LUMINA · 120V single-phase UPS
LUM2200RT-2U-LI LUMINA 2.2 kVA, 120V single-phase UPS
The AEC LUMINA LUM2200RT-2U-LI is a 2.2 kVA / 1.98 kW online double-conversion UPS for 120 V single-phase loads, with internal LiFePO4 lithium batteries: 23 minutes at full load, 46 at half load. Kept at 80 % of its rating, it carries loads up to 1.6 kW.
Drag to turnThe same on every LUMINA:The LUMINA display
Runtime
LUMINA 2.2 kVA · LiFePO4, extended runtime at your load.
The same chart as the LUMINA page: this model in bold, the other set-ups faded behind it to compare. 2026 catalog, new batteries.
At 50 % of the rating
LUMINA 2.2 kVA
This model LiFePO4, extended runtime46 minLUMINA 1 kVA
LiFePO4 inside27 minLUMINA 1.5 kVA
LiFePO4 inside27 minLUMINA 2 kVA
LiFePO4 inside27 minLUMINA 3 kVA
LiFePO4 inside27 minTable: this model at 25, 50, 75 and 100 % load
| Model | 25% load | 50% load | 75% load | 100% load |
|---|---|---|---|---|
| LUMINA 2.2 kVA · LiFePO4, extended runtimeLUM2200RT-2U-LI | 98 min | 46 min | 34.5 min | 23 min |
Load by load
The LUM2200RT-2U-LI at 25, 50, 75 and 100 % load.
Its 2.0 kW rating in four steps, worked out from its own catalog figures.
| Load | On battery | Output current, at 120 V | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|---|
| 25 % of the LUM2200RT-2U-LI, 495 W | 98 min on battery | 4.6 A at the output | 89.1 % efficient | 61 W of heat | 210 BTU/h to cool |
| 50 % of the LUM2200RT-2U-LI, 990 W | 46 min on battery | 9.2 A at the output | 92.1 % efficient | 85 W of heat | 290 BTU/h to cool |
| 75 % of the LUM2200RT-2U-LI, 1.5 kW | 34.5 min on battery | 13.8 A at the output | 92.6 % efficient | 119 W of heat | 400 BTU/h to cool |
| 100 % of the LUM2200RT-2U-LI, 2.0 kW | 23 min on battery | 18.3 A at the output | 92.4 % efficient | 163 W of heat | 560 BTU/h to cool |
Current = kVA × load ÷ volts.
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Runtime from the catalog's table, with new batteries; between its points, read on a straight line.
Efficiency
How efficient is the LUM2200RT-2U-LI at your load?
The LUM2200RT-2U-LI in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
Sizing
What load fits the LUM2200RT-2U-LI?
At 80 % load the LUM2200RT-2U-LI's runtime table gives about 32 min on battery, with new batteries.
At 1 kW, half its rating, it runs 46 min.
At the same 1 kW, the other LUMINA models:
- LUM2000RT-2U-LI: 25.5 min on battery, at 55 % of its rating.
- LUM3000RT-2U-LI: 36.3 min on battery, at 37 % of its rating.
From the 2026 catalog
What is the LUM2200RT-2U-LI?
- Output: 2,200 VA / 1,980 W (power factor 0.9).
- Input: IEC C20 inlet, power cord with NEMA 5-20P plug supplied.
- Battery: internal LiFePO4 lithium, 13.6 Ah · 979.2 Wh — 23 min at full load, 12–15 year life (3,000 cycles).
- Efficiency: up to 92.6%.
- Outlets: 6× NEMA 5-20R.
The lines every LUMINA shares, from technology to warranty, are in the LUMINA key facts and in the datasheet below.
Size and floor
How big it is
17.2" W × 24.2" D × 3.4" H (438 × 615 × 87 mm); 42.1 lb (19.1 kg) net. It ships in one carton of 21.5 × 29.5 × 9.6 in, 57.1 lb (25.9 kg) gross.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
The LUM2200RT-2U-LI takes the clearances, wiring, cable entry and breakers of every LUMINA model, from its AEC US user manual: see them on the LUMINA page.
Place the LUM2200RT-2U-LI in your room, to the inch, with Room fit
What is what
Inside the LUMINA, part by part.
Each number on the picture is named in the list.
Rear · 1 kVA
12345678- Intelligent slotFor an SNMP network card or a dry-contact card; the -NC models ship with the SNMP card fitted.
- Cooling fanOne fan on the 1 kVA; the air leaves at the rear.
- EPOEmergency power off contact.
- USB portTo a computer, for the monitoring and shutdown software.
- Circuit protectorThe input breaker: press it to reset after an overload.
- Input: C14 inletIEC C14 inlet for the supply cord.
- 8 × NEMA 5-15R outletsThe protected outputs, 120 V.
- Battery connectorDC input of the internal battery.
Rear · 1.5–2.2 kVA
12345678- Intelligent slotFor an SNMP network card or a dry-contact card; the -NC models ship with the SNMP card fitted.
- Two cooling fansTwo fans on the 1.5, 2, 2.2 and 3 kVA; the air leaves at the rear.
- EPOEmergency power off contact.
- USB portTo a computer, for the monitoring and shutdown software.
- Circuit protectorThe input breaker: press it to reset after an overload.
- Input: C20 inlet + 5 ft cordIEC C20 inlet; the 5 ft supply cord plugs in with its C19 connector.
- 6 × NEMA 5-20R outletsThe protected outputs, 120 V, 20 A receptacles.
- Battery connectorDC input of the internal battery.
Rear · 3 kVA
123456789- Intelligent slotFor an SNMP network card or a dry-contact card; the -NC models ship with the SNMP card fitted.
- Two cooling fansTwo fans on the 1.5, 2, 2.2 and 3 kVA; the air leaves at the rear.
- EPOEmergency power off contact.
- USB portTo a computer, for the monitoring and shutdown software.
- Circuit protectorThe input breaker: press it to reset after an overload.
- Input: NEMA L5-30P plugLocking 30 A plug on a 5 ft cord.
- 1 × NEMA L5-30R outletA locking 30 A output for the larger load.
- 4 × NEMA 5-20R outletsThe protected outputs, 120 V, 20 A receptacles.
- Battery connectorDC input of the internal battery.
Datasheet
LUM2200RT-2U-LI datasheet.
The LUM2200RT-2U-LI in the AEC 2026 catalog, figure by figure. Compare it with every LUMINA model.
| Parameter | LUM2200RT-2U-LI |
|---|---|
| Power | |
| Rated power (kVA) | 2.2 |
| Active power (kW) | 1.98 |
| Output power factor | 0.9 |
| Electrical | |
| Input / output | 120 V single-phase |
| Topology | Online Double Conversion |
| Efficiency, up to | 92.6% |
| Battery DC bus | 72 V DC |
| Battery and runtime | |
| Battery type | Lithium LiFePO4 |
| Battery configuration | Internal |
| Runtime at 50 % load | 46 min |
| Runtime at 100 % load | 23 min |
| Mechanical | |
| Form factor | Rack 2U |
| Dimensions W × D × H | 17.2 × 24.2 × 3.4 in (438 × 615 × 87 mm) |
| Net weight | 42.1 lb (19.1 kg) |
| Footprint | 2.9 ft² (0.27 m²) |
| Shipping | |
| Cartons | 1 |
| Shipping weight | 57.1 lb |
| Common to every LUMINA | |
| Battery, LUM2200RT-2U-LI | internal LiFePO4 lithium, 13.6 Ah · 979.2 Wh — 23 min at full load, 12–15 year life (3,000 cycles) |
| Display | rotating color LCD |
| Comms | RS-232, EPO and USB, standard |
| Form factor | 2U rack; telescopic rail kit available |
| Network card | SNMP-L (SNMP) |
| Warranty | 5 years incl. lithium batteries |
| Certification | ETL Listed to UL 1778 and CSA C22.2 No. 107.3 |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The LUMINA documents cover every model of the series, this one included. PDF, in English.
Quick answers
LUM2200RT-2U-LI: what people ask
How long does the LUM2200RT-2U-LI run on battery?
23 min at 100 % load (2.0 kW), 46 min at 50 % load (990 W), 3 h 56 min at 10 % load (198 W), from the catalog runtime table at the start of battery life. Runtime falls faster than the load rises, so the LUM2200RT-2U-LI chart above gives the minutes at any load in between.
What is the output current of the LUM2200RT-2U-LI?
18.3 A at 120 V at full load: 2.2 kVA ÷ 120 V. Size the input breaker and the cables of the LUM2200RT-2U-LI from its installation manual and the local electrical code, not from this figure alone.
How much heat does the LUM2200RT-2U-LI give off?
About 163 W, 560 BTU/h, at full load, where it is 92.4% efficient. Plan the room's cooling for a little more than that: the LUM2200RT-2U-LI is less efficient at part load and while its battery recharges.
How many rack units does the LUM2200RT-2U-LI take?
2U of a 19-inch rack: 3.4 in high, 24.2 in deep. Check the rack's usable depth, rails and rear clearance for the cables.
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
LUMINA
Other LUMINA models
By power, the LUM2200RT-2U-LI is number 4 of 5 in the LUMINA series, which runs from 1 to 3 kVA. One size down is the LUM2000RT-2U-LI (0.2 kVA less and 12 lb lighter). One size up is the LUM3000RT-2U-LI (0.8 kVA more and 4 lb lighter).
Every LUMINA model side by side (5)
| Model | Power | Power against this model | Net weight | Weight against this model | Runtime at 50 % load |
|---|---|---|---|---|---|
| LUM1000RT-2U-LI | 1 kVA | 1.2 kVA less | 20 lb | 23 lb lighter | 27 min at 50 % load |
| LUM1500RT-2U-LI | 1.5 kVA | 0.7 kVA less | 32 lb | 10 lb lighter | 27 min at 50 % load, AEC estimate |
| LUM2000RT-2U-LI | 2 kVA | 0.2 kVA less | 30 lb | 12 lb lighter | 27 min at 50 % load |
| LUM2200RT-2U-LI | 2.2 kVA | this page | 42 lb | this page | 46 min at 50 % load |
| LUM3000RT-2U-LI | 3 kVA | 0.8 kVA more | 38 lb | 4 lb lighter | 27 min at 50 % load |
Install and run it:LUMINA operating guide
The LUM2200RT-2U-LI for your project
Send the load, the voltage and the minutes you need from the LUM2200RT-2U-LI. We reply with the configuration, the batteries and the lead time.