AUREON · 208V three-phase UPS

AUR30-80X9A AUREON 30 kVA, 208V three-phase UPS

VRLA30 kVAOnline double conversion

The AEC AUREON AUR30-80X9A is a 30 kVA / 30 kW online double-conversion UPS for 208 V three-phase loads, with internal VRLA batteries. Kept at 80 % of its rating, it carries loads up to 24 kW.

30 kVA / 30 kWRating
14.9 × 39.1 × 49.2 inW × D × H
750 lbWeight
VRLA, internalBattery
AEC AUREON UPS, series picture

Series picture.

Load by load

The AUR30-80X9A at 25, 50, 75 and 100 % load.

Its 30 kW rating in four steps, worked out from its own catalog figures.

At 25, 50, 75 and 100 % load
LoadOutput current per phase, at 208 VEfficiencyHeat to removeHeat to remove (BTU/h)
25 % of the AUR30-80X9A, 7.5 kW20.8 A per phase92.5 % efficient608 W of heat2,070 BTU/h to cool
50 % of the AUR30-80X9A, 15 kW41.6 A per phase93.9 % efficient974 W of heat3,320 BTU/h to cool
75 % of the AUR30-80X9A, 23 kW62.5 A per phase94.0 % efficient1.4 kW of heat4,900 BTU/h to cool
100 % of the AUR30-80X9A, 30 kW83.3 A per phase93.8 % efficient2.0 kW of heat6,770 BTU/h to cool

Current = kVA × load ÷ (√3 × volts).

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

What is the AUR30-80X9A?

The code AUR30-80X9A orders these catalog items:

  • 1 × AUR-30: 30 kVA tower, without batteries, 14.9 × 39.1 × 49.2 in (378 × 993 × 1,250 mm), 282 lb (127.9 kg)
  • 80 × CSB-9AH: 12 V 9 Ah VRLA battery block, 5.9 lb (2.7 kg) each
  • Output: 30,000 VA / 30,000 W (unity power factor, kVA = kW).
  • Input / Output: 208 V three-phase.
  • Technology: 3-level IGBT; cold start, self-cleaning and smart functions.
  • Battery: internal hot-swappable VRLA, 80 × 12 V 9 Ah.
  • Efficiency: up to 94%.
  • Display: 4.3-inch color touchscreen.
  • Comms: Modbus and dry contacts, standard.

The lines every AUREON shares, from technology to warranty, are in the AUREON key facts and in the datasheet below.

Size and floor

How big it is

14.9" W × 39.1" D × 49.2" H (378 × 993 × 1,250 mm); 750 lb (340.2 kg) net. It ships in one carton of 18 × 43.7 × 54.7 in, 900 lb (408.2 kg) gross.

4.0 ft²footprint (0.38 m²)
185 lb/ft²floor load of the cabinet alone
Towerform factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

5′9″ FrontSide 14.9″39.1″49.2″

Datasheet

AUR30-80X9A datasheet.

The AUR30-80X9A in the AEC 2026 catalog, figure by figure. Compare it with every AUREON model.

AUR30-80X9A datasheet
ParameterAUR30-80X9A
Power
Rated power (kVA)30
Active power (kW)30
Output power factor1.0
Electrical
Input / output208 V three-phase, 4-wire (3P+N)
TopologyOnline Double Conversion
Efficiency, up to94%
Battery DC bus240 V DC
Battery and runtime
Battery typeVRLA (sealed lead-acid)
Battery configurationInternal
Runtime at 50 % load14 min
Runtime at 100 % load4 min
Mechanical
Form factorTower
Dimensions W × D × H14.9 × 39.1 × 49.2 in (378 × 993 × 1,250 mm)
Net weight750 lb (340.2 kg)
Footprint4.0 ft² (0.38 m²)
Shipping
Cartons1
Shipping weight900 lb
Common to every AUREON
Battery, AUR30-80X9Ainternal hot-swappable VRLA, 80 × 12V 9Ah
Network cardSNMP-L (SNMP)
Warranty3 years on UPS · 2 years on VRLA batteries
CertificationUL 1778 listed, UL file E543003 (AEC UPS USA LLC)
Quality systemISO 9001:2015, the group's quality system (SGS)

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

AUR30-80X9A: what people ask

What is the output current of the AUR30-80X9A?

83.3 A per phase at full load: 30 kVA ÷ (√3 × 208 V). Size the input breaker and the cables of the AUR30-80X9A from its installation manual and the local electrical code, not from this figure alone.

How much heat does the AUR30-80X9A give off?

About 2.0 kW, 6,770 BTU/h, at full load, where it is 93.8% efficient. Plan the room's cooling for a little more than that: the AUR30-80X9A is less efficient at part load and while its battery recharges.

Will the AUR30-80X9A fit through a standard door?

Yes: 14.9 in (378 mm) across its narrow side and 49.2 in (1,250 mm) high, it passes a standard 36 × 80-inch door upright. On the way in, check corridors, elevators and the floor load of the AUR30-80X9A (size section above).

The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h

AUREON

Other AUREON models

The AUREON series, with pictures

By power, the AUR30-80X9A is the largest in the AUREON series, which runs from 10 to 30 kVA. One size down are the AUR-20, AUR20-60X9A and AUR20-80X9A, all 10 kVA less. The same 30 kVA also comes as AUR-30 (frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80), 468 lb lighter); the AUR30-80X9A has internal batteries.

Every AUREON model side by side (8)
AUREON models side by side
ModelPowerPower against this modelNet weightWeight against this modelRuntime at 50 % loadBattery configuration
AUR-1010 kVA20 kVA less231 lb519 lb lighter—Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80)
AUR10-40X9A10 kVA20 kVA less465 lb285 lb lighter25 min at 50 % loadInternal
AUR10-80X9A10 kVA20 kVA less699 lb51 lb lighter60 min at 50 % loadInternal
AUR-2020 kVA10 kVA less258 lb492 lb lighter—Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80)
AUR20-60X9A20 kVA10 kVA less609 lb141 lb lighter13.5 min at 50 % load, AEC estimateInternal
AUR20-80X9A20 kVA10 kVA less726 lb24 lb lighter20 min at 50 % load, AEC estimateInternal
AUR-3030 kVAthe same power282 lb468 lb lighter—Frame only, no batteries included: takes up to 80 internal 12 V 9 Ah VRLA blocks (20, 40, 60 or 80)
AUR30-80X9A30 kVAthis page750 lbthis page14 min at 50 % loadInternal

The AUR30-80X9A for your project

Send the load, the voltage and the minutes you need from the AUR30-80X9A. We reply with the configuration, the batteries and the lead time.