INFINITE 1.5MW · 480V three-phase UPS
INF15-750 INFINITE 1.5MW 750 kVA, 480V three-phase UPS
The AEC INFINITE 1.5MW INF15-750 is a 750 kVA / 750 kW online double-conversion UPS for 480 V three-phase loads, built on six 125 kVA power modules, with 4, 6 or 8 external AEC L6 lithium cabinets or a VRLA bank. Kept at 80 % of its rating, it carries loads up to 600 kW.
3-wire · Delta480 V 3-wire, delta: three phases and ground, no neutral
Drag to turnThe same on every INFINITE 1.5MW:The INFINITE 1.5MW display
Load by load
The INF15-750 at 25, 50, 75 and 100 % load.
Its 750 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current per phase, at 480 V | Load on each of its 6 power modules |
|---|---|---|
| 25 % of the INF15-750, 188 kW | 226 A per phase | 25 % on each module |
| 50 % of the INF15-750, 375 kW | 451 A per phase | 50 % on each module |
| 75 % of the INF15-750, 563 kW | 677 A per phase | 75 % on each module |
| 100 % of the INF15-750, 750 kW | 902 A per phase | 100 % on each module |
Current = kVA × load ÷ (√3 × volts).
Module load = load ÷ the kVA of the power modules fitted.
From the 2026 catalog
What is the INF15-750?
The code INF15-750 orders these catalog items:
- 1 × INF15-FRAME-1500: 1,500 kVA frame, without power modules, 70.9 × 39.4 × 78.7 in (1,800 × 1,000 × 2,000 mm)
- 6 × INFINITE-PWR-125: 125 kVA hot-swappable power module, 119 lb (54 kg) each
- Architecture: 6 × 125 kVA hot-swappable power modules in a 1,500 kVA frame.
- Technology: Silicon-Carbide (SiC) semiconductors; unity power factor; charger up to 600 A settable (6 modules × 100 A, 20 A default); parallel up to 8 units.
- Battery: external: 4, 6 or 8 AEC L6 lithium cabinets (80, 120 or 160 × 50 Ah modules) or lead-acid; 600 Vdc nominal (360–600 V settable, 576–600 V at full load).
Its other catalog lines are those of the INF15-1500, built in the same frame: see them on its page.
Size and floor
How big it is
70.9" W × 39.4" D × 78.7" H (1,800 × 1,000 × 2,000 mm); 5,456.4 lb (2,475 kg) net.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Datasheet
INF15-750 datasheet.
The INF15-750 in the AEC 2026 catalog, figure by figure. Compare it with every INFINITE 1.5MW model.
| Parameter | INF15-750 |
|---|---|
| Power | |
| Rated power (kVA) | 750 |
| Active power (kW) | 750 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 480 V three-phase, 3-wire (delta) |
| Topology | Online double conversion, modular |
| Efficiency, up to | 97.5% |
| Battery DC bus | 600 V DC |
| Battery and runtime | |
| Battery type | VRLA or lithium LiFePO4 |
| Battery configuration | External battery bank |
| Mechanical | |
| Form factor | Modular |
| Dimensions W × D × H | 70.9 × 39.4 × 78.7 in (1,800 × 1,000 × 2,000 mm) |
| Net weight | 5,456.4 lb (2,475 kg) |
| Footprint | 19.4 ft² (1.80 m²) |
| Common to every INFINITE 1.5MW | |
| Battery, INF15-750 | external: 4, 6 or 8 AEC L6 lithium cabinets (80, 120 or 160 × 50 Ah modules) or lead-acid; 600 Vdc nominal (360–600 V settable, 576–600 V at full load) |
| Certification | UL 1778 listed, UL file E543003; FCC Part 15 Subpart B, Class A |
| Technology, display, communications, warranty | As on the INF15-1500 datasheet |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
The INFINITE 1.5MW manuals and catalogs cover every model of the series, this one included: download them from the INFINITE 1.5MW page.
Quick answers
INF15-750: what people ask
What is the output current of the INF15-750?
902.1 A per phase at full load: 750 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the INF15-750 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the INF15-750 give off?
About 19 kW, 65,620 BTU/h, at full load and the catalog's top efficiency of 97.5%. Plan the room's cooling for a little more than that: the INF15-750 is less efficient at part load and while its battery recharges.
Will the INF15-750 fit through a standard door?
Not upright through a standard 36 × 80-inch door, which clears about 34 in: at 39.4 in (1,000 mm) across it needs an opening wider than 39.4 in. Check elevators and the floor load on the way in too.
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
INFINITE 1.5MW
Other INFINITE 1.5MW models
By power, the INF15-750 is the smallest in the INFINITE 1.5MW series, which runs from 750 to 1,500 kVA. One size up are the INF15-1000 and INF15-1000+1, all 250 kVA more. The same 750 kVA also comes as INF15-750+1 (seven power modules, N+1, 119 lb heavier); the INF15-750 has external battery bank.
Every INFINITE 1.5MW model side by side (7)
| Model | Power | Power against this model | Net weight | Weight against this model |
|---|---|---|---|---|
| INF15-750 | 750 kVA | this page | 5,456 lb | this page |
| INF15-750+1 | 750 kVA | the same power | 5,576 lb | 119 lb heavier |
| INF15-1000 | 1,000 kVA | 250 kVA more | 5,695 lb | 238 lb heavier |
| INF15-1000+1 | 1,000 kVA | 250 kVA more | 5,814 lb | 357 lb heavier |
| INF15-1250 | 1,250 kVA | 500 kVA more | 5,933 lb | 476 lb heavier |
| INF15-1250+1 | 1,250 kVA | 500 kVA more | 6,052 lb | 595 lb heavier |
| INF15-1500 | 1,500 kVA | 750 kVA more | 6,171 lb | 714 lb heavier |
Install and run it:INFINITE operating guideL6 lithium cabinet guide
The INF15-750 for your project
Send the load, the voltage and the minutes you need from the INF15-750. We reply with the configuration, the batteries and the lead time.