INFINITE 1.5MW · 480V three-phase UPS

INF15-1250 INFINITE 1.5MW 1,250 kVA, 480V three-phase UPS

Lithium or VRLA1,250 kVAOnline double conversion

The AEC INFINITE 1.5MW INF15-1250 is a 1,250 kVA / 1,250 kW online double-conversion UPS for 480 V three-phase loads, built on ten 125 kVA power modules, with 8 external AEC L6 lithium cabinets or a VRLA bank. Kept at 80 % of its rating, it carries loads up to 1,000 kW.

3-wire · Delta480 V 3-wire, delta: three phases and ground, no neutral

1,250 kVA / 1,250 kWRating
70.9 × 39.4 × 78.7 inW × D × H
5,932.6 lbWeight
VRLA or lithium, externalBattery
AEC INF15-1250, rendered from its 3D modelDrag to turn

In 3D

Look around the INF15-1250

Load by load

The INF15-1250 at 25, 50, 75 and 100 % load.

Its 1,250 kW rating in four steps, worked out from its own catalog figures.

At 25, 50, 75 and 100 % load
LoadOutput current per phase, at 480 VLoad on each of its 10 power modules
25 % of the INF15-1250, 313 kW376 A per phase25 % on each module
50 % of the INF15-1250, 625 kW752 A per phase50 % on each module
75 % of the INF15-1250, 938 kW1,128 A per phase75 % on each module
100 % of the INF15-1250, 1,250 kW1,504 A per phase100 % on each module

Current = kVA × load ÷ (√3 × volts).

Module load = load ÷ the kVA of the power modules fitted.

From the 2026 catalog

What is the INF15-1250?

The code INF15-1250 orders these catalog items:

  • 1 × INF15-FRAME-1500: 1,500 kVA frame, without power modules, 70.9 × 39.4 × 78.7 in (1,800 × 1,000 × 2,000 mm)
  • 10 × INFINITE-PWR-125: 125 kVA hot-swappable power module, 119 lb (54 kg) each
  • Architecture: 10 × 125 kVA hot-swappable power modules in a 1,500 kVA frame.
  • Technology: Silicon-Carbide (SiC) semiconductors; unity power factor; charger up to 1,000 A settable (10 modules × 100 A, 20 A default); parallel up to 8 units.

Its other catalog lines are those of the INF15-1500, built in the same frame: see them on its page.

Size and floor

How big it is

70.9" W × 39.4" D × 78.7" H (1,800 × 1,000 × 2,000 mm); 5,932.6 lb (2,691 kg) net.

19.4 ft²footprint (1.80 m²)
306 lb/ft²floor load of the cabinet alone
Modularform factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

5′9″ FrontSide 70.87″39.37″78.74″

Datasheet

INF15-1250 datasheet.

The INF15-1250 in the AEC 2026 catalog, figure by figure. Compare it with every INFINITE 1.5MW model.

INF15-1250 datasheet
ParameterINF15-1250
Power
Rated power (kVA)1,250
Active power (kW)1,250
Output power factor1.0
Electrical
Input / output480 V three-phase, 3-wire (delta)
TopologyOnline double conversion, modular
Efficiency, up to97.5%
Battery DC bus600 V DC
Battery and runtime
Battery typeVRLA or lithium LiFePO4
Battery configurationExternal battery bank
Mechanical
Form factorModular
Dimensions W × D × H70.9 × 39.4 × 78.7 in (1,800 × 1,000 × 2,000 mm)
Net weight5,932.6 lb (2,691 kg)
Footprint19.4 ft² (1.80 m²)
Common to every INFINITE 1.5MW
Battery, INF15-1250external: 8 AEC L6 lithium cabinets (160 × 50 Ah modules) or lead-acid; 600 Vdc nominal (360–600 V settable, 576–600 V at full load)
CertificationUL 1778 listed, UL file E543003; FCC Part 15 Subpart B, Class A
Technology, display, communications, warrantyAs on the INF15-1500 datasheet

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

INF15-1250: what people ask

What is the output current of the INF15-1250?

1,503.5 A per phase at full load: 1,250 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the INF15-1250 from its installation manual and the local electrical code, not from this figure alone.

How much heat does the INF15-1250 give off?

About 32 kW, 109,360 BTU/h, at full load and the catalog's top efficiency of 97.5%. Plan the room's cooling for a little more than that: the INF15-1250 is less efficient at part load and while its battery recharges.

Will the INF15-1250 fit through a standard door?

Not upright through a standard 36 × 80-inch door, which clears about 34 in: at 39.4 in (1,000 mm) across it needs an opening wider than 39.4 in. Check elevators and the floor load on the way in too.

The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h

INFINITE 1.5MW

Other INFINITE 1.5MW models

The INFINITE 1.5MW series, with pictures

By power, the INF15-1250 is number 3 of 4 in the INFINITE 1.5MW series, which runs from 750 to 1,500 kVA. One size down are the INF15-1000 and INF15-1000+1, all 250 kVA less. One size up is the INF15-1500 (250 kVA more and 238 lb heavier). The same 1,250 kVA also comes as INF15-1250+1 (11 power modules, N+1, 119 lb heavier); the INF15-1250 has external battery bank.

Every INFINITE 1.5MW model side by side (7)
INFINITE 1.5MW models side by side
ModelPowerPower against this modelNet weightWeight against this model
INF15-750750 kVA500 kVA less5,456 lb476 lb lighter
INF15-750+1750 kVA500 kVA less5,576 lb357 lb lighter
INF15-10001,000 kVA250 kVA less5,695 lb238 lb lighter
INF15-1000+11,000 kVA250 kVA less5,814 lb119 lb lighter
INF15-12501,250 kVAthis page5,933 lbthis page
INF15-1250+11,250 kVAthe same power6,052 lb119 lb heavier
INF15-15001,500 kVA250 kVA more6,171 lb238 lb heavier

The INF15-1250 for your project

Send the load, the voltage and the minutes you need from the INF15-1250. We reply with the configuration, the batteries and the lead time.