AUREON · 208V three-phase UPS

AUR-10 AUREON 10 kVA, 208V three-phase UPS

VRLA10 kVAOnline double conversion

The AEC AUREON AUR-10 is a 10 kVA / 10 kW online double-conversion UPS for 208 V three-phase loads, with no batteries included: the frame takes up to 80 internal 12 V 9 Ah VRLA blocks, in 20, 40, 60 or 80. Kept at 80 % of its rating, it carries loads up to 8 kW.

10 kVA / 10 kWRating
14.9 × 39.1 × 49.2 inW × D × H
231 lbWeight
VRLA, up to 80 inside, not includedBattery
AEC AUREON UPS, series picture

Series picture.

Load by load

The AUR-10 at 25, 50, 75 and 100 % load.

Its 10 kW rating in four steps, worked out from its own catalog figures.

At 25, 50, 75 and 100 % load
LoadOutput current per phase, at 208 VEfficiencyHeat to removeHeat to remove (BTU/h)
25 % of the AUR-10, 2.5 kW6.9 A per phase92.5 % efficient203 W of heat690 BTU/h to cool
50 % of the AUR-10, 5.0 kW13.9 A per phase93.9 % efficient325 W of heat1,110 BTU/h to cool
75 % of the AUR-10, 7.5 kW20.8 A per phase94.0 % efficient479 W of heat1,630 BTU/h to cool
100 % of the AUR-10, 10 kW27.8 A per phase93.8 % efficient661 W of heat2,260 BTU/h to cool

Current = kVA × load ÷ (√3 × volts).

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

What is the AUR-10?

  • Technology: 3-level IGBT; unity power factor (kVA = kW).
  • Efficiency: up to 94%. 4.3" touch screen color display; cold start and self-cleaning functions.
  • Comms: Modbus and dry contact standard.

The lines every AUREON shares, from technology to warranty, are in the AUREON key facts and in the datasheet below.

Size and floor

How big it is

14.9" W × 39.1" D × 49.2" H (378 × 993 × 1,250 mm); 231 lb (104.8 kg) net.

4.0 ft²footprint (0.38 m²)
57 lb/ft²floor load of the cabinet alone
Towerform factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

5′9″ FrontSide 14.9″39.1″49.2″

Datasheet

AUR-10 datasheet.

The AUR-10 in the AEC 2026 catalog, figure by figure. Compare it with every AUREON model.

AUR-10 datasheet
ParameterAUR-10
Power
Rated power (kVA)10
Active power (kW)10
Output power factor1.0
Electrical
Input / output208 V three-phase, 4-wire (3P+N)
TopologyOnline Double Conversion
Efficiency, up to94%
Battery DC bus240 V DC
Battery and runtime
Battery typeVRLA (sealed lead-acid)
Battery configurationFrame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80)
Mechanical
Form factorTower
Dimensions W × D × H14.9 × 39.1 × 49.2 in (378 × 993 × 1,250 mm)
Net weight231 lb (104.8 kg)
Footprint4.0 ft² (0.38 m²)
Common to every AUREON
BatteryVRLA batteries
Network cardSNMP-L (SNMP)
Warranty3 years on UPS · 2 years on VRLA batteries
CertificationUL 1778 listed, UL file E543003 (AEC UPS USA LLC)
Quality systemISO 9001:2015, the group's quality system (SGS)

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

AUR-10: what people ask

What is the output current of the AUR-10?

27.8 A per phase at full load: 10 kVA ÷ (√3 × 208 V). Size the input breaker and the cables of the AUR-10 from its installation manual and the local electrical code, not from this figure alone.

How much heat does the AUR-10 give off?

About 661 W, 2,260 BTU/h, at full load, where it is 93.8% efficient. Plan the room's cooling for a little more than that: the AUR-10 is less efficient at part load and while its battery recharges.

Will the AUR-10 fit through a standard door?

Yes: 14.9 in (378 mm) across its narrow side and 49.2 in (1,250 mm) high, it passes a standard 36 × 80-inch door upright. On the way in, check corridors, elevators and the floor load of the AUR-10 (size section above).

The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h

AUREON

Other AUREON models

The AUREON series, with pictures

By power, the AUR-10 is the smallest in the AUREON series, which runs from 10 to 30 kVA. One size up are the AUR-20, AUR20-60X9A and AUR20-80X9A, all 10 kVA more. The same 10 kVA also comes as the AUR10-40X9A and AUR10-80X9A: the table below gives each one's weight and battery.

Every AUREON model side by side (8)
AUREON models side by side
ModelPowerPower against this modelNet weightWeight against this modelRuntime at 50 % loadBattery configuration
AUR-1010 kVAthis page231 lbthis page—Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80)
AUR10-40X9A10 kVAthe same power465 lb234 lb heavier25 min at 50 % loadInternal
AUR10-80X9A10 kVAthe same power699 lb468 lb heavier60 min at 50 % loadInternal
AUR-2020 kVA10 kVA more258 lb27 lb heavier—Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80)
AUR20-60X9A20 kVA10 kVA more609 lb378 lb heavier13.5 min at 50 % load, AEC estimateInternal
AUR20-80X9A20 kVA10 kVA more726 lb495 lb heavier20 min at 50 % load, AEC estimateInternal
AUR-3030 kVA20 kVA more282 lb51 lb heavier—Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80)
AUR30-80X9A30 kVA20 kVA more750 lb519 lb heavier14 min at 50 % loadInternal

The AUR-10 for your project