LUMINA · 120V single-phase UPS
LUM1500RT-2U-LI LUMINA 1.5 kVA, 120V single-phase UPS
The AEC LUMINA LUM1500RT-2U-LI is a 1.5 kVA / 1.35 kW online double-conversion UPS for 120 V single-phase loads, with internal LiFePO4 lithium batteries: 11 minutes at full load, 27 at half load by AEC's estimate. Kept at 80 % of its rating, it carries loads up to 1.1 kW.
Drag to turnThe same on every LUMINA:The LUMINA display
Runtime
LUMINA 1.5 kVA · LiFePO4 inside at your load.
The same chart as the LUMINA page: this model in bold, the other set-ups faded behind it to compare. This model's full-load minutes are published; its other points are an AEC estimate. The others are the 2026 catalog's, new batteries.
At 50 % of the rating
LUMINA 1.5 kVA
This model LiFePO4 inside27 minLUMINA 1 kVA
LiFePO4 inside27 minLUMINA 2 kVA
LiFePO4 inside27 minLUMINA 2.2 kVA
LiFePO4, extended runtime46 minLUMINA 3 kVA
LiFePO4 inside27 minTable: this model at 25, 50, 75 and 100 % load
| Model | 25% load | 50% load | 75% load | 100% load |
|---|---|---|---|---|
| LUMINA 1.5 kVA · LiFePO4 insideLUM1500RT-2U-LI | 55 min | 27 min | 19 min | 11 min |
Load by load
The LUM1500RT-2U-LI at 25, 50, 75 and 100 % load.
Its 1.4 kW rating in four steps, worked out from its own catalog figures.
| Load | On battery | Output current, at 120 V | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|---|
| 25 % of the LUM1500RT-2U-LI, 338 W | 55 min on battery | 3.1 A at the output | 89.1 % efficient | 41 W of heat | 140 BTU/h to cool |
| 50 % of the LUM1500RT-2U-LI, 675 W | 27 min on battery | 6.3 A at the output | 92.1 % efficient | 58 W of heat | 200 BTU/h to cool |
| 75 % of the LUM1500RT-2U-LI, 1.0 kW | 19 min on battery | 9.4 A at the output | 92.5 % efficient | 82 W of heat | 280 BTU/h to cool |
| 100 % of the LUM1500RT-2U-LI, 1.4 kW | 11 min on battery | 12.5 A at the output | 92.4 % efficient | 111 W of heat | 380 BTU/h to cool |
Current = kVA × load ÷ volts.
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Runtime from the catalog's table, with new batteries; between its points, read on a straight line.
Efficiency
How efficient is the LUM1500RT-2U-LI at your load?
The LUM1500RT-2U-LI in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
Sizing
What load fits the LUM1500RT-2U-LI?
At 80 % load the LUM1500RT-2U-LI's runtime table gives about 17 min on battery, with new batteries.
At 0.7 kW, half its rating, it runs 27 min.
At the same 0.7 kW, the other LUMINA models:
- LUM1000RT-2U-LI: 19 min on battery, at 75 % of its rating.
- LUM2000RT-2U-LI: 35.5 min on battery, at 38 % of its rating.
From the 2026 catalog
What is the LUM1500RT-2U-LI?
- Output: 1,500 VA / 1,350 W (power factor 0.9).
- Input: IEC C14 inlet, power cord with NEMA 5-15P plug supplied; max. input current 17.5 A.
- Battery: internal LiFePO4 lithium, 10.2 Ah · 489.6 Wh — 11 min at full load, against 6 min for the VRLA FERRUS RT of the same kVA, each at its own full load, 12–15 year life (3,000 cycles).
- Efficiency: up to 92.5%.
- Outlets: 6× NEMA 5-15R; max. total output current 13.7 A.
The lines every LUMINA shares, from technology to warranty, are in the LUMINA key facts and in the datasheet below.
Size and floor
How big it is
17.2" W × 22.6" D × 3.4" H (437 × 574 × 86 mm); 32.4 lb (14.7 kg) net.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
The LUM1500RT-2U-LI takes the clearances, wiring, cable entry and breakers of every LUMINA model, from its AEC US user manual: see them on the LUMINA page.
Place the LUM1500RT-2U-LI in your room, to the inch, with Room fit
What is what
Inside the LUMINA, part by part.
Each number on the picture is named in the list.
Rear · 1 kVA
12345678- Intelligent slotFor an SNMP network card or a dry-contact card; the -NC models ship with the SNMP card fitted.
- Cooling fanOne fan on the 1 kVA; the air leaves at the rear.
- EPOEmergency power off contact.
- USB portTo a computer, for the monitoring and shutdown software.
- Circuit protectorThe input breaker: press it to reset after an overload.
- Input: C14 inletIEC C14 inlet for the supply cord.
- 8 × NEMA 5-15R outletsThe protected outputs, 120 V.
- Battery connectorDC input of the internal battery.
Rear · 1.5–2.2 kVA
12345678- Intelligent slotFor an SNMP network card or a dry-contact card; the -NC models ship with the SNMP card fitted.
- Two cooling fansTwo fans on the 1.5, 2, 2.2 and 3 kVA; the air leaves at the rear.
- EPOEmergency power off contact.
- USB portTo a computer, for the monitoring and shutdown software.
- Circuit protectorThe input breaker: press it to reset after an overload.
- Input: C20 inlet + 5 ft cordIEC C20 inlet; the 5 ft supply cord plugs in with its C19 connector.
- 6 × NEMA 5-20R outletsThe protected outputs, 120 V, 20 A receptacles.
- Battery connectorDC input of the internal battery.
Rear · 3 kVA
123456789- Intelligent slotFor an SNMP network card or a dry-contact card; the -NC models ship with the SNMP card fitted.
- Two cooling fansTwo fans on the 1.5, 2, 2.2 and 3 kVA; the air leaves at the rear.
- EPOEmergency power off contact.
- USB portTo a computer, for the monitoring and shutdown software.
- Circuit protectorThe input breaker: press it to reset after an overload.
- Input: NEMA L5-30P plugLocking 30 A plug on a 5 ft cord.
- 1 × NEMA L5-30R outletA locking 30 A output for the larger load.
- 4 × NEMA 5-20R outletsThe protected outputs, 120 V, 20 A receptacles.
- Battery connectorDC input of the internal battery.
Datasheet
LUM1500RT-2U-LI datasheet.
The LUM1500RT-2U-LI in the AEC 2026 catalog, figure by figure. Compare it with every LUMINA model.
| Parameter | LUM1500RT-2U-LI |
|---|---|
| Power | |
| Rated power (kVA) | 1.5 |
| Active power (kW) | 1.35 |
| Output power factor | 0.9 |
| Electrical | |
| Input / output | 120 V single-phase |
| Topology | Online Double Conversion |
| Efficiency, up to | 92.5% |
| Battery DC bus | 48 V DC |
| Battery and runtime | |
| Battery type | Lithium LiFePO4 |
| Battery configuration | Internal |
| Runtime at 50 % load | 27 min, AEC estimate |
| Runtime at 100 % load | 11 min |
| Mechanical | |
| Form factor | Rack 2U |
| Dimensions W × D × H | 17.2 × 22.6 × 3.4 in (437 × 574 × 86 mm) |
| Net weight | 32.4 lb (14.7 kg) |
| Footprint | 2.7 ft² (0.25 m²) |
| Common to every LUMINA | |
| Battery, LUM1500RT-2U-LI | internal LiFePO4 lithium, 10.2 Ah · 489.6 Wh — 11 min at full load, against 6 min for the VRLA FERRUS RT of the same kVA, each at its own full load, 12–15 year life (3,000 cycles) |
| Display | rotating color LCD |
| Comms | RS-232, EPO and USB, standard |
| Form factor | 2U rack; telescopic rail kit available |
| Network card | SNMP-L (SNMP) |
| Warranty | 5 years incl. lithium batteries |
| Certification | ETL Listed to UL 1778 and CSA C22.2 No. 107.3 |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The LUMINA documents cover every model of the series, this one included. PDF, in English.
Quick answers
LUM1500RT-2U-LI: what people ask
How long does the LUM1500RT-2U-LI run on battery?
11 min at 100 % load (1.4 kW), 27 min at 50 % load (675 W), 2 h 5 min at 10 % load (135 W), at the start of battery life: the full-load figure published, the other points an AEC estimate. Runtime falls faster than the load rises, so the LUM1500RT-2U-LI chart above gives the minutes at any load in between.
What is the output current of the LUM1500RT-2U-LI?
12.5 A at 120 V at full load: 1.5 kVA ÷ 120 V. Size the input breaker and the cables of the LUM1500RT-2U-LI from its installation manual and the local electrical code, not from this figure alone.
How much heat does the LUM1500RT-2U-LI give off?
About 111 W, 380 BTU/h, at full load, where it is 92.4% efficient. Plan the room's cooling for a little more than that: the LUM1500RT-2U-LI is less efficient at part load and while its battery recharges.
How many rack units does the LUM1500RT-2U-LI take?
2U of a 19-inch rack: 3.4 in high, 22.6 in deep. Check the rack's usable depth, rails and rear clearance for the cables.
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
LUMINA
Other LUMINA models
By power, the LUM1500RT-2U-LI is number 2 of 5 in the LUMINA series, which runs from 1 to 3 kVA. One size down is the LUM1000RT-2U-LI (0.5 kVA less and 13 lb lighter). One size up is the LUM2000RT-2U-LI (0.5 kVA more and 2 lb lighter).
Every LUMINA model side by side (5)
| Model | Power | Power against this model | Net weight | Weight against this model | Runtime at 50 % load |
|---|---|---|---|---|---|
| LUM1000RT-2U-LI | 1 kVA | 0.5 kVA less | 20 lb | 13 lb lighter | 27 min at 50 % load |
| LUM1500RT-2U-LI | 1.5 kVA | this page | 32 lb | this page | 27 min at 50 % load, AEC estimate |
| LUM2000RT-2U-LI | 2 kVA | 0.5 kVA more | 30 lb | 2 lb lighter | 27 min at 50 % load |
| LUM2200RT-2U-LI | 2.2 kVA | 0.7 kVA more | 42 lb | 10 lb heavier | 46 min at 50 % load |
| LUM3000RT-2U-LI | 3 kVA | 1.5 kVA more | 38 lb | 5 lb heavier | 27 min at 50 % load |
Install and run it:LUMINA operating guide
The LUM1500RT-2U-LI for your project
Send the load, the voltage and the minutes you need from the LUM1500RT-2U-LI. We reply with the configuration, the batteries and the lead time.