RADIANT · 208V three-phase UPS
RAD90-5X15 RADIANT 75 kVA, 208V three-phase UPS
The AEC RADIANT RAD90-5X15 is a 75 kVA / 75 kW online double-conversion UPS for 208 V three-phase loads, built on five 15 kVA power modules, with external battery cabinets. Kept at 80 % of its rating, it carries loads up to 60 kW.
Five of the frame's six module slots are fitted and one is free; with one module held as a spare (N+1) it carries 60 kVA. As configured it weighs 360 lb (163.4 kg) net.
Series picture.
Drag to turnIn 3D
Look around the RAD90-5X15
The turntable shows the 90 kVA · 6 modules configuration; the full 3D view opens on this model.
The same on every RADIANT:The RADIANT display
Load by load
The RAD90-5X15 at 25, 50, 75 and 100 % load.
Its 75 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current per phase, at 208 V | Load on each of its 5 power modules | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|---|
| 25 % of the RAD90-5X15, 19 kW | 52.0 A per phase | 25 % on each module | 92.8 % efficient | 1.5 kW of heat | 4,960 BTU/h to cool |
| 50 % of the RAD90-5X15, 38 kW | 104 A per phase | 50 % on each module | 93.9 % efficient | 2.4 kW of heat | 8,310 BTU/h to cool |
| 75 % of the RAD90-5X15, 56 kW | 156 A per phase | 75 % on each module | 94.0 % efficient | 3.6 kW of heat | 12,250 BTU/h to cool |
| 100 % of the RAD90-5X15, 75 kW | 208 A per phase | 100 % on each module | 93.8 % efficient | 5.0 kW of heat | 16,910 BTU/h to cool |
Current = kVA × load ÷ (√3 × volts).
Module load = load ÷ the kVA of the power modules fitted.
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the RAD90-5X15 at your load?
The RAD90-5X15 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What is the RAD90-5X15?
The code RAD90-5X15 orders these catalog items:
- 1 × RAD90-FRAME: 90 kVA frame, without power modules, 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm)
- 5 × RAD-PWR-15: 15 kVA hot-swappable power module, 30.5 lb (13.9 kg) each
- Architecture: 5 × 15 kVA hot-swappable power modules in a 90 kVA / 90 kW frame, 6 slots with 4 breakers (scalable to 6 modules / 90 kVA); parallel up to 4 frames.
The lines every RADIANT shares, from technology to warranty, are in the RADIANT key facts and in the datasheet below.
5 × 15 kVA power modules fitted in a 6-slot frame: 1 free slot to grow or add redundancy.
Size and floor
How big it is
17.4" W × 33.1" D × 59.4" H (442 × 840 × 1,510 mm); 360 lb (163.4 kg) net.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
The RAD90-5X15 takes the clearances, wiring, cable entry and breakers of every RADIANT model, from its AEC US user manual: see them on the RADIANT page.
Place the RAD90-5X15 in your room, to the inch, with Room fit
Datasheet
RAD90-5X15 datasheet.
The RAD90-5X15 in the AEC 2026 catalog, figure by figure. Compare it with every RADIANT model.
| Parameter | RAD90-5X15 |
|---|---|
| Power | |
| Rated power (kVA) | 75 |
| Active power (kW) | 75 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 208 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X |
| Efficiency, up to | 94% |
| Battery DC bus | 240 V DC |
| Battery and runtime | |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | External battery bank |
| Mechanical | |
| Form factor | Modular Rack 19" |
| Dimensions W × D × H | 17.4 × 33.1 × 59.4 in (442 × 840 × 1,510 mm) |
| Net weight | 360 lb (163.4 kg) |
| Footprint | 4.0 ft² (0.37 m²) |
| Common to every RADIANT | |
| Technology | 3-level IGBT; unity power factor (kVA = kW); 40 A settable charger |
| Battery, RAD90-5X15 | external VRLA (battery bank sized separately) |
| Display | 7-inch color touchscreen |
| Comms | RS-232, EPO and USB, standard |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The RADIANT documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
Quick answers
RAD90-5X15: what people ask
What is the output current of the RAD90-5X15?
208.2 A per phase at full load: 75 kVA ÷ (√3 × 208 V). Size the input breaker and the cables of the RAD90-5X15 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the RAD90-5X15 give off?
About 5.0 kW, 16,910 BTU/h, at full load, where it is 93.8% efficient. Plan the room's cooling for a little more than that: the RAD90-5X15 is less efficient at part load and while its battery recharges.
Will the RAD90-5X15 fit through a standard door?
Yes: 17.4 in (442 mm) across its narrow side and 59.4 in (1,510 mm) high, it passes a standard 36 × 80-inch door upright. On the way in, check corridors, elevators and the floor load of the RAD90-5X15 (size section above).
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
RADIANT
Other RADIANT models
By power, the RAD90-5X15 is number 5 of 6 in the RADIANT series, which runs from 15 to 90 kVA. One size down is the RAD90-4X15 (15 kVA less and 31 lb lighter). One size up is the RAD90-6X15 (15 kVA more and 31 lb heavier).
Every RADIANT model side by side (6)
| Model | Power | Power against this model | Net weight | Weight against this model |
|---|---|---|---|---|
| RAD90-1X15 | 15 kVA | 60 kVA less | 238 lb | 122 lb lighter |
| RAD90-2X15 | 30 kVA | 45 kVA less | 269 lb | 92 lb lighter |
| RAD90-3X15 | 45 kVA | 30 kVA less | 299 lb | 61 lb lighter |
| RAD90-4X15 | 60 kVA | 15 kVA less | 330 lb | 31 lb lighter |
| RAD90-5X15 | 75 kVA | this page | 360 lb | this page |
| RAD90-6X15 | 90 kVA | 15 kVA more | 391 lb | 31 lb heavier |
The RAD90-5X15 for your project
Send the load, the voltage and the minutes you need from the RAD90-5X15. We reply with the configuration, the batteries and the lead time.