ECO mode vs double conversion: what the load gives up

ECO mode is not the safe choice for a critical load in a data center: it runs the load on the UPS's static bypass, straight from the utility, with the inverter on standby, so the load is no longer conditioned and reaches the inverter only after the supply goes wrong. AEC designs its UPS for online double conversion, at up to 97.3 % efficiency on INFINITE and 97.5 % on INFINITE 1.5MW.

Data center, black-and-white photograph

What does ECO mode give up?

In online double conversion the rectifier turns the utility into DC and the inverter rebuilds a regulated sine wave from it, every cycle. In ECO mode the UPS feeds the load from its bypass while the bypass voltage and frequency stay inside a set window, keeps the inverter ready and the battery charged, and moves the load to the inverter when the bypass leaves the window or fails. Three things change for the load:

  • No conditioning. The load gets the utility as it comes: sags, surges, distortion and frequency drift inside the window pass straight through. The AEC manuals state that in ECO mode the load is not protected from utility disturbances. Online double conversion explains the difference.
  • A transfer on every disturbance. The load reaches the inverter only after the bypass has left its window. The RADIANT, RADIANT-IB and CIRRO-IB manuals give that break as less than 10 ms. The ITI (CBEMA) curve application note describes a complete loss of voltage of up to 20 ms as typically tolerated by most information technology equipment on 120 V systems; motors, drives and some controls may not ride through it.
  • Harmonics to the supply. The load's current distortion goes straight to the utility and to the generator, where in double conversion the rectifier draws a near-sinusoidal current.

The ETHERNO, AUREON, CIRRO and INFINITE manuals answer the question "What is ECO mode?" the same way: higher efficiency, no protection from disturbances; use online mode for critical loads.

How efficient is double conversion on an AEC UPS?

The catalog's efficiency curves, in online double conversion:

Series25 % load50 %75 %100 %
ETHERNO, AUREON92.5 %93.9 %94.0 %93.8 %
RADIANT92.8 %93.9 %94.0 %93.8 %
RADIANT-IB92.7 %93.9 %94.0 %93.8 %
CIRRO-IB95.0 %95.9 %96.0 %95.8 %
CIRRO 36095.1 %95.9 %96.0 %95.8 %
CIRRO 600 to 160096.2 %96.9 %97.0 %96.8 %
INFINITE (SiC)96.9 %97.3 %97.3 %97.3 %
INFINITE 1.5MW (SiC)up to 97.5 % AC/AC

INFINITE and INFINITE 1.5MW switch with silicon carbide (SiC) semiconductors, which lose less than silicon at each switching step. At 97.3 % an INFINITE carrying 100 kW loses about 2.8 kW, with the load fully conditioned. The efficiency page has every series' curve at your load, and UPS heat output turns the losses into cooling.

Why does AEC run its UPS in double conversion?

  • The load is the point of the UPS. In double conversion the inverter sets the output voltage and frequency whatever the utility does, and an outage reaches the load as no break at all.
  • The efficiency gap is small on current designs. On INFINITE double conversion runs 96.9 to 97.3 %, against up to 99 % in ECO: about 2 points, bought back with the protection of the load.
  • Part load has its own answer. On a modular UPS, module sleep keeps the load in double conversion and lets the modules it does not need stand by (below).
  • The site's supply decides the rest. On a generator or a poor utility, ECO either passes the disturbances to the load or keeps transferring.

What is module sleep?

On a modular UPS at part load, the modules the load does not need stand by in turn, so they age evenly, and wake as the load grows. The load stays in double conversion the whole time, and the running modules work nearer their best efficiency. RADIANT, RADIANT-IB and CIRRO-IB log it as Intelligent Sleep; on INFINITE, AEC service sets it under Smart mode, Sleep redundancy. The manuals ask that the running modules can carry any load you add: wake the sleeping modules before connecting a load of uncertain size.

Which AEC UPS have an ECO setting?

SeriesECO settingWhat it doesWho sets it
ETHERNO, AUREONECO on or off; voltage window ±10 or ±15 %; frequency window ±5 or ±10 %Load on the bypass while it stays inside both windows. Single UPS only: not in a parallel system.Settings on the touchscreen
RADIANT, RADIANT-IB, CIRRO-IBSystem mode: Single, Parallel, Single ECO, Parallel ECOLoad on the static bypass, inverters on standby, chargers on; back to the inverters in less than 10 ms. RADIANT-IB bypass window +15 / −20 % by default.Sys Set → System Mode, at commissioning
CIRRO 60 to 1,600 kVASystem mode: Single, Parallel, Single ECO, Parallel ECO, LBS, Parallel LBSLoad on the static bypass while the inverters stand by; if the bypass fails the inverters take the load. The manual gives no transfer time for it: ask AEC.Set › Sys Set
INFINITEStandard ECO; W-ECOStandard ECO: load on the bypass, inverter ready, rectifier charging. W-ECO: load on the bypass while the power modules run tied to it and compensate the harmonics of the bypass current; if the bypass voltage falls too low, the load goes to the inverter.AEC service

The INFINITE operating guide shows how each mode looks on the display.

When must ECO mode stay off?

  • Critical loads. The manuals' own advice: online mode for critical loads.
  • On generator power. A generator's frequency moves with every load step. With ECO on, the load either sees those swings or the UPS keeps transferring; ETHERNO's ±5 % frequency window is 3 Hz at 60 Hz.
  • Loads that cannot take the transfer. Motors, drives, some controls and medical equipment: check each maker's ride-through.
  • Parallel ETHERNO and AUREON systems. Their ECO works on a single UPS only.
  • A poor or distorted supply. The UPS spends its time transferring, and the load gets the disturbances in between.

What does ECO save against double conversion?

Losses are the load times (1 ÷ efficiency − 1). A RADIANT with six 15 kVA modules carrying 22.5 kW runs at 25 % of its 90 kW, on the steep end of its curve. The catalog curve gives 92.8 % there; the RADIANT manual gives 99 % in ECO mode, one figure not stated by load:

RADIANT at 22.5 kWLoad protectedEfficiencyLossesA year (8,760 h)
Double conversion, six modules runningyes92.8 %1.75 kWabout 15,300 kWh
Double conversion, three modules running, three asleepyes93.9 %1.46 kWabout 12,800 kWh
ECO modeno99 %0.23 kWabout 2,000 kWh

The second row takes the running modules at the catalog's 50 % point. A frame sized closer to the load, or module sleep, recovers part of the loss and keeps the protection; ECO recovers more by giving it up. The higher the double-conversion efficiency, the less there is to recover: on INFINITE the gap is about 2 points instead of 6.

What mistakes come up with ECO mode?

  • Comparing a 99 % ECO figure with a double-conversion figure. They describe two levels of protection; compare like with like, at your load.
  • Leaving the mode at whatever was set at commissioning. Record the mode chosen and why, as a deliberate setting.
  • Using ECO to fix an oversized UPS. On a modular frame, fewer modules or module sleep recover part of the loss and keep the load in double conversion.

The UPS sizing tool sizes the frame for your load, so the modules run near their best point in double conversion.

Questions people ask

What is ECO mode on a UPS?

A setting in which an online UPS feeds the load from its static bypass, straight from the utility, with the inverter on standby. Efficiency rises, but the load is no longer conditioned and moves to the inverter only after a disturbance has started.

Does AEC recommend ECO mode?

No. AEC designs and recommends online double conversion as the normal operating mode. The ETHERNO, AUREON, CIRRO and INFINITE manuals say the same: in ECO the load has no protection from disturbances, so use online mode for critical loads.

How efficient is an AEC UPS in double conversion?

From 92.5 to 94.0 % on ETHERNO, AUREON, RADIANT and RADIANT-IB, 95.0 to 96.0 % on CIRRO-IB, up to 97.0 % on CIRRO 600 to 1600, 96.9 to 97.3 % on INFINITE and up to 97.5 % on INFINITE 1.5MW, from the catalog curves.

How fast does a UPS leave ECO mode?

AEC RADIANT, RADIANT-IB and CIRRO-IB move the load to the inverters in less than 10 ms when the bypass fails. The ITI (CBEMA) curve describes a dropout of up to 20 ms as typically tolerated by most IT equipment; check motors and controls.

What is the difference between ECO mode and module sleep?

ECO puts the load on the bypass. Module sleep keeps the load in double conversion and lets the modules not needed stand by, so the running ones work nearer their best efficiency.