AUREON · 208V three-phase UPS
AUR-10 AUREON 10 kVA, 208V three-phase UPS
The AEC AUREON AUR-10 is a 10 kVA / 10 kW online double-conversion UPS for 208 V three-phase loads, with no batteries included: the frame takes up to 80 internal 12 V 9 Ah VRLA blocks, in 20, 40, 60 or 80. Kept at 80 % of its rating, it carries loads up to 8 kW.

Series picture.
Load by load
The AUR-10 at 25, 50, 75 and 100 % load.
Its 10 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current per phase, at 208 V | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|
| 25 % of the AUR-10, 2.5 kW | 6.9 A per phase | 92.5 % efficient | 203 W of heat | 690 BTU/h to cool |
| 50 % of the AUR-10, 5.0 kW | 13.9 A per phase | 93.9 % efficient | 325 W of heat | 1,110 BTU/h to cool |
| 75 % of the AUR-10, 7.5 kW | 20.8 A per phase | 94.0 % efficient | 479 W of heat | 1,630 BTU/h to cool |
| 100 % of the AUR-10, 10 kW | 27.8 A per phase | 93.8 % efficient | 661 W of heat | 2,260 BTU/h to cool |
Current = kVA × load ÷ (√3 × volts).
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the AUR-10 at your load?
The AUR-10 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What is the AUR-10?
- Technology: 3-level IGBT; unity power factor (kVA = kW).
- Efficiency: up to 94%. 4.3" touch screen color display; cold start and self-cleaning functions.
- Comms: Modbus and dry contact standard.
The lines every AUREON shares, from technology to warranty, are in the AUREON key facts and in the datasheet below.
Size and floor
How big it is
14.9" W × 39.1" D × 49.2" H (378 × 993 × 1,250 mm); 231 lb (104.8 kg) net.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
The AUR-10 takes the clearances, wiring, cable entry and breakers of every AUREON model, from its AEC US user manual: see them on the AUREON page.
Datasheet
AUR-10 datasheet.
The AUR-10 in the AEC 2026 catalog, figure by figure. Compare it with every AUREON model.
| Parameter | AUR-10 |
|---|---|
| Power | |
| Rated power (kVA) | 10 |
| Active power (kW) | 10 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 208 V three-phase, 4-wire (3P+N) |
| Topology | Online Double Conversion |
| Efficiency, up to | 94% |
| Battery DC bus | 240 V DC |
| Battery and runtime | |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80) |
| Mechanical | |
| Form factor | Tower |
| Dimensions W × D × H | 14.9 × 39.1 × 49.2 in (378 × 993 × 1,250 mm) |
| Net weight | 231 lb (104.8 kg) |
| Footprint | 4.0 ft² (0.38 m²) |
| Common to every AUREON | |
| Battery | VRLA batteries |
| Network card | SNMP-L (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Certification | UL 1778 listed, UL file E543003 (AEC UPS USA LLC) |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The AUREON documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
Quick answers
AUR-10: what people ask
What is the output current of the AUR-10?
27.8 A per phase at full load: 10 kVA ÷ (√3 × 208 V). Size the input breaker and the cables of the AUR-10 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the AUR-10 give off?
About 661 W, 2,260 BTU/h, at full load, where it is 93.8% efficient. Plan the room's cooling for a little more than that: the AUR-10 is less efficient at part load and while its battery recharges.
Will the AUR-10 fit through a standard door?
Yes: 14.9 in (378 mm) across its narrow side and 49.2 in (1,250 mm) high, it passes a standard 36 × 80-inch door upright. On the way in, check corridors, elevators and the floor load of the AUR-10 (size section above).
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
AUREON
Other AUREON models
By power, the AUR-10 is the smallest in the AUREON series, which runs from 10 to 30 kVA. One size up are the AUR-20, AUR20-60X9A and AUR20-80X9A, all 10 kVA more. The same 10 kVA also comes as the AUR10-40X9A and AUR10-80X9A: the table below gives each one's weight and battery.
Every AUREON model side by side (8)
| Model | Power | Power against this model | Net weight | Weight against this model | Runtime at 50 % load | Battery configuration |
|---|---|---|---|---|---|---|
| AUR-10 | 10 kVA | this page | 231 lb | this page | — | Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80) |
| AUR10-40X9A | 10 kVA | the same power | 465 lb | 234 lb heavier | 25 min at 50 % load | Internal |
| AUR10-80X9A | 10 kVA | the same power | 699 lb | 468 lb heavier | 60 min at 50 % load | Internal |
| AUR-20 | 20 kVA | 10 kVA more | 258 lb | 27 lb heavier | — | Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80) |
| AUR20-60X9A | 20 kVA | 10 kVA more | 609 lb | 378 lb heavier | 13.5 min at 50 % load, AEC estimate | Internal |
| AUR20-80X9A | 20 kVA | 10 kVA more | 726 lb | 495 lb heavier | 20 min at 50 % load, AEC estimate | Internal |
| AUR-30 | 30 kVA | 20 kVA more | 282 lb | 51 lb heavier | — | Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80) |
| AUR30-80X9A | 30 kVA | 20 kVA more | 750 lb | 519 lb heavier | 14 min at 50 % load | Internal |
Install and run it:Guide specification, CSI 26 33 53
The AUR-10 for your project
Send the load, the voltage and the minutes you need from the AUR-10. We reply with the configuration, the batteries and the lead time.