CIRRO · 480V three-phase UPS

CIR800-7X100 CIRRO 700 kVA, 480V three-phase UPS

VRLA700 kVAOnline double conversion

The AEC CIRRO CIR800-7X100 is a 700 kVA / 700 kW online double-conversion UPS for 480 V three-phase loads, built on seven 100 kVA power modules, with external battery cabinets. Kept at 80 % of its rating, it carries loads up to 560 kW.

Seven of the frame's eight module slots are fitted and one is free; with one module held as a spare (N+1) it carries 600 kVA. As configured it weighs 1,798.8 lb (815.9 kg) net.

4-wire · 3P+N480 V 4-wire, wye: three phases, neutral and ground (277/480 V)

700 kVA / 700 kWRating
31.5 × 39.4 × 78.7 inW × D × H
1,798.8 lbWeight
VRLA, externalBattery

Load by load

The CIR800-7X100 at 25, 50, 75 and 100 % load.

Its 700 kW rating in four steps, worked out from its own catalog figures.

At 25, 50, 75 and 100 % load
LoadOutput current per phase, at 480 VLoad on each of its 7 power modulesEfficiencyHeat to removeHeat to remove (BTU/h)
25 % of the CIR800-7X100, 175 kW210 A per phase25 % on each module96.2 % efficient6.9 kW of heat23,590 BTU/h to cool
50 % of the CIR800-7X100, 350 kW421 A per phase50 % on each module96.9 % efficient11 kW of heat38,200 BTU/h to cool
75 % of the CIR800-7X100, 525 kW631 A per phase75 % on each module97.0 % efficient16 kW of heat55,400 BTU/h to cool
100 % of the CIR800-7X100, 700 kW842 A per phase100 % on each module96.8 % efficient23 kW of heat78,960 BTU/h to cool

Current = kVA × load ÷ (√3 × volts).

Module load = load ÷ the kVA of the power modules fitted.

Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.

From the 2026 catalog

What is the CIR800-7X100?

The code CIR800-7X100 orders these catalog items:

  • 1 × CIR800-FRAME: 800 kVA frame, without power modules, 31.5 × 39.4 × 78.7 in (800 × 1,001 × 1,999 mm)
  • 7 × CIR-PWR-100: 100 kVA hot-swappable power module, 103.6 lb (47 kg) each
  • Architecture: 7 × 100 kVA hot-swappable power modules in a 800 kVA / 800 kW frame (8 slots, scalable to 8 modules / 800 kVA); parallel up to 8 units.
  • Battery: external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 × 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole).
  • Switchgear: 4 breakers included in the frame — main input, output, bypass input, maintenance bypass.
  • Efficiency: up to 97%.

The lines every CIRRO shares, from technology to warranty, are in the CIRRO key facts and in the datasheet below.

7 × 100 kVA power modules fitted in a 8-slot frame: 1 free slot to grow or add redundancy.

Size and floor

How big it is

31.5" W × 39.4" D × 78.7" H (800 × 1,001 × 1,999 mm); 1,798.8 lb (815.9 kg) net.

8.6 ft²footprint (0.80 m²)
209 lb/ft²floor load of the cabinet alone
Modularform factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

5′9″ FrontSide 31.5″39.4″78.7″

Datasheet

CIR800-7X100 datasheet.

The CIR800-7X100 in the AEC 2026 catalog, figure by figure. Compare it with every CIRRO model.

CIR800-7X100 datasheet
ParameterCIR800-7X100
Power
Rated power (kVA)700
Active power (kW)700
Output power factor1.0
Electrical
Input / output480 V three-phase, 4-wire (3P+N)
TopologyOnline double conversion, modular N+X
Efficiency, up to97%
Battery DC bus480 V DC
Battery and runtime
Battery typeVRLA (sealed lead-acid)
Battery configurationExternal battery bank
Mechanical
Form factorModular
Dimensions W × D × H31.5 × 39.4 × 78.7 in (800 × 1,001 × 1,999 mm)
Net weight1,798.8 lb (815.9 kg)
Footprint8.6 ft² (0.80 m²)
Common to every CIRRO
Technology3-level IGBT; unity power factor (kVA = kW); 80 A settable charger
Displaypersonalized AEC red color touchscreen
CommsRS232, RS485, USB, dry contacts, intelligent slot and EPO standard; battery cold start
Battery, CIR800-7X100external VRLA (battery bank sized separately). DC bus ±240 Vdc (480 Vdc total), 40 x 12 V blocks by default; selectable 30 to 50 blocks (±15 to ±25 per pole)
Network cardSNMP-M (SNMP)
Warranty3 years on UPS · 2 years on VRLA batteries
Quality systemISO 9001:2015, the group's quality system (SGS)

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

CIR800-7X100: what people ask

What is the output current of the CIR800-7X100?

842.0 A per phase at full load: 700 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the CIR800-7X100 from its installation manual and the local electrical code, not from this figure alone.

How much heat does the CIR800-7X100 give off?

About 23 kW, 78,960 BTU/h, at full load, where it is 96.8% efficient. Plan the room's cooling for a little more than that: the CIR800-7X100 is less efficient at part load and while its battery recharges.

Will the CIR800-7X100 fit through a standard door?

Yes: 31.5 in (800 mm) across its narrow side and 78.7 in (1,999 mm) high, it passes a standard 36 × 80-inch door upright, with little to spare in height. On the way in, check corridors, elevators and the floor load of the CIR800-7X100 (size section above).

The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h

CIRRO

Other CIRRO models

The CIRRO series, with pictures

By power, the CIR800-7X100 is number 12 of 21 in the CIRRO series, which runs from 60 to 1,600 kVA. One size down is the CIR600-6X100 (100 kVA less and 284 lb lighter). One size up is the CIR800-8X100 (100 kVA more and 104 lb heavier).

Every CIRRO model side by side (21)
CIRRO models side by side
ModelPowerPower against this modelNet weightWeight against this model
CIR360-1X6060 kVA640 kVA less636 lb1,162 lb lighter
CIR600-1X100100 kVA600 kVA less997 lb802 lb lighter
CIR360-2X60120 kVA580 kVA less727 lb1,072 lb lighter
CIR360-3X60180 kVA520 kVA less817 lb982 lb lighter
CIR600-2X100200 kVA500 kVA less1,100 lb699 lb lighter
CIR360-4X60240 kVA460 kVA less908 lb891 lb lighter
CIR360-5X60300 kVA400 kVA less998 lb801 lb lighter
CIR360-6X60360 kVA340 kVA less1,088 lb710 lb lighter
CIR600-4X100400 kVA300 kVA less1,307 lb492 lb lighter
CIR600-5X100500 kVA200 kVA less1,411 lb388 lb lighter
CIR600-6X100600 kVA100 kVA less1,515 lb284 lb lighter
CIR800-7X100700 kVAthis page1,799 lbthis page
CIR800-8X100800 kVA100 kVA more1,902 lb104 lb heavier
CIR1200-9X100900 kVA200 kVA more2,308 lb509 lb heavier
CIR1200-10X1001,000 kVA300 kVA more2,412 lb613 lb heavier
CIR1200-11X1001,100 kVA400 kVA more2,515 lb717 lb heavier
CIR1200-12X1001,200 kVA500 kVA more2,619 lb820 lb heavier
CIR1600-13X1001,300 kVA600 kVA more3,485 lb1,687 lb heavier
CIR1600-14X1001,400 kVA700 kVA more3,589 lb1,790 lb heavier
CIR1600-15X1001,500 kVA800 kVA more3,693 lb1,894 lb heavier
CIR1600-16X1001,600 kVA900 kVA more3,796 lb1,997 lb heavier

The CIR800-7X100 for your project

Send the load, the voltage and the minutes you need from the CIR800-7X100. We reply with the configuration, the batteries and the lead time.