INFINITE 1.5MW · 480V three-phase UPS

INF15-1500 INFINITE 1.5MW 1,500 kVA, 480V three-phase UPS

Lithium or VRLA1,500 kVAOnline double conversion

The AEC INFINITE 1.5MW INF15-1500 is a 1,500 kVA / 1,500 kW online double-conversion UPS for 480 V three-phase loads, built on 12 × 125 kVA power modules, with 8 external AEC L6 lithium cabinets or a VRLA bank. Kept at 80 % of its rating, it carries loads up to 1,200 kW.

3-wire · Delta480 V 3-wire, delta: three phases and ground, no neutral

1,500 kVA / 1,500 kWRating
70.9 × 39.4 × 78.7 inW × D × H
6,170.7 lbWeight
VRLA or lithium, externalBattery
AEC INF15-1500, rendered from its 3D modelDrag to turn

In 3D

Look around the INF15-1500

Load by load

The INF15-1500 at 25, 50, 75 and 100 % load.

Its 1,500 kW rating in four steps, worked out from its own catalog figures.

At 25, 50, 75 and 100 % load
LoadOutput current per phase, at 480 VLoad on each of its 12 power modules
25 % of the INF15-1500, 375 kW451 A per phase25 % on each module
50 % of the INF15-1500, 750 kW902 A per phase50 % on each module
75 % of the INF15-1500, 1,125 kW1,353 A per phase75 % on each module
100 % of the INF15-1500, 1,500 kW1,804 A per phase100 % on each module

Current = kVA × load ÷ (√3 × volts).

Module load = load ÷ the kVA of the power modules fitted.

From the 2026 catalog

What is the INF15-1500?

The code INF15-1500 orders these catalog items:

  • 1 × INF15-FRAME-1500: 1,500 kVA frame, without power modules, 70.9 × 39.4 × 78.7 in (1,800 × 1,000 × 2,000 mm)
  • 12 × INFINITE-PWR-125: 125 kVA hot-swappable power module, 119 lb (54 kg) each
  • Architecture: 12 × 125 kVA hot-swappable power modules in a 1,500 kVA frame.
  • Technology: Silicon-Carbide (SiC) semiconductors; unity power factor; charger up to 1,200 A settable (12 modules × 100 A, 20 A default); parallel up to 8 units.
  • Battery: external: 8 AEC L6 lithium cabinets (160 × 50 Ah modules) or lead-acid; 600 Vdc nominal (360–600 V settable, 576–600 V at full load).

The lines every INFINITE 1.5MW shares, from technology to warranty, are in the INFINITE 1.5MW key facts and in the datasheet below.

Size and floor

How big it is

70.9" W × 39.4" D × 78.7" H (1,800 × 1,000 × 2,000 mm); 6,170.7 lb (2,799 kg) net.

19.4 ft²footprint (1.80 m²)
318 lb/ft²floor load of the cabinet alone
Modularform factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

5′9″ FrontSide 70.87″39.37″78.74″

Datasheet

INF15-1500 datasheet.

The INF15-1500 in the AEC 2026 catalog, figure by figure. Compare it with every INFINITE 1.5MW model.

INF15-1500 datasheet
ParameterINF15-1500
Power
Rated power (kVA)1,500
Active power (kW)1,500
Output power factor1.0
Electrical
Input / output480 V three-phase, 3-wire (delta)
TopologyOnline double conversion, modular
Efficiency, up to97.5%
Battery DC bus600 V DC
Battery and runtime
Battery typeVRLA or lithium LiFePO4
Battery configurationExternal battery bank
Mechanical
Form factorModular
Dimensions W × D × H70.9 × 39.4 × 78.7 in (1,800 × 1,000 × 2,000 mm)
Net weight6,170.7 lb (2,799 kg)
Footprint19.4 ft² (1.80 m²)
Common to every INFINITE 1.5MW
TechnologySilicon-Carbide (SiC) semiconductors; modular N+1, 125 kVA / 125 kW hot-swappable power modules, up to 12 in one 1,500 kVA frame; unity power factor; charger 100 A per power module, settable (20 A default); parallel up to 8 units
Overload105% continuous, 110% for 60 min, 125% for 10 min, 150% for 1 min
Display7-inch color touchscreen + LED display
CommsRS232, RS485/Modbus RTU, Modbus TCP/IP, BACnet, BMS, EPO and dry contacts standard; SNMP card optional
Battery, INF15-1500external: 8 AEC L6 lithium cabinets (160 × 50 Ah modules) or lead-acid; 600 Vdc nominal (360–600 V settable, 576–600 V at full load)
Cabinet1800 × 1000 × 2,000 mm (W × D × H), the bypass breaker cabinet on the left included; IP20, <78 dB at full load, -5 to 40 °C, up to 2,000 m
CertificationUL 1778 listed, UL file E543003; FCC Part 15 Subpart B, Class A
Uselarge data centers, 750 to 1,500 kVA per frame; INFINITE 100–600 kVA covers smaller sites
Network cardSNMP-L (SNMP)
Warranty3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries
Quality systemISO 9001:2015, the group's quality system (SGS)

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

INF15-1500: what people ask

What is the output current of the INF15-1500?

1,804.2 A per phase at full load: 1,500 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the INF15-1500 from its installation manual and the local electrical code, not from this figure alone.

How much heat does the INF15-1500 give off?

About 38 kW, 131,230 BTU/h, at full load and the catalog's top efficiency of 97.5%. Plan the room's cooling for a little more than that: the INF15-1500 is less efficient at part load and while its battery recharges.

Will the INF15-1500 fit through a standard door?

Not upright through a standard 36 × 80-inch door, which clears about 34 in: at 39.4 in (1,000 mm) across it needs an opening wider than 39.4 in. Check elevators and the floor load on the way in too.

The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h

INFINITE 1.5MW

Other INFINITE 1.5MW models

The INFINITE 1.5MW series, with pictures

By power, the INF15-1500 is the largest in the INFINITE 1.5MW series, which runs from 750 to 1,500 kVA. One size down are the INF15-1250 and INF15-1250+1, all 250 kVA less.

Every INFINITE 1.5MW model side by side (7)
INFINITE 1.5MW models side by side
ModelPowerPower against this modelNet weightWeight against this model
INF15-750750 kVA750 kVA less5,456 lb714 lb lighter
INF15-750+1750 kVA750 kVA less5,576 lb595 lb lighter
INF15-10001,000 kVA500 kVA less5,695 lb476 lb lighter
INF15-1000+11,000 kVA500 kVA less5,814 lb357 lb lighter
INF15-12501,250 kVA250 kVA less5,933 lb238 lb lighter
INF15-1250+11,250 kVA250 kVA less6,052 lb119 lb lighter
INF15-15001,500 kVAthis page6,171 lbthis page

The INF15-1500 for your project

Send the load, the voltage and the minutes you need from the INF15-1500. We reply with the configuration, the batteries and the lead time.