AUREON · 208V three-phase UPS

AUR10-40X9A AUREON 10 kVA, 208V three-phase UPS

VRLA10 kVAOnline double conversion

The AEC AUREON AUR10-40X9A is a 10 kVA / 10 kW online double-conversion UPS for 208 V three-phase loads, with internal VRLA batteries. Kept at 80 % of its rating, it carries loads up to 8 kW.

10 kVA / 10 kWRating
14.9 × 39.1 × 49.2 inW × D × H
465 lbWeight
VRLA, internalBattery
AEC AUREON UPS, series picture

Series picture.

Load by load

The AUR10-40X9A at 25, 50, 75 and 100 % load.

Its 10 kW rating in four steps, worked out from its own catalog figures.

At 25, 50, 75 and 100 % load
LoadOutput current per phase, at 208 VEfficiencyHeat to removeHeat to remove (BTU/h)
25 % of the AUR10-40X9A, 2.5 kW6.9 A per phase92.5 % efficient203 W of heat690 BTU/h to cool
50 % of the AUR10-40X9A, 5.0 kW13.9 A per phase93.9 % efficient325 W of heat1,110 BTU/h to cool
75 % of the AUR10-40X9A, 7.5 kW20.8 A per phase94.0 % efficient479 W of heat1,630 BTU/h to cool
100 % of the AUR10-40X9A, 10 kW27.8 A per phase93.8 % efficient661 W of heat2,260 BTU/h to cool

Current = kVA × load ÷ (√3 × volts).

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

What is the AUR10-40X9A?

The code AUR10-40X9A orders these catalog items:

  • 1 × AUR-10: 10 kVA tower, without batteries, 14.9 × 39.1 × 49.2 in (378 × 993 × 1,250 mm), 231 lb (104.8 kg)
  • 40 × CSB-9AH: 12 V 9 Ah VRLA battery block, 5.9 lb (2.7 kg) each
  • Output: 10,000 VA / 10,000 W (unity power factor, kVA = kW).
  • Input / Output: 208 V three-phase.
  • Technology: 3-level IGBT; cold start, self-cleaning and smart functions.
  • Battery: internal hot-swappable VRLA, 40 × 12 V 9 Ah.
  • Efficiency: up to 94%.
  • Display: 4.3-inch color touchscreen.
  • Comms: Modbus and dry contacts, standard.

The lines every AUREON shares, from technology to warranty, are in the AUREON key facts and in the datasheet below.

Size and floor

How big it is

14.9" W × 39.1" D × 49.2" H (378 × 993 × 1,250 mm); 465 lb (210.9 kg) net. It ships in one carton of 18 × 43.7 × 54.7 in, 558 lb (253.1 kg) gross.

4.0 ft²footprint (0.38 m²)
115 lb/ft²floor load of the cabinet alone
Towerform factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

5′9″ FrontSide 14.9″39.1″49.2″

Datasheet

AUR10-40X9A datasheet.

The AUR10-40X9A in the AEC 2026 catalog, figure by figure. Compare it with every AUREON model.

AUR10-40X9A datasheet
ParameterAUR10-40X9A
Power
Rated power (kVA)10
Active power (kW)10
Output power factor1.0
Electrical
Input / output208 V three-phase, 4-wire (3P+N)
TopologyOnline Double Conversion
Efficiency, up to94%
Battery DC bus240 V DC
Battery and runtime
Battery typeVRLA (sealed lead-acid)
Battery configurationInternal
Runtime at 50 % load25 min
Runtime at 100 % load7 min
Mechanical
Form factorTower
Dimensions W × D × H14.9 × 39.1 × 49.2 in (378 × 993 × 1,250 mm)
Net weight465 lb (210.9 kg)
Footprint4.0 ft² (0.38 m²)
Shipping
Cartons1
Shipping weight558 lb
Common to every AUREON
Battery, AUR10-40X9Ainternal hot-swappable VRLA, 40 × 12V 9Ah
Network cardSNMP-L (SNMP)
Warranty3 years on UPS · 2 years on VRLA batteries
CertificationUL 1778 listed, UL file E543003 (AEC UPS USA LLC)
Quality systemISO 9001:2015, the group's quality system (SGS)

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

AUR10-40X9A: what people ask

What is the output current of the AUR10-40X9A?

27.8 A per phase at full load: 10 kVA ÷ (√3 × 208 V). Size the input breaker and the cables of the AUR10-40X9A from its installation manual and the local electrical code, not from this figure alone.

How much heat does the AUR10-40X9A give off?

About 661 W, 2,260 BTU/h, at full load, where it is 93.8% efficient. Plan the room's cooling for a little more than that: the AUR10-40X9A is less efficient at part load and while its battery recharges.

Will the AUR10-40X9A fit through a standard door?

Yes: 14.9 in (378 mm) across its narrow side and 49.2 in (1,250 mm) high, it passes a standard 36 × 80-inch door upright. On the way in, check corridors, elevators and the floor load of the AUR10-40X9A (size section above).

The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h

AUREON

Other AUREON models

The AUREON series, with pictures

By power, the AUR10-40X9A is the smallest in the AUREON series, which runs from 10 to 30 kVA. One size up are the AUR-20, AUR20-60X9A and AUR20-80X9A, all 10 kVA more. The same 10 kVA also comes as the AUR-10 and AUR10-80X9A: the table below gives each one's weight and battery.

Every AUREON model side by side (8)
AUREON models side by side
ModelPowerPower against this modelNet weightWeight against this modelRuntime at 50 % loadBattery configuration
AUR-1010 kVAthe same power231 lb234 lb lighter—Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80)
AUR10-40X9A10 kVAthis page465 lbthis page25 min at 50 % loadInternal
AUR10-80X9A10 kVAthe same power699 lb234 lb heavier60 min at 50 % loadInternal
AUR-2020 kVA10 kVA more258 lb207 lb lighter—Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80)
AUR20-60X9A20 kVA10 kVA more609 lb144 lb heavier13.5 min at 50 % load, AEC estimateInternal
AUR20-80X9A20 kVA10 kVA more726 lb261 lb heavier20 min at 50 % load, AEC estimateInternal
AUR-3030 kVA20 kVA more282 lb183 lb lighter—Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80)
AUR30-80X9A30 kVA20 kVA more750 lb285 lb heavier14 min at 50 % loadInternal

The AUR10-40X9A for your project