RADIANT-IB · 208 V three-phase UPS
RADIB100 RADIANT-IB 100 kVA frame, 20–100 kVA fitted
The AEC RADIANT-IB RADIB100 is a 100 kVA modular UPS frame for 208 V three-phase loads with five slots for 20 kVA hot-swappable power modules. The 2026 catalog lists it with 1, 2, 3, 4 or 5 modules fitted, 20–100 kVA in all; each code is a row below.
Series picture.
5 ordering codes
Which RADIB100 do you need?
One 100 kVA frame, a row per number of modules fitted. Only what changes from one code to the next is here; what they share is under the table.
| Ordering code | Power | Free slots | With one module spare (N+1) | Net weight | Floor load | Current per phase at 208 V | Cartons |
|---|---|---|---|---|---|---|---|
| RADIB100-1X201 × 20 kVA power module3DAsk | 20 kVA / 20 kW | 4 of 5 | no spare with one module | 1,998 lb (906.3 kg) | 310 lb/ft² | 55.5 A | 26 |
| RADIB100-2X202 × 20 kVA power modules3DAsk | 40 kVA / 40 kW | 3 of 5 | 20 kVA | 2,042 lb (926.2 kg) | 317 lb/ft² | 111 A | 27 |
| RADIB100-3X203 × 20 kVA power modules3DAsk | 60 kVA / 60 kW | 2 of 5 | 40 kVA | 2,086 lb (946.2 kg) | 324 lb/ft² | 167 A | 28 |
| RADIB100-4X204 × 20 kVA power modules3DAsk | 80 kVA / 80 kW | 1 of 5 | 60 kVA | 2,130 lb (966.2 kg) | 331 lb/ft² | 222 A | 29 |
| RADIB100-5X205 × 20 kVA power modules3DAsk | 100 kVA / 100 kW | none of 5 | 80 kVA | 2,174 lb (986.1 kg) | 338 lb/ft² | 278 A | 30 |
This model
What sets the RADIB100 apart
The RADIANT-IB is a 100 kVA frame for 208 V three-phase that carries its own batteries: five slots for 20 kVA power modules and 240 blocks of 12 V 9 Ah on internal trays, in one 23.6 × 39.3 × 78.7 in cabinet. The catalog lists it with one to five modules, 20 to 100 kVA.
With its blocks it weighs 1,998 lb (906.3 kg) at 20 kVA and 2,174 lb (986.1 kg) at 100 kVA, 310 to 338 lb/ft² on 6.4 ft²: check the floor rating before it is placed. Each module adds 44 lb and 55.5 A per phase at full load. It is the 208 V counterpart of the CIRRO-IB.
Drag to turnThe same on every RADIANT-IB:The RADIANT-IB display
Efficiency
How efficient is the RADIB100-5X20 at your load?
The RADIB100-5X20 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What every RADIB100 code shares
- Each 20 kVA power module, RADIB-PWR-20: 44 lb (20 kg), hot-swappable
- Technology: 3-level IGBT; unity power factor (kVA = kW); 40 A settable charger.
- Input / Output: 208/120 V three-phase.
- Battery: internal hot-swappable VRLA, up to 240 × 12 V 9 Ah blocks.
- Efficiency: up to 94%.
- Display: 7-inch color touchscreen.
- Comms: RS-232, EPO and USB, standard.
- Warranty: 3 years on UPS · 2 years on VRLA batteries.
- Cabinet: 23.6" W × 39.3" D × 78.7" H (599 × 998 × 1,999 mm), the same for every code above
The lines every RADIANT-IB shares, from technology to warranty, are in the RADIANT-IB key facts.
Size and floor
How big it is
23.6" W × 39.3" D × 78.7" H (599 × 998 × 1,999 mm); from 1,998 lb (906.3 kg) to 2,174 lb (986.1 kg) net, code by code.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
The RADIB100 takes the clearances, wiring, cable entry and breakers of every RADIANT-IB model, from its AEC US user manual: see them on the RADIANT-IB page.
Datasheet
RADIB100 datasheet, code by code.
Every figure of the 5 codes in the AEC 2026 catalog. Compare them with every RADIANT-IB model.
| Model | RADIB100-1X20 | RADIB100-2X20 | RADIB100-3X20 | RADIB100-4X20 | RADIB100-5X20 |
|---|---|---|---|---|---|
| Power | |||||
| Rated power (kVA) | 20 | 40 | 60 | 80 | 100 |
| Active power (kW) | 20 | 40 | 60 | 80 | 100 |
| Output power factor | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
| Electrical | |||||
| Input / output | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) | 208 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X | Online double conversion, modular N+X | Online double conversion, modular N+X | Online double conversion, modular N+X | Online double conversion, modular N+X |
| Efficiency, up to | 94% | 94% | 94% | 94% | 94% |
| Battery DC bus | 240 V DC | 240 V DC | 240 V DC | 240 V DC | 240 V DC |
| Battery and runtime | |||||
| Battery type | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) | VRLA (sealed lead-acid) |
| Battery configuration | Internal Tray System | Internal Tray System | Internal Tray System | Internal Tray System | Internal Tray System |
| Runtime at 50% load | 85 min | 32 min | 21.5 min | 14 min | 12 min |
| Runtime at 100% load | 32 min | 14 min | 8 min | 6 min | 3 min |
| Mechanical | |||||
| Form factor | Modular | Modular | Modular | Modular | Modular |
| Dimensions W × D × H | 23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm) | 23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm) | 23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm) | 23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm) | 23.6 × 39.3 × 78.7 in (599 × 998 × 1,999 mm) |
| Net weight | 1,998 lb (906.3 kg) | 2,042 lb (926.2 kg) | 2,086 lb (946.2 kg) | 2,130 lb (966.2 kg) | 2,174 lb (986.1 kg) |
| Footprint | 6.4 ft² (0.60 m²) | 6.4 ft² (0.60 m²) | 6.4 ft² (0.60 m²) | 6.4 ft² (0.60 m²) | 6.4 ft² (0.60 m²) |
| Shipping | |||||
| Cartons | 26 | 27 | 28 | 29 | 30 |
From the AEC 2026 catalog. Efficiency is the catalog's “up to” figure; runtimes are AEC's runtime tables with new batteries; weights are the unit alone, without batteries outside it. Figures may change; the order confirmation governs.
Downloads
The RADIANT-IB manuals and catalogs cover every model of the series, these codes included: download them from the RADIANT-IB page.
RADIANT-IB
Other RADIANT-IB models
The RADIANT-IB has this one model page; its datasheet sets every code side by side.
The RADIB100 for your project
Send the load, the voltage and the minutes you need from the RADIB100. We reply with the code, the batteries and the lead time.