 kW | 3 cabinets |
| CIRRO 360 | 480Y/277 V, 4-wire | 60 kVA, 77 lb | 6 | 360 kVA | 300 kW | 8 units |
| CIRRO 600 | 480Y/277 V, 4-wire | 100 kVA, 103.6 lb | 6 | 600 kVA | 500 kW | 8 units |
| CIRRO 800 | 480Y/277 V, 4-wire | 100 kVA, 103.6 lb | 8 | 800 kVA | 700 kW | 8 units |
| CIRRO 1200 | 480Y/277 V, 4-wire | 100 kVA, 103.6 lb | 12 | 1,200 kVA | 1,100 kW | 8 units |
| CIRRO 1600 | 480Y/277 V, 4-wire | 100 kVA, 103.6 lb | 16 | 1,600 kVA | 1,500 kW | 8 units |
| INFINITE 100 | 480 V, 3-wire | 100 kVA, 119 lb | 1 + 1 | 100 kVA | 100 kW | 3 frames |
| INFINITE 200 | 480 V, 3-wire | 100 kVA, 119 lb | 2 + 1 | 200 kVA | 200 kW | 3 frames |
| INFINITE 1.5MW | 480 V, 3-wire | 125 kVA, 119 lb | 12 | 1,500 kVA | 1,375 kW | 8 units |
Floor, weight and switchgear
kW per square foot is the N+1 power over the frame's own footprint: the figure that sets how much of the room the UPS takes. Batteries and service space come on top.
| Frame | W × D × H | Footprint | N+1 power per ft² | Weight, every slot filled | Breakers in the frame |
|---|---|---|---|---|---|
| RADIANT 90 | 17.4 × 33.1 × 59.5 in | 4 ft² | 19 kW/ft² | 390.5 lb | 4 |
| RADIANT-IB 100 | 23.6 × 39.4 × 78.7 in | 6.5 ft² | 12 kW/ft² | 650 lb* | not stated |
| CIRRO-IB 150 | 23.6 × 39.4 × 78.7 in | 6.5 ft² | 19 kW/ft² | 876 lb* | not stated |
| CIRRO 360 | 23.6 × 39.4 × 78.7 in | 6.5 ft² | 46 kW/ft² | 1,088.4 lb | 1 |
| CIRRO 600 | 31.5 × 39.4 × 78.7 in | 8.6 ft² | 58 kW/ft² | 1,514.5 lb | 4 |
| CIRRO 800 | 31.5 × 39.4 × 78.7 in | 8.6 ft² | 81 kW/ft² | 1,902.4 lb | 4 |
| CIRRO 1200 | 47.2 × 43.3 × 78.7 in | 14.2 ft² | 78 kW/ft² | 2,618.9 lb | none: external switchgear |
| CIRRO 1600 | 63 × 39.4 × 78.7 in | 17.2 ft² | 87 kW/ft² | 3,796.1 lb | none: external switchgear |
| INFINITE 100 | 23.6 × 39.4 × 81.4 in | 6.5 ft² | 15 kW/ft² | 571.3 lb | 3 |
| INFINITE 200 | 23.6 × 39.4 × 81.4 in | 6.5 ft² | 31 kW/ft² | 710.4 lb | 3 |
| INFINITE 1.5MW | 70.9 × 39.4 × 78.7 in | 19.4 ft² | 71 kW/ft² | 6,170.7 lb | not stated |
* RADIANT-IB and CIRRO-IB: the frame and its five modules, without the battery trays and blocks they also hold (up to 240 × 12 V 9 Ah). Other weights: the catalog's full configuration. The CIRRO 600 and 800 are the same 31.5 × 39.4 in cabinet with 6 or 8 slots: the 800 adds 200 kW of N+1 power for 388 lb and no floor.
By load
Which frame carries your load with N+1?
The sizing rule of the RADIANT-IB user manual, for any frame: modules = load ÷ (80% of one module), rounded up, plus one. The smallest frame that holds them, or the fewest frames in parallel; each module's share in normal running and the efficiency there on the catalog's curve.
| IT load | 208Y/120 V | 480Y/277 V, 4-wire | 480 V, 3-wire |
|---|---|---|---|
| 30 kW | RADIANT 90: 4 × 15 kVA in 6 slots, each at 50%, 93.9% | CIRRO-IB 150: 3 × 30 kVA in 5 slots, each at 33%, 95.3% | — |
| 60 kW | RADIANT 90: 6 × 15 kVA in 6 slots, each at 67%, 94% | CIRRO-IB 150: 4 × 30 kVA in 5 slots, each at 50%, 95.9% | — |
| 120 kW | 2 × RADIANT 90: 11 × 15 kVA in 12 slots, each at 73%, 94% | CIRRO 360: 4 × 60 kVA in 6 slots, each at 50%, 95.9% | INFINITE 200: 3 × 100 kVA in 3 slots, each at 40%, 97.1% |
| 250 kW | 4 × RADIANT 90: 22 × 15 kVA in 24 slots, each at 76%, 94% | CIRRO 600: 5 × 100 kVA in 6 slots, each at 50%, 96.9% | 2 × INFINITE 200: 5 × 100 kVA in 6 slots, each at 50%, 97.3% |
| 400 kW | — | CIRRO 600: 6 × 100 kVA in 6 slots, each at 67%, 97% | 3 × INFINITE 200: 6 × 100 kVA in 9 slots, each at 67%, 97.3% |
| 600 kW | — | CIRRO 1200: 9 × 100 kVA in 12 slots, each at 67%, 97% | INFINITE 1.5MW: 7 × 125 kVA in 12 slots, each at 69% |
| 900 kW | — | CIRRO 1600: 13 × 100 kVA in 16 slots, each at 69%, 97% | INFINITE 1.5MW: 10 × 125 kVA in 12 slots, each at 72% |
| 1,200 kW | — | CIRRO 1600: 16 × 100 kVA in 16 slots, each at 75%, 97% | 2 × INFINITE 1.5MW: 13 × 125 kVA in 24 slots, each at 74% |
208 V shown up to 300 kW; INFINITE 1.5MW from its smallest catalog set-up, six modules (INF15-750). INFINITE 1.5MW has no published curve: its catalog gives up to 97.5% AC/AC. The sizing tool adds the battery minutes; growing a modular UPS plans the day-one frame for the load in five years.
Efficiency where the modules run
What N+1 does to efficiency and heat
With N+1 the modules never run at full load: a full frame at its N+1 power runs each module at (slots − 1) ÷ slots. In a 2N design each side carries half of that. Read off the 2026 catalog's curves.
| Frame | At N+1 power | At half of it (one side of 2N) |
|---|---|---|
| RADIANT 90 | 75 kW: 83% each, 93.9%, 4.8 kW of heat | 38 kW: 42% each, 93.5%, 2.6 kW of heat |
| RADIANT-IB 100 | 80 kW: 80% each, 94%, 5.1 kW of heat | 40 kW: 40% each, 93.4%, 2.8 kW of heat |
| CIRRO-IB 150 | 120 kW: 80% each, 96%, 5.1 kW of heat | 60 kW: 40% each, 95.5%, 2.8 kW of heat |
| CIRRO 360 | 300 kW: 83% each, 95.9%, 12.7 kW of heat | 150 kW: 42% each, 95.6%, 6.8 kW of heat |
| CIRRO 600 | 500 kW: 83% each, 96.9%, 15.8 kW of heat | 250 kW: 42% each, 96.7%, 8.6 kW of heat |
| CIRRO 800 | 700 kW: 88% each, 96.9%, 22.4 kW of heat | 350 kW: 44% each, 96.7%, 11.9 kW of heat |
| CIRRO 1200 | 1,100 kW: 92% each, 96.9%, 35.6 kW of heat | 550 kW: 46% each, 96.8%, 18.3 kW of heat |
| CIRRO 1600 | 1,500 kW: 94% each, 96.9%, 48.8 kW of heat | 750 kW: 47% each, 96.8%, 24.7 kW of heat |
| INFINITE 100 | 100 kW: 50% each, 97.3%, 2.8 kW of heat | 50 kW: 25% each, 96.9%, 1.6 kW of heat |
| INFINITE 200 | 200 kW: 67% each, 97.3%, 5.5 kW of heat | 100 kW: 33% each, 97%, 3.1 kW of heat |
Heat = load × (1 ÷ efficiency − 1), in double conversion, straight between the curve's 25, 50, 75 and 100% points. Every curve: UPS efficiency curves.
Batteries
What each frame runs on
RADIANT and CIRRO: an external VRLA bank on the DC bus; CIRRO 600–1600 takes 40 blocks of 12 V by default, 30 to 50 selectable. RADIANT-IB and CIRRO-IB: up to 240 blocks of 12 V 9 Ah in hot-swappable trays inside the cabinet. INFINITE and INFINITE 1.5MW: lead-acid or L6 lithium cabinets; INFINITE 1.5MW takes 4, 6 or 8 of them, 80 to 160 modules of 50 Ah, 10 kW each. The 50 Ah LiFePO4 battery modules are certified to UL 1973 and UL 9540A tested.
Before you buy
Three things to fix on day one
The frame, not the modules. A frame full on day one has no slot left for N+1 or growth. The switchgear. CIRRO 1200 and 1600 have no breakers inside; plan the external board with the room. The cables and the battery for the frame's final power, so added modules arrive with their runtime. The method in full: modular UPS and N+X · N+1 redundancy.
Like for like
Modular frames of other makers, from their own documents
Frame rating over the frame's footprint, the same arithmetic for every row. Other makers' figures as their documents give them, read 10 Oct 2026; the documents are named, not linked. Weights are left out: not every maker gives one for the same configuration.
| Frame | Rating | Module | Efficiency, as published | W × D | kW per ft² | Document |
|---|---|---|---|---|---|---|
| AEC RADIANT 90 | 90 kW | 15 kVA | up to 94% | 17.4 × 33.1 in | 23 | AEC 2026 catalog |
| AEC RADIANT-IB 100 | 100 kW | 20 kVA | up to 94% | 23.6 × 39.4 in | 15 | AEC 2026 catalog |
| AEC CIRRO 600 | 600 kW | 100 kVA | up to 97% | 31.5 × 39.4 in | 70 | AEC 2026 catalog |
| AEC CIRRO 800 | 800 kW | 100 kVA | up to 97% | 31.5 × 39.4 in | 93 | AEC 2026 catalog |
| AEC CIRRO 1600 | 1,600 kW | 100 kVA | up to 97% | 63 × 39.4 in | 93 | AEC 2026 catalog |
| AEC INFINITE 200 | 200 kW | 100 kVA | up to 97.3% | 23.6 × 39.4 in | 31 | AEC 2026 catalog |
| AEC INFINITE 1.5MW | 1,500 kW | 125 kVA | up to 97.5% | 70.9 × 39.4 in | 77 | AEC 2026 catalog |
| Eaton 93PM 250 kW 480 VEaton 93PM, 480 V | 250 kW | 50 kW | 97% | 22 × 42 in | 39 | eaton.com/…/eaton-93pm-480v-ups; eaton-93pm-480v-250kw-ups-brochure-br153218en.pdf (eaton.com) |
| Vertiv APM2 480 V 600 kVA frameVertiv Liebert APM2, 480 V | 600 kW | 60 kVA | 97.5% | 47.2 × 40.6 in | 45 | vertiv-liebert-apm2-10-600kw-brochure-sl-71311.pdf (vertiv.com); vertiv-liebert-apm2-data-sheet-sl-71300.pdf (vertiv.com) |
A maker's "up to" efficiency is the top of its own curve and test; the rows are not measured side by side. Model by model at the same power: modular UPS at 208 V · modular UPS at 480 V up to 1,600 kVA.
Open them
See a frame before it reaches the room
The ranges
The modular series

RADIANT
Modular online UPS with N+X redundancy for three-phase 208 V loads from 15 to 90 kVA, with an external VRLA battery bank.
View series
RADIANT-IB
Modular online UPS with N+X redundancy for three-phase 208 V loads from 20 to 100 kVA, with internal hot-swappable VRLA battery trays.
View series
CIRRO-IB
Modular online UPS with N+X redundancy for three-phase 480 V, 4-wire loads from 30 to 150 kVA, with internal hot-swappable VRLA battery trays.
View series
CIRRO
Modular online UPS with N+X redundancy for three-phase 480 V, 4-wire loads from 60 to 1,600 kVA, with an external VRLA battery bank.
View series
INFINITE
Modular online UPS with room for N+1 redundancy for three-phase 480 V, 3-wire loads from 100 to 600 kVA, with external lithium battery cabinets.
View series
INFINITE 1.5MW
Modular online UPS with room for N+1 redundancy for three-phase 480 V, 3-wire loads from 750 to 1,500 kVA, with external lithium battery cabinets.
View seriesModular UPS
Questions people ask
What is a modular UPS?
A UPS built as a frame of slots and a set of identical power modules, each with its own rectifier, inverter and control. The modules share the load; one more than the load needs gives N+1, and any one can be pulled with the system running. AEC modules run from 15 kVA (RADIANT) to 125 kVA (INFINITE 1.5MW).
How many modules do I need for N+1?
Divide the load by 80% of one module's kW, round up, add one. For 400 kW on 100 kVA CIRRO modules: 400 ÷ 80 = 5, plus one is 6, a full CIRRO 600; the same 6 modules in a CIRRO 800 leave two slots to grow, in the same 31.5 × 39.4 in footprint.
Can modules of different series share a frame?
No. Each frame takes its own series' module only; the catalog states it for the two that look alike, the 20 kVA RADIANT-IB and the 30 kVA CIRRO-IB modules, which are not interchangeable.
Does adding modules add runtime?
No. Modules add power, not stored energy: the same battery behind more kW gives fewer minutes. Size the battery, its cables and its breaker for the frame's final power.
Which modular UPS for 480 V without a neutral?
INFINITE (100 to 600 kVA, up to 3 frames in parallel) and INFINITE 1.5MW (750 to 1,500 kVA per frame, up to 8 in parallel) take 480 V 3-wire; CIRRO and CIRRO-IB need the 480Y/277 V 4-wire supply.
How heavy is a power module?
From 30.5 lb (RAD-PWR-15, 15 kVA) to 119 lb (INFINITE-PWR-100), by the 2026 catalog. The RADIANT-IB user manual asks for two people to lift a module out of its slot.
Which modular frame for your project?
Send the load today and in five years, the supply and the minutes: we answer with the frame, the modules and the battery.