IST6 200–500 · Modular UPS
IST6-400, 8 × 50 kVA Hot-swappable modular UPS, 400 V
The IST6-400 is a double-column modular online UPS cabinet for up to eight 50 kVA power modules: 400 kVA / 400 kW in 1203 × 864 × 2000 mm. For data centres and hospitals of 200 to 400 kW that prefer small 50 kVA steps, and fine N+1 granularity, at this power.
Quick answers
IST6-400, 8 × 50 kVA: quick answers
- What it is
- The IST6-400 is a double-column modular online UPS cabinet for up to eight 50 kVA power modules: 400 kVA / 400 kW in 1203 × 864 × 2000 mm.
- Who it is for
- For data centres and hospitals of 200 to 400 kW that prefer small 50 kVA steps, and fine N+1 granularity, at this power.
- Supply and configuration
- 380 / 400 / 415 V
- Battery and backup
- ±240 V DC nominal (±180 … ±300 V), 30–50 × 12 V blocks, standard 40
- Size and weight
- 1203 × 864 × 2000 mm · 459 kg without modules
- Ordering code
- IST6-400
IST6 200–500
What sets apart the IST6-400, 8 × 50 kVA
400 kVA is also sold on the 100 kW-module frame, as a different product: the IST6 400 kVA with 4 × 100 kVA modules, one 801 × 1000 × 2000 mm column of 345 kg without modules, against this double column of 1203 × 864 × 2000 mm. AEC chooses the frame with you: 50 kVA modules spread the redundancy finer, 100 kVA modules take less floor.
The IST6-400 is the first double-column cabinet: 1203 mm wide, 459 kg without modules, with the power modules even above and odd below, a 3U bypass module and optional SPD with its own switch. Its 50 kVA step means N+1 at 350 kVA costs one 50 kVA module; the 400–1200 kVA range reaches 400 kVA with four 100 kVA modules instead.
Fully loaded it draws 690 A at the mains (2 × (4 × 185) mm², 800 A 3P breaker), 606 A at bypass and output and 868 A from a 40-block battery on 3 × (3 × 185) mm², and needs 4840 m³/h of air.
- Against the IST6-300, 6 × 50 kVA (one size down): Power modules · rating 8 × 50 kVA against 6 × 50 kVA; Bypass module 400 kVA · 3U against 300 kVA · 3U; W × D × H 1203 × 864 × 2000 mm against 607 × 860 × 2000 mm; Weight without power modules 459 kg against 236 kg.
- Against the IST6-500, 10 × 50 kVA (one size up): Power modules · rating 8 × 50 kVA against 10 × 50 kVA; Bypass module 400 kVA · 3U against 500 kVA · 4.5U; Weight without power modules 459 kg against 506 kg.
Planning data
IST6-400, 8 × 50 kVA: currents, breakers, cables, batteries
The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the IST6-400, 8 × 50 kVA.
Four cabinets, one 50 kVA module
| Cabinet | 400 kVA |
|---|---|
| Power modules (50 kVA) | 8 |
| Bypass module | 400 kVA · 3U |
| W × D × H (mm) | 1203 × 864 × 2000 |
| Weight without power modules | 459 kg |
| Mains input current | 690 A |
| Cooling air flow (min.) | 4840 m³/h |
Site conditions and service
| Line | 400 kVA |
|---|---|
| Mains input | 690 A · 2×(4×185) |
| Bypass / output | 606 A · 2×(4×185) |
| Battery (40 blocks) | 868 A · 3×(3×185) |
| Mains breaker | 800 A 3P |
Installation
Installing the IST6-400, 8 × 50 kVA: space, heat, cables
Each figure with its source. Heat is the power lost at the peak efficiency stated.
| Item | Figure | Source |
|---|---|---|
| Clearances | front 800 mm, rear 500 mm, top 500 mm; left and right: not given | AEC user manual Table 3-1; EMEA 2026 catalogue p.157 |
| Cable entry | Bottom (standard); Top (built to order) | AEC user manual Table 3-1; EMEA 2026 catalogue p.157 |
| Cooling air | 4,840 m³/h | EMEA 2026 catalogue p.157 |
| Heat at full load | 7.75 kW at 400 kW load, 98.1 % efficiency | IST6 200–500 data (up to 98.1 %, AEC); output PF 1 (EMEA 2026 catalogue) |
| Operating temperature | 0 to 40 °C | IST6 200–500 AEC user manual |
| Switches and terminals | Mains, bypass, maintenance bypass and output switches inside the front door (single column 1,148–1,711 mm up; double column on the left, 462–1,658 mm). | IST6 200–500 user manual §3.5.1 p.43 (right-hand hinges, one door per column) |
| Door | One leaf, hinged on the right | IST6 200–500 user manual §3.5.1 p.43 (right-hand hinges, one door per column) |
| Module withdrawal | 650 mm in front of the cabinet to withdraw a module | EMEA 2026 catalogue p.143; AEC user manual A.2.1 |
| Units in parallel | Up to 8 units | AEC user manual A.1.2; EMEA 2026 catalogue p.139 |
Size and floor
How big it is
1203 × 864 × 2000 mm · 459 kg without modules.
Efficiency
How efficient is the AEC IST6-400, 8 × 50 kVA at your load?
IST6-400, 8 × 50 kVA, 400 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 2.56 kW (η 97.5%) · 50%: 3.87 kW (η 98.1%) · 75%: 6.75 kW (η 97.8%) · 100%: 10.3 kW (η 97.5%). At 50% load, 24/7, it loses about 33,933 kWh a year.
How the curve is drawn and where each figure comes from: the IST6 200–500 range page. ECO and W-ECO modes are listed without an efficiency figure.
- Load
- —
- Lost as heat
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at € per kWh
- —
- The catalogue's examples use €0.20 per kWh.
Where each figure comes from
| Mode | Efficiency | Kind | Models | Source |
|---|---|---|---|---|
| Online, double conversion | 25%: 97.5% · 50%: 98.1% · 75%: 97.8% · 100%: 97.5% | Typical curve, derived from the datasheet efficiency of 98.1% (AEC method) | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99.2% | Datasheet figure, load not stated | all | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
EMEA 2026 catalogue figures: Online, double conversion up to 98.1%.
Drag to turnIn 3D
Look around the IST6-400, 8 × 50 kVA
The turntable shows the IST6 500 kVA; the full 3D view opens on the IST6 400 kVA.
Technical data
Technical data IST6-400, 8 × 50 kVA
Only this model's values, from the EMEA 2026 catalogue table.
| Cabinet | |
|---|---|
| Power modules · rating | 8 × 50 kVA |
| Bypass module | 400 kVA · 3U |
| Input | |
| System · voltage | 3Ph+N+PE · 380 / 400 / 415 V; 138–485 V (full power 324–485 V, linear derating below) |
| Frequency · PF · THDi | 40–70 Hz · ≥ 0.99 · ≤ 1.5% at full load |
| Bypass | 304–438 V; synchronisation 50 ± 5 / 60 ± 6 Hz; settable window |
| Battery | |
| Lead-acid | ±240 V DC nominal (±180 … ±300 V), 30–50 × 12 V blocks, standard 40 |
| Lithium (with BMS card) | ±256 V DC nominal (±192 … ±294.4 V), 120–200 cells, standard 160 |
| Charging current | up to 30 A × number of modules · cold start · shared battery |
| Output | |
| System · voltage | 3Ph+N+PE (3Ph+PE optional) · 380 / 400 / 415 V ± 1% |
| Power factor · THDv | settable 0.8–1.0 (default 1.0) · ≤ 1% linear, ≤ 4% non-linear |
| Frequency · phase error | tracks the bypass; 50 / 60 ± 0.1 Hz with mains abnormal · ≤ 1° balanced, ≤ 3° unbalanced |
| Transfer | mains ↔ battery 0 ms · bypass ↔ inverter < 1 ms synchronised, < 15 ms |
| Inverter overload (PF 1) | ≤ 105% continuous · 105–110% 60 min · 110–125% 10 min · 125–150% 1 min · > 150% to bypass |
| Bypass overload | ≤ 130% continuous · 130–150% 5 min · 150–200% 1 min · 200–300% 100 ms |
| System | |
| Efficiency · modes | up to 98.1% · ECO, WECO, source share, redundancy sleep |
| Parallel | up to 8 UPS, current imbalance ≤ 5% · BSC dual bus and multi-bus (3 buses) |
| Communication | Modbus · RS232 · RS485 · 4 inputs / 3 outputs dry contact · options: SNMP, expansion, BMS |
| Environment | 0 … 40 °C · 0–95% RH · ≤ 2000 m (derating to 4000 m) · IP20 · < 70 dB · EMC C3 |
| W × D × H (mm) | 1203 × 864 × 2000 |
| Weight without power modules | 459 kg |
| Item | IST6-400, 8 × 50 kVA |
|---|---|
| Power modules (50 kVA) | 8 |
| Bypass module | 400 kVA · 3U |
| W × D × H (mm) | 1203 × 864 × 2000 |
| Weight without power modules | 459 kg |
| Mains input current | 690 A |
| Cooling air flow (min.) | 4840 m³/h |
Power module 500 × 650 × 130 mm, 39 kg. Data from the IST6 200–500 kVA user manual. Specifications are subject to change without notice.
More technical detailshow it works, ordering codes
Diagrams
How the power flows: AEC IST6-400, 8 × 50 kVA
Pick an operating mode: the path the power takes to the load lights up.
Normal. Double conversion: the rectifier feeds the DC bus, the inverter rebuilds a clean voltage and the load always runs on the inverter. The battery stays on charge. Efficiency up to 98.1% (double conversion, up to; ECO and WECO modes stated without a figure).
Battery. The mains fails: the battery feeds the DC bus and the inverter carries on without a break. The load does not notice. Transfer: mains ↔ battery 0 ms.
Bypass. Overload or internal fault: the static switch moves the load to the bypass line, fed by the mains.
ECO. The load runs on the bypass and the inverter stands ready: if the mains leaves the set window, the load goes back to the inverter. Higher efficiency, less protection.
Maintenance. The maintenance bypass feeds the load straight from the mains, so the UPS can be isolated for service without switching the load off.
Frequency converter. Output at 50 or 60 Hz whatever the input: the load always runs on the inverter and the bypass is not used.
Modules and redundancy
Move the slider: the modules the load needs light up, and the spare slot holds the N+1 redundancy. Each slot takes one 50 kVA module.
modules working · redundant · free slot
Ordering codes
Ordering codes IST6-400, 8 × 50 kVA
| Code | Description |
|---|---|
| IST6-400 | Modular cabinet, max. 8 × 50 kVA power modules, without modules |
| IST6-50-J | 50 kVA / 50 kW power module |
| PAR - IST6 | Parallel kit |
Questions
Questions about the IST6-400, 8 × 50 kVA
IST6-400 with 50 kVA modules or IST6 400 kVA with 100 kVA modules?
The IST6-400 (8 × 50 kVA, 1203 mm wide) gives finer steps and cheaper redundancy. The 400 kVA cabinet of the 400–1200 range (4 × 100 kVA, 801 mm wide) takes less floor, reaches up to 98.1% efficiency with PLUS modules and keeps the same module up to 1.2 MW.
Can the IST6-400 run on lithium batteries?
Yes, with the BMS expansion card: lithium at ±256 V DC nominal, 120 to 200 cells (standard 160). Lead-acid runs at ±240 V nominal with 30 to 50 blocks, full output from 40 blocks.
How long does a 400 kVA UPS like the IST6-400, 8 × 50 kVA run?
5 to 78 minutes at full load (400 kW), and 16 to 156 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 120 × 12 V 100 Ah · 4 × 30 (IST6-400-120X100): 5 minutes at 100% and 16 at 50%. For other loads and batteries use the backup-time tool.
How big is the AEC IST6-400, 8 × 50 kVA and how much does it weigh?
The AEC IST6-400, 8 × 50 kVA measures 1203 × 864 × 2000 mm; weight: 459 kg without modules (size from AEC's CAD drawing, weight from the EMEA 2026 catalogue).
What is the ordering code of the AEC IST6-400, 8 × 50 kVA?
In the EMEA 2026 catalogue the AEC IST6-400, 8 × 50 kVA is listed as IST6-400; AEC gives the full code, batteries included, from the load and the backup time.