N+1 · hot-swap · 208 V and 480 V · 15 to 125 kVA modules

Modular UPS: hot-swap power modules, 15 kVA to 1,500 kVA per frame

A modular UPS is a frame of slots filled with identical power modules: it grows by adding modules and keeps the load on the inverter while one is swapped. AEC builds 11 modular frames for US supplies, from the 15 kVA modules of RADIANT at 208 V to the 125 kVA silicon carbide modules of INFINITE 1.5MW at 480 V.

From the 2026 catalog

Every AEC modular frame, with N+1 worked out

N+1 here is the frame with every slot filled and one module held spare. INFINITE 100 and 200 are sold with their spare slot: 1 + 1 and 2 + 1 modules. kVA = kW on every series (unity power factor).

AEC modular UPS frames, power and redundancy, US catalog 2026
FrameSupplyModule, weightSlotsFrame ratingN+1, frame fullIn parallel, up to
RADIANT 90208Y/120 V15 kVA, 30.5 lb690 kVA75 kW4 frames
RADIANT-IB 100208Y/120 V20 kVA, 44 lb5100 kVA80 kW3 cabinets
CIRRO-IB 150480Y/277 V, 4-wire30 kVA, 52 lb5150 kVA120 kW3 cabinets
CIRRO 360480Y/277 V, 4-wire60 kVA, 77 lb6360 kVA300 kW8 units
CIRRO 600480Y/277 V, 4-wire100 kVA, 103.6 lb6600 kVA500 kW8 units
CIRRO 800480Y/277 V, 4-wire100 kVA, 103.6 lb8800 kVA700 kW8 units
CIRRO 1200480Y/277 V, 4-wire100 kVA, 103.6 lb121,200 kVA1,100 kW8 units
CIRRO 1600480Y/277 V, 4-wire100 kVA, 103.6 lb161,600 kVA1,500 kW8 units
INFINITE 100480 V, 3-wire100 kVA, 119 lb1 + 1100 kVA100 kW3 frames
INFINITE 200480 V, 3-wire100 kVA, 119 lb2 + 1200 kVA200 kW3 frames
INFINITE 1.5MW480 V, 3-wire125 kVA, 119 lb121,500 kVA1,375 kW8 units

Floor, weight and switchgear

kW per square foot is the N+1 power over the frame's own footprint: the figure that sets how much of the room the UPS takes. Batteries and service space come on top.

AEC modular UPS frames, size, power density and weight
FrameW × D × HFootprintN+1 power per ft²Weight, every slot filledBreakers in the frame
RADIANT 9017.4 × 33.1 × 59.5 in4 ft²19 kW/ft²390.5 lb4
RADIANT-IB 10023.6 × 39.4 × 78.7 in6.5 ft²12 kW/ft²650 lb*not stated
CIRRO-IB 15023.6 × 39.4 × 78.7 in6.5 ft²19 kW/ft²876 lb*not stated
CIRRO 36023.6 × 39.4 × 78.7 in6.5 ft²46 kW/ft²1,088.4 lb1
CIRRO 60031.5 × 39.4 × 78.7 in8.6 ft²58 kW/ft²1,514.5 lb4
CIRRO 80031.5 × 39.4 × 78.7 in8.6 ft²81 kW/ft²1,902.4 lb4
CIRRO 120047.2 × 43.3 × 78.7 in14.2 ft²78 kW/ft²2,618.9 lbnone: external switchgear
CIRRO 160063 × 39.4 × 78.7 in17.2 ft²87 kW/ft²3,796.1 lbnone: external switchgear
INFINITE 10023.6 × 39.4 × 81.4 in6.5 ft²15 kW/ft²571.3 lb3
INFINITE 20023.6 × 39.4 × 81.4 in6.5 ft²31 kW/ft²710.4 lb3
INFINITE 1.5MW70.9 × 39.4 × 78.7 in19.4 ft²71 kW/ft²6,170.7 lbnot stated

* RADIANT-IB and CIRRO-IB: the frame and its five modules, without the battery trays and blocks they also hold (up to 240 × 12 V 9 Ah). Other weights: the catalog's full configuration. The CIRRO 600 and 800 are the same 31.5 × 39.4 in cabinet with 6 or 8 slots: the 800 adds 200 kW of N+1 power for 388 lb and no floor.

By load

Which frame carries your load with N+1?

The sizing rule of the RADIANT-IB user manual, for any frame: modules = load ÷ (80% of one module), rounded up, plus one. The smallest frame that holds them, or the fewest frames in parallel; each module's share in normal running and the efficiency there on the catalog's curve.

Smallest AEC modular frame with N+1 for each load, by supply
IT load208Y/120 V480Y/277 V, 4-wire480 V, 3-wire
30 kWRADIANT 90: 4 × 15 kVA in 6 slots, each at 50%, 93.9%CIRRO-IB 150: 3 × 30 kVA in 5 slots, each at 33%, 95.3%—
60 kWRADIANT 90: 6 × 15 kVA in 6 slots, each at 67%, 94%CIRRO-IB 150: 4 × 30 kVA in 5 slots, each at 50%, 95.9%—
120 kW2 × RADIANT 90: 11 × 15 kVA in 12 slots, each at 73%, 94%CIRRO 360: 4 × 60 kVA in 6 slots, each at 50%, 95.9%INFINITE 200: 3 × 100 kVA in 3 slots, each at 40%, 97.1%
250 kW4 × RADIANT 90: 22 × 15 kVA in 24 slots, each at 76%, 94%CIRRO 600: 5 × 100 kVA in 6 slots, each at 50%, 96.9%2 × INFINITE 200: 5 × 100 kVA in 6 slots, each at 50%, 97.3%
400 kW—CIRRO 600: 6 × 100 kVA in 6 slots, each at 67%, 97%3 × INFINITE 200: 6 × 100 kVA in 9 slots, each at 67%, 97.3%
600 kW—CIRRO 1200: 9 × 100 kVA in 12 slots, each at 67%, 97%INFINITE 1.5MW: 7 × 125 kVA in 12 slots, each at 69%
900 kW—CIRRO 1600: 13 × 100 kVA in 16 slots, each at 69%, 97%INFINITE 1.5MW: 10 × 125 kVA in 12 slots, each at 72%
1,200 kW—CIRRO 1600: 16 × 100 kVA in 16 slots, each at 75%, 97%2 × INFINITE 1.5MW: 13 × 125 kVA in 24 slots, each at 74%

208 V shown up to 300 kW; INFINITE 1.5MW from its smallest catalog set-up, six modules (INF15-750). INFINITE 1.5MW has no published curve: its catalog gives up to 97.5% AC/AC. The sizing tool adds the battery minutes; growing a modular UPS plans the day-one frame for the load in five years.

Efficiency where the modules run

What N+1 does to efficiency and heat

With N+1 the modules never run at full load: a full frame at its N+1 power runs each module at (slots − 1) ÷ slots. In a 2N design each side carries half of that. Read off the 2026 catalog's curves.

Efficiency and heat of each AEC modular frame at its N+1 power and at half of it
FrameAt N+1 powerAt half of it (one side of 2N)
RADIANT 9075 kW: 83% each, 93.9%, 4.8 kW of heat38 kW: 42% each, 93.5%, 2.6 kW of heat
RADIANT-IB 10080 kW: 80% each, 94%, 5.1 kW of heat40 kW: 40% each, 93.4%, 2.8 kW of heat
CIRRO-IB 150120 kW: 80% each, 96%, 5.1 kW of heat60 kW: 40% each, 95.5%, 2.8 kW of heat
CIRRO 360300 kW: 83% each, 95.9%, 12.7 kW of heat150 kW: 42% each, 95.6%, 6.8 kW of heat
CIRRO 600500 kW: 83% each, 96.9%, 15.8 kW of heat250 kW: 42% each, 96.7%, 8.6 kW of heat
CIRRO 800700 kW: 88% each, 96.9%, 22.4 kW of heat350 kW: 44% each, 96.7%, 11.9 kW of heat
CIRRO 12001,100 kW: 92% each, 96.9%, 35.6 kW of heat550 kW: 46% each, 96.8%, 18.3 kW of heat
CIRRO 16001,500 kW: 94% each, 96.9%, 48.8 kW of heat750 kW: 47% each, 96.8%, 24.7 kW of heat
INFINITE 100100 kW: 50% each, 97.3%, 2.8 kW of heat50 kW: 25% each, 96.9%, 1.6 kW of heat
INFINITE 200200 kW: 67% each, 97.3%, 5.5 kW of heat100 kW: 33% each, 97%, 3.1 kW of heat

Heat = load × (1 ÷ efficiency − 1), in double conversion, straight between the curve's 25, 50, 75 and 100% points. Every curve: UPS efficiency curves.

Batteries

What each frame runs on

RADIANT and CIRRO: an external VRLA bank on the DC bus; CIRRO 600–1600 takes 40 blocks of 12 V by default, 30 to 50 selectable. RADIANT-IB and CIRRO-IB: up to 240 blocks of 12 V 9 Ah in hot-swappable trays inside the cabinet. INFINITE and INFINITE 1.5MW: lead-acid or L6 lithium cabinets; INFINITE 1.5MW takes 4, 6 or 8 of them, 80 to 160 modules of 50 Ah, 10 kW each. The 50 Ah LiFePO4 battery modules are certified to UL 1973 and UL 9540A tested.

Before you buy

Three things to fix on day one

The frame, not the modules. A frame full on day one has no slot left for N+1 or growth. The switchgear. CIRRO 1200 and 1600 have no breakers inside; plan the external board with the room. The cables and the battery for the frame's final power, so added modules arrive with their runtime. The method in full: modular UPS and N+X · N+1 redundancy.

Like for like

Modular frames of other makers, from their own documents

Frame rating over the frame's footprint, the same arithmetic for every row. Other makers' figures as their documents give them, read 10 Oct 2026; the documents are named, not linked. Weights are left out: not every maker gives one for the same configuration.

Modular UPS frames: rating, module, efficiency, footprint and kW per square foot
FrameRatingModuleEfficiency, as publishedW × DkW per ft²Document
AEC RADIANT 9090 kW15 kVAup to 94%17.4 × 33.1 in23AEC 2026 catalog
AEC RADIANT-IB 100100 kW20 kVAup to 94%23.6 × 39.4 in15AEC 2026 catalog
AEC CIRRO 600600 kW100 kVAup to 97%31.5 × 39.4 in70AEC 2026 catalog
AEC CIRRO 800800 kW100 kVAup to 97%31.5 × 39.4 in93AEC 2026 catalog
AEC CIRRO 16001,600 kW100 kVAup to 97%63 × 39.4 in93AEC 2026 catalog
AEC INFINITE 200200 kW100 kVAup to 97.3%23.6 × 39.4 in31AEC 2026 catalog
AEC INFINITE 1.5MW1,500 kW125 kVAup to 97.5%70.9 × 39.4 in77AEC 2026 catalog
Eaton 93PM 250 kW 480 VEaton 93PM, 480 V250 kW50 kW97%22 × 42 in39eaton.com/…/eaton-93pm-480v-ups; eaton-93pm-480v-250kw-ups-brochure-br153218en.pdf (eaton.com)
Vertiv APM2 480 V 600 kVA frameVertiv Liebert APM2, 480 V600 kW60 kVA97.5%47.2 × 40.6 in45vertiv-liebert-apm2-10-600kw-brochure-sl-71311.pdf (vertiv.com); vertiv-liebert-apm2-data-sheet-sl-71300.pdf (vertiv.com)

A maker's "up to" efficiency is the top of its own curve and test; the rows are not measured side by side. Model by model at the same power: modular UPS at 208 V · modular UPS at 480 V up to 1,600 kVA.

Modular UPS

Questions people ask

What is a modular UPS?

A UPS built as a frame of slots and a set of identical power modules, each with its own rectifier, inverter and control. The modules share the load; one more than the load needs gives N+1, and any one can be pulled with the system running. AEC modules run from 15 kVA (RADIANT) to 125 kVA (INFINITE 1.5MW).

How many modules do I need for N+1?

Divide the load by 80% of one module's kW, round up, add one. For 400 kW on 100 kVA CIRRO modules: 400 ÷ 80 = 5, plus one is 6, a full CIRRO 600; the same 6 modules in a CIRRO 800 leave two slots to grow, in the same 31.5 × 39.4 in footprint.

Can modules of different series share a frame?

No. Each frame takes its own series' module only; the catalog states it for the two that look alike, the 20 kVA RADIANT-IB and the 30 kVA CIRRO-IB modules, which are not interchangeable.

Does adding modules add runtime?

No. Modules add power, not stored energy: the same battery behind more kW gives fewer minutes. Size the battery, its cables and its breaker for the frame's final power.

Which modular UPS for 480 V without a neutral?

INFINITE (100 to 600 kVA, up to 3 frames in parallel) and INFINITE 1.5MW (750 to 1,500 kVA per frame, up to 8 in parallel) take 480 V 3-wire; CIRRO and CIRRO-IB need the 480Y/277 V 4-wire supply.

How heavy is a power module?

From 30.5 lb (RAD-PWR-15, 15 kVA) to 119 lb (INFINITE-PWR-100), by the 2026 catalog. The RADIANT-IB user manual asks for two people to lift a module out of its slot.

Which modular frame for your project?

Send the load today and in five years, the supply and the minutes: we answer with the frame, the modules and the battery.