Questions and answers

CIRRO-IB: questions and answers

9 questions about the AEC CIRRO-IB, from its series page and its 5 model pages, grouped by subject. Each answer is the one printed on its page; follow the link for the full data, the tables and the drawings.

Choosing, sizing and ordering 2 questions

How much power do 3 CIRIB150-1X30 give in parallel?

90 kVA: up to 3 units of the same model run in parallel, by the AEC US user manual of the CIRRO-IB. Kept as N+1, with one unit spare, 3 CIRIB150-1X30 carry 60 kVA (60 kW).

Answered on CIRIB150-1X30

What sizes does CIRRO-IB come in?

30 to 150 kVA, in 5 models of the 2026 catalog for the US, from the CIRIB150-1X30 (30 kVA) to the CIRIB150-5X30 (150 kVA). The datasheet on this page gives every one.

Answered on CIRRO-IB

Runtime and batteries 1 question

What batteries does CIRRO-IB use?

Internal hot-swappable VRLA, up to 240 × 12 V 9 Ah blocks. The battery bus is 480 V DC on every model.

Answered on CIRRO-IB

Installation, size and connections 4 questions

What is the output current of each CIRRO-IB model?

At full load, from the rating and the voltage:

ModelOutput currentWorked out as
CIRIB150-1X3036.1 A per phase30 kVA ÷ (√3 × 480 V)
CIRIB150-2X3072.2 A per phase60 kVA ÷ (√3 × 480 V)
CIRIB150-3X30108.3 A per phase90 kVA ÷ (√3 × 480 V)
CIRIB150-4X30144.3 A per phase120 kVA ÷ (√3 × 480 V)
CIRIB150-5X30180.4 A per phase150 kVA ÷ (√3 × 480 V)

Size the input breaker and the cables of each model from its installation manual and the local electrical code, not from this figure alone.

Each model's own page, linked in the table, gives its full answer and data.

How much heat does each CIRRO-IB model give off?

At full load, model by model:

ModelHeatBTU/hEfficiency
CIRIB150-1X301.3 kW4,49095.8%
CIRIB150-2X302.6 kW8,98095.8%
CIRIB150-3X303.9 kW13,46095.8%
CIRIB150-4X305.3 kW17,95095.8%
CIRIB150-5X306.6 kW22,44095.8%

Plan the room's cooling for a little more than that: each model is less efficient at part load and while its battery recharges.

Each model's own page, linked in the table, gives its full answer and data.

Which CIRRO-IB models fit through a standard door?

A standard 36 × 80-inch door clears about 34 × 79 in. Upright, model by model:

ModelUpright through the doorNarrow side, height
CIRIB150-1X30Yes, with little to spare in height23.6 in (599 mm) across, 78.7 in (1,999 mm) high
CIRIB150-2X30Yes, with little to spare in height23.6 in (599 mm) across, 78.7 in (1,999 mm) high
CIRIB150-3X30Yes, with little to spare in height23.6 in (599 mm) across, 78.7 in (1,999 mm) high
CIRIB150-4X30Yes, with little to spare in height23.6 in (599 mm) across, 78.7 in (1,999 mm) high
CIRIB150-5X30Yes, with little to spare in height23.6 in (599 mm) across, 78.7 in (1,999 mm) high

On the way in, check corridors, elevators and the floor load (size section of each model's page).

Each model's own page, linked in the table, gives its full answer and data.

What supply does CIRRO-IB need?

480/277 V three-phase, 4-wire, for every model of the series. Its power factor is 1.0, so each model gives its kVA rating in kW.

Answered on CIRRO-IB

Communication and monitoring 1 question

How is CIRRO-IB monitored over the network?

With the AEC SNMP-M network card, which reports the UPS status and alarms over SNMP to your monitoring software.

Answered on CIRRO-IB

Warranty, service and maintenance 1 question

What warranty does CIRRO-IB have?

3 years on UPS; 2 years on VRLA batteries, from start-up. Register the UPS with AEC after start-up.

Answered on CIRRO-IB

Still a question?

Tell us the load, the voltage and the minutes you need: an AEC engineer answers.