INFINITE · 480V three-phase UPS

INF-600 INFINITE 600 kVA, 480V three-phase UPS

Lithium or VRLA600 kVAOnline double conversion

The AEC INFINITE INF-600 is a 600 kVA / 600 kW online double-conversion UPS for 480 V three-phase loads, built on six 100 kVA power modules, supplied as three cabinets in parallel, with external VRLA or lithium cabinets. Kept at 80 % of its rating, it carries loads up to 480 kW.

3-wire · Delta480 V 3-wire, delta: three phases and ground, no neutral

600 kVA / 600 kWRating
3 × 23.6 × 39.4 × 81.4 inW × D × H, 3 cabinets
1,773.8 lbWeight
VRLA or lithium, externalBattery

Series picture. The INF-600 is 3 × 200 kVA frames.

Runtime

The INF-600 with its batteries, at your load.

The INF-600 has no batteries of its own: the chart draws in bold the catalog set-ups built on it, the other INFINITE set-ups faded behind. The same chart as the INFINITE page. 2026 catalog, new batteries.

50 %
102050100200500100010%25%50%75%100%INF-100+1+L6-CAB-20x50LI, INF-100+L6-CAB-20x50LIINF-100+L6-CAB-10x50LI, INF-200+1+L6-CAB-20x50LI, INF-200+L6-CAB-20x50LI, INF-400+2xL6-CAB-20x50LI, INF-600+3xL6-CAB-20x50LIminutes (log scale)
INFINITE 100 kVA N+1 · 1 L6 cabinet, 20 lithium modules · INFINITE 100 kVA · 1 L6 cabinet, 20 lithium modulesINFINITE 100 kVA · half L6 cabinet, 10 modules and 4 more, same minutes
Table: this model at 25, 50, 75 and 100 % load
Model25% load50% load75% load100% load
INFINITE 600 kVA · 3 L6 cabinets, 60 lithium modulesINF-600+3xL6-CAB-20x50LI60 min30 min20 min15 min

Every INFINITE set-up in one table

From the 2026 catalog

What is the INF-600?

The code INF-600 orders these catalog items, shipped in 3 cartons:

  • 3 × INF-200: 200 kVA UPS, 23.6 × 39.4 × 81.4 in (600 × 1,000 × 2,068 mm), 591.3 lb (268.2 kg) each
  • Architecture: 6 × 100 kVA hot-swappable power modules in 3 × 200 kVA frames.
  • Supplied as 3 x INF-200 cabinets operating in parallel; the 200 kVA frame hosts a maximum of 2+1 power modules.

Its other catalog lines are those of the INF-100, of the same series: see them on its page.

Size and floor

How big it is

3 cabinets in parallel, each 23.6" W × 39.4" D × 81.4" H (600 × 1,000 × 2,068 mm); 1,773.8 lb (804.6 kg) net in all.

19.4 ft²footprint, 3 cabinets side by side (1.80 m²)
92 lb/ft²floor load of the cabinet alone
Modularform factor

Floor load = net weight ÷ footprint, without batteries outside the cabinet.

5′9″ FrontSide 23.62″39.37″81.42″

Datasheet

INF-600 datasheet.

The INF-600 in the AEC 2026 catalog, figure by figure. Compare it with every INFINITE model.

INF-600 datasheet
ParameterINF-600
Power
Rated power (kVA)600
Active power (kW)600
Output power factor1.0
Electrical
Input / output480 V three-phase, 3-wire (delta)
TopologyOnline double conversion, modular
Efficiency, up to97.3%
Battery DC bus480 V DC
Battery and runtime
Battery typeVRLA or lithium LiFePO4
Battery configurationExternal VRLA bank or L6 lithium cabinets
Mechanical
Form factorModular
Dimensions W × D × H3 cabinets, each 23.6 × 39.4 × 81.4 in (600 × 1,000 × 2,068 mm)
Net weight1,773.8 lb (804.6 kg)
Footprint19.4 ft² (1.80 m²), 3 cabinets
Common to every INFINITE
Battery, INF-600external, lead-acid (30–50 blocks) or AEC L6 lithium cabinets
Technology, display, communications, warrantyAs on the INF-100 datasheet

From the AEC 2026 catalog. Figures can change: the order confirmation rules.

Quick answers

INF-600: what people ask

What is the output current of the INF-600?

721.7 A per phase at full load: 600 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the INF-600 from its installation manual and the local electrical code, not from this figure alone.

How much heat does the INF-600 give off?

About 17 kW, 56,810 BTU/h, at full load, where it is 97.3% efficient. Plan the room's cooling for a little more than that: the INF-600 is less efficient at part load and while its battery recharges.

Will the INF-600 fit through a standard door?

Not upright through a standard 36 × 80-inch door, which clears about 79 in in height: at 81.4 in (2,068 mm) high it needs an opening taller than 81.4 in. Check elevators and the floor load on the way in too.

The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h

INFINITE

Other INFINITE models

The INFINITE series, with pictures

By power, the INF-600 is the largest in the INFINITE series, which runs from 100 to 600 kVA. One size down are the INF-400 and INF-400+2xL6-CAB-20x50LI, all 200 kVA less. The same 600 kVA also comes as INF-600+3xL6-CAB-20x50LI (external L6 lithium cabinets, 6,823 lb heavier); the INF-600 has external VRLA bank or L6 lithium cabinets.

Every INFINITE model side by side (13)
INFINITE models side by side
ModelPowerPower against this modelNet weightWeight against this modelBattery configuration
INF-100100 kVA500 kVA less452 lb1,322 lb lighterExternal VRLA bank or L6 lithium cabinets
INF-100+1100 kVA500 kVA less571 lb1,203 lb lighterExternal VRLA bank or L6 lithium cabinets
INF-100+1+L6-CAB-20x50LI100 kVA500 kVA less2,743 lb969 lb heavierExternal L6 lithium cabinets
INF-100+L6-CAB-10x50LI100 kVA500 kVA less1,808 lb34 lb heavierExternal L6 lithium cabinets
INF-100+L6-CAB-20x50LI100 kVA500 kVA less2,624 lb850 lb heavierExternal L6 lithium cabinets
INF-200200 kVA400 kVA less591 lb1,183 lb lighterExternal VRLA bank or L6 lithium cabinets
INF-200+1200 kVA400 kVA less710 lb1,063 lb lighterExternal VRLA bank or L6 lithium cabinets
INF-200+1+L6-CAB-20x50LI200 kVA400 kVA less2,882 lb1,108 lb heavierExternal L6 lithium cabinets
INF-200+L6-CAB-20x50LI200 kVA400 kVA less2,763 lb989 lb heavierExternal L6 lithium cabinets
INF-400400 kVA200 kVA less1,183 lb591 lb lighterExternal VRLA bank or L6 lithium cabinets
INF-400+2xL6-CAB-20x50LI400 kVA200 kVA less5,526 lb3,752 lb heavierExternal L6 lithium cabinets
INF-600600 kVAthis page1,774 lbthis pageExternal VRLA bank or L6 lithium cabinets
INF-600+3xL6-CAB-20x50LI600 kVAthe same power8,597 lb6,823 lb heavierExternal L6 lithium cabinets

The INF-600 for your project

Send the load, the voltage and the minutes you need from the INF-600. We reply with the configuration, the batteries and the lead time.