CIRRO-IB · 480 V three-phase UPS

CIRIB150 CIRRO-IB 150 kVA frame, 30–150 kVA fitted

VRLA30–150 kVA5 ordering codes

The AEC CIRRO-IB CIRIB150 is a 150 kVA modular UPS frame for 480 V three-phase loads with five slots for 30 kVA hot-swappable power modules. The 2026 catalog lists it with 1, 2, 3, 4 or 5 modules fitted, 30–150 kVA in all; each code is a row below.

4-wire · 3P+N480 V 4-wire, wye: three phases, neutral and ground (277/480 V)

30–150 kVARating
23.6 × 39.3 × 78.7 inW × D × H
2,192–2,400 lbWeight, by code
VRLA, insideBattery

Series picture.

5 ordering codes

Which CIRIB150 do you need?

One 150 kVA frame, a row per number of modules fitted. Only what changes from one code to the next is here; what they share is under the table.

CIRIB150: the ordering codes and what changes from one to the next
Ordering codePowerFree slotsWith one module spare (N+1)Net weightFloor loadCurrent per phase at 480 VCartons
CIRIB150-1X301 × 30 kVA power module3DAsk30 kVA / 30 kW4 of 5no spare with one module2,191.8 lb (994.2 kg)340 lb/ft²36.1 A26
CIRIB150-2X302 × 30 kVA power modules3DAsk60 kVA / 60 kW3 of 530 kVA2,243.8 lb (1,017.8 kg)348 lb/ft²72.2 A27
CIRIB150-3X303 × 30 kVA power modules3DAsk90 kVA / 90 kW2 of 560 kVA2,295.8 lb (1,041.4 kg)356 lb/ft²108 A28
CIRIB150-4X304 × 30 kVA power modules3DAsk120 kVA / 120 kW1 of 590 kVA2,347.8 lb (1,065 kg)365 lb/ft²144 A29
CIRIB150-5X305 × 30 kVA power modules3DAsk150 kVA / 150 kWnone of 5120 kVA2,399.8 lb (1,088.6 kg)373 lb/ft²180 A30

This model

What sets the CIRIB150 apart

The CIRRO-IB is one 150 kVA frame for 480 V three-phase that carries its batteries inside: five slots for 30 kVA power modules and trays for 240 blocks of 12 V 9 Ah, all in one 23.6 × 39.3 × 78.7 in cabinet. The catalog lists it with one to five modules, 30 to 150 kVA.

The blocks make it heavy from the first module: 2,191.8 lb (994.2 kg) with one, 340 lb/ft² on 6.4 ft², and each 30 kVA module adds 52 lb. It ships in 26 cartons and one more for each module, so plan the delivery as well as the floor. Where the batteries can stand in a room of their own, the CIRRO frames take the same 480 V load on an external bank.

AEC CIRIB150-5X30, rendered from its 3D modelDrag to turn

In 3D

Look around the CIRIB150-5X30

Efficiency

How efficient is the CIRIB150-5X30 at your load?

The CIRIB150-5X30 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.

—%

Load
—
Lost as heat
—
Heat to remove
—
Energy lost in a year, 24/7
—
Its cost in a year at per kWh
—

Every CIRRO-IB size on one curve

From the 2026 catalog

What every CIRIB150 code shares

  • Each 30 kVA power module, CIRIB-PWR-30: 52 lb (23.6 kg), hot-swappable
  • Technology: 3-level IGBT; unity power factor (kVA = kW); 40 A settable charger.
  • Input / Output: 480/277 V three-phase, 4-wire.
  • Battery: internal hot-swappable VRLA, up to 240 × 12 V 9 Ah blocks.
  • Efficiency: up to 96%.
  • Display: 7-inch color touchscreen.
  • Comms: RS-232, EPO and USB, standard.
  • Warranty: 3 years on UPS · 2 years on VRLA batteries.
  • Cabinet: 23.6" W × 39.3" D × 78.7" H (599 × 998 × 1,999 mm), the same for every code above

The lines every CIRRO-IB shares, from technology to warranty, are in the CIRRO-IB key facts.

Size and floor

How big it is

23.6" W × 39.3" D × 78.7" H (599 × 998 × 1,999 mm); from 2,191.8 lb (994.2 kg) to 2,399.8 lb (1,088.6 kg) net, code by code.

6.4 ft²footprint (0.60 m²)
373 lb/ft²floor load of the heaviest code
Modularform factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

5′9″ FrontSide 23.6″39.3″78.7″

Datasheet

CIRIB150 datasheet, code by code.

Every figure of the 5 codes in the AEC 2026 catalog. Compare them with every CIRRO-IB model.

CIRRO-IB datasheet, 5 models
ModelCIRIB150-1X30CIRIB150-2X30CIRIB150-3X30CIRIB150-4X30CIRIB150-5X30
Power
Rated power (kVA)306090120150
Active power (kW)306090120150
Output power factor1.01.01.01.01.0
Electrical
Input / output480 V three-phase, 4-wire (3P+N)480 V three-phase, 4-wire (3P+N)480 V three-phase, 4-wire (3P+N)480 V three-phase, 4-wire (3P+N)480 V three-phase, 4-wire (3P+N)
TopologyOnline double conversion, modular N+XOnline double conversion, modular N+XOnline double conversion, modular N+XOnline double conversion, modular N+XOnline double conversion, modular N+X
Efficiency, up to96%96%96%96%96%
Battery DC bus480 V DC480 V DC480 V DC480 V DC480 V DC
Battery and runtime
Battery typeVRLA (sealed lead-acid)VRLA (sealed lead-acid)VRLA (sealed lead-acid)VRLA (sealed lead-acid)VRLA (sealed lead-acid)
Battery configurationInternal Tray SystemInternal Tray SystemInternal Tray SystemInternal Tray SystemInternal Tray System
Runtime at 50% load45 min14 min10.5 min6 min6 min
Runtime at 100% load14 min6 min3 min2 min—
Mechanical
Form factorModularModularModularModularModular
Dimensions W × D × H23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm)23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm)23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm)23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm)23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm)
Net weight2,191.8 lb (994.2 kg)2,243.8 lb (1,017.8 kg)2,295.8 lb (1,041.4 kg)2,347.8 lb (1,065 kg)2,399.8 lb (1,088.6 kg)
Footprint6.4 ft² (0.60 m²)6.4 ft² (0.60 m²)6.4 ft² (0.60 m²)6.4 ft² (0.60 m²)6.4 ft² (0.60 m²)
Shipping
Cartons2627282930

From the AEC 2026 catalog. Efficiency is the catalog's “up to” figure; runtimes are AEC's runtime tables with new batteries; weights are the unit alone, without batteries outside it. Figures may change; the order confirmation governs.

CIRRO-IB

Other CIRRO-IB models

The CIRRO-IB series, with pictures

The CIRRO-IB has this one model page; its datasheet sets every code side by side.

The CIRIB150 for your project

Send the load, the voltage and the minutes you need from the CIRIB150. We reply with the code, the batteries and the lead time.