CIRRO · 480V three-phase UPS
CIR800-7X100 CIRRO 700 kVA, 480V three-phase UPS
The AEC CIRRO CIR800-7X100 is a 700 kVA / 700 kW online double-conversion UPS for 480 V three-phase loads, built on seven 100 kVA power modules, with external battery cabinets. Kept at 80 % of its rating, it carries loads up to 560 kW.
Seven of the frame's eight module slots are fitted and one is free; with one module held as a spare (N+1) it carries 600 kVA. As configured it weighs 1,798.8 lb (815.9 kg) net.
4-wire · 3P+N480 V 4-wire, wye: three phases, neutral and ground (277/480 V)
The same on every CIRRO:The CIRRO display
Load by load
The CIR800-7X100 at 25, 50, 75 and 100 % load.
Its 700 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current per phase, at 480 V | Load on each of its 7 power modules | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|---|
| 25 % of the CIR800-7X100, 175 kW | 210 A per phase | 25 % on each module | 96.2 % efficient | 6.9 kW of heat | 23,590 BTU/h to cool |
| 50 % of the CIR800-7X100, 350 kW | 421 A per phase | 50 % on each module | 96.9 % efficient | 11 kW of heat | 38,200 BTU/h to cool |
| 75 % of the CIR800-7X100, 525 kW | 631 A per phase | 75 % on each module | 97.0 % efficient | 16 kW of heat | 55,400 BTU/h to cool |
| 100 % of the CIR800-7X100, 700 kW | 842 A per phase | 100 % on each module | 96.8 % efficient | 23 kW of heat | 78,960 BTU/h to cool |
Current = kVA × load ÷ (√3 × volts).
Module load = load ÷ the kVA of the power modules fitted.
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the CIR800-7X100 at your load?
The CIR800-7X100 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What is the CIR800-7X100?
The code CIR800-7X100 orders these catalog items:
- 1 × CIR800-FRAME: 800 kVA frame, without power modules, 31.5 × 39.4 × 78.7 in (800 × 1,001 × 1,999 mm)
- 7 × CIR-PWR-100: 100 kVA hot-swappable power module, 103.6 lb (47 kg) each
- Architecture: 7 × 100 kVA hot-swappable power modules in a 800 kVA / 800 kW frame (8 slots, scalable to 8 modules / 800 kVA); parallel up to 8 units.
- Battery: external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 × 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole).
- Switchgear: 4 breakers included in the frame — main input, output, bypass input, maintenance bypass.
- Efficiency: up to 97%.
The lines every CIRRO shares, from technology to warranty, are in the CIRRO key facts and in the datasheet below.
7 × 100 kVA power modules fitted in a 8-slot frame: 1 free slot to grow or add redundancy.
Size and floor
How big it is
31.5" W × 39.4" D × 78.7" H (800 × 1,001 × 1,999 mm); 1,798.8 lb (815.9 kg) net.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
What does the CIRRO need in the room?
From the AEC US user manual of the CIRRO. Where the manual gives no distance, none is printed here: ask AEC.
- Clearances
- Front 36 in (914 mm), rear 31.5 in (800 mm), top 19.7 in (500 mm) on the 600, 800 and 1200 frames. Sides: not given.
- Wiring
- Hardwired: an electrician connects it to the panel.
- Cable entry
- Top, through the cable entry plate; Bottom (Only with the optional side wiring cabinet beside the UPS: its size from AEC)
- Breakers and terminals
- The four breakers are in the breaker section beside the cabinet (55.1 in / 1,400 mm wide in all); terminals under the top cover. Battery breaker external.
- Door
- Hinge side not given.
- Space to pull a module
- Keep at least 27.8 in (705 mm) free in front to slide a module out.
- Units in parallel
- Up to 8 of the same model.
Datasheet
CIR800-7X100 datasheet.
The CIR800-7X100 in the AEC 2026 catalog, figure by figure. Compare it with every CIRRO model.
| Parameter | CIR800-7X100 |
|---|---|
| Power | |
| Rated power (kVA) | 700 |
| Active power (kW) | 700 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 480 V three-phase, 4-wire (3P+N) |
| Topology | Online double conversion, modular N+X |
| Efficiency, up to | 97% |
| Battery DC bus | 480 V DC |
| Battery and runtime | |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | External battery bank |
| Mechanical | |
| Form factor | Modular |
| Dimensions W × D × H | 31.5 × 39.4 × 78.7 in (800 × 1,001 × 1,999 mm) |
| Net weight | 1,798.8 lb (815.9 kg) |
| Footprint | 8.6 ft² (0.80 m²) |
| Common to every CIRRO | |
| Technology | 3-level IGBT; unity power factor (kVA = kW); 80 A settable charger |
| Display | personalized AEC red color touchscreen |
| Comms | RS232, RS485, USB, dry contacts, intelligent slot and EPO standard; battery cold start |
| Battery, CIR800-7X100 | external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 x 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole) |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The CIRRO documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
Quick answers
CIR800-7X100: what people ask
What is the output current of the CIR800-7X100?
842.0 A per phase at full load: 700 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the CIR800-7X100 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the CIR800-7X100 give off?
About 23 kW, 78,960 BTU/h, at full load, where it is 96.8% efficient. Plan the room's cooling for a little more than that: the CIR800-7X100 is less efficient at part load and while its battery recharges.
Will the CIR800-7X100 fit through a standard door?
Yes: 31.5 in (800 mm) across its narrow side and 78.7 in (1,999 mm) high, it passes a standard 36 × 80-inch door upright, with little to spare in height. On the way in, check corridors, elevators and the floor load of the CIR800-7X100 (size section above).
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
CIRRO
Other CIRRO models
By power, the CIR800-7X100 is number 12 of 21 in the CIRRO series, which runs from 60 to 1,600 kVA. One size down is the CIR600-6X100 (100 kVA less and 284 lb lighter). One size up is the CIR800-8X100 (100 kVA more and 104 lb heavier).
Every CIRRO model side by side (21)
| Model | Power | Power against this model | Net weight | Weight against this model |
|---|---|---|---|---|
| CIR360-1X60 | 60 kVA | 640 kVA less | 636 lb | 1,162 lb lighter |
| CIR600-1X100 | 100 kVA | 600 kVA less | 997 lb | 802 lb lighter |
| CIR360-2X60 | 120 kVA | 580 kVA less | 727 lb | 1,072 lb lighter |
| CIR360-3X60 | 180 kVA | 520 kVA less | 817 lb | 982 lb lighter |
| CIR600-2X100 | 200 kVA | 500 kVA less | 1,100 lb | 699 lb lighter |
| CIR360-4X60 | 240 kVA | 460 kVA less | 908 lb | 891 lb lighter |
| CIR360-5X60 | 300 kVA | 400 kVA less | 998 lb | 801 lb lighter |
| CIR360-6X60 | 360 kVA | 340 kVA less | 1,088 lb | 710 lb lighter |
| CIR600-4X100 | 400 kVA | 300 kVA less | 1,307 lb | 492 lb lighter |
| CIR600-5X100 | 500 kVA | 200 kVA less | 1,411 lb | 388 lb lighter |
| CIR600-6X100 | 600 kVA | 100 kVA less | 1,515 lb | 284 lb lighter |
| CIR800-7X100 | 700 kVA | this page | 1,799 lb | this page |
| CIR800-8X100 | 800 kVA | 100 kVA more | 1,902 lb | 104 lb heavier |
| CIR1200-9X100 | 900 kVA | 200 kVA more | 2,308 lb | 509 lb heavier |
| CIR1200-10X100 | 1,000 kVA | 300 kVA more | 2,412 lb | 613 lb heavier |
| CIR1200-11X100 | 1,100 kVA | 400 kVA more | 2,515 lb | 717 lb heavier |
| CIR1200-12X100 | 1,200 kVA | 500 kVA more | 2,619 lb | 820 lb heavier |
| CIR1600-13X100 | 1,300 kVA | 600 kVA more | 3,485 lb | 1,687 lb heavier |
| CIR1600-14X100 | 1,400 kVA | 700 kVA more | 3,589 lb | 1,790 lb heavier |
| CIR1600-15X100 | 1,500 kVA | 800 kVA more | 3,693 lb | 1,894 lb heavier |
| CIR1600-16X100 | 1,600 kVA | 900 kVA more | 3,796 lb | 1,997 lb heavier |
Install and run it:RADIANT and CIRRO operating guide
The CIR800-7X100 for your project
Send the load, the voltage and the minutes you need from the CIR800-7X100. We reply with the configuration, the batteries and the lead time.