IST8 · Single-phase UPS

IST8-3 Single-phase lithium UPS 3 kVA, rack 2U

Lithium3 kVAonline UPS, lithium, 2U

The IST8-3 is a 3 kVA / 3 kW single-phase online double-conversion UPS with a built-in lithium-ion battery, the most efficient IST8 at 93% AC/AC. For full racks of up to 3 kW in data rooms, telecom and industrial cabinets that want lithium in two rack units.

3 kVA / 3 kWRating
438 × 570 × 87 mm (2U)W × D × H
16.1 kgWeight

Quick answers

IST8-3: quick answers

What it is
The IST8-3 is a 3 kVA / 3 kW single-phase online double-conversion UPS with a built-in lithium-ion battery, the most efficient IST8 at 93% AC/AC.
Who it is for
For full racks of up to 3 kW in data rooms, telecom and industrial cabinets that want lithium in two rack units.
Supply and configuration
208 / 220 / 230 / 240 V
Battery and backup
lithium iron phosphate (LFP), built in · 11 min · 4 A
Size and weight
438 × 570 × 87 mm (2U) · 16.1 kg
Ordering code
IST8-3

IST8

What sets apart the IST8-3

The IST8-3 gives 3000 W from the same 2U, 570 mm chassis as the IST8-2, at 16.1 kg. Its AC/AC efficiency rises to 93% (91.5% on the smaller two), and the input stays on the mains from 120 to 295 V, so short dips and brownouts do not draw on the battery.

Overload is carried for 1 minute at 101–115% and 1 second at 116–133%; above 134% the UPS moves to bypass after 200 ms. Like every IST8 it ships with the battery connector unplugged for transport, to be connected after installation.

  • Against the IST8-2 (one size down): Power 3000 VA / 3000 W against 2000 VA / 2000 W; AC/AC efficiency 93% against 91.5%; Weight 16.1 kg against 13.6 kg.

Installation

Installing the IST8-3: space, heat, cables

Each figure with its source. Heat is the power lost at the peak efficiency stated.

IST8-3 · installation
ItemFigureSource
Clearancesrear 300 mm (recommended 500), left 300 mm (recommended 500), right 300 mm (recommended 500), top 500 mm; front: not givenIST8 user manual p.11–12, 19; EMEA 2026 catalogue p.41; IST8 user manual p.11–12; IST8 user manual p.19
Cable entryPlugs and sockets at the rearIST8 user manual p.11–12, 19; EMEA 2026 catalogue p.41
Heat at full load0.25 kW at 2.7 kW load, 91.5 % efficiencyEMEA 2026 catalogue p.39, 44 (IST8 1–2 kVA; 3 kVA 93 %)
Operating temperature0 to 40 °CEMEA 2026 catalogue p.38, 44: lithium 0–60 °C, best 0–40 °C
Switches and terminalsSockets and connections on the rear panel; lithium battery built in.IST8 user manual p.11–12, 19; EMEA 2026 catalogue p.41

Size and floor

How big it is

438 × 570 × 87 mm · 16.1 kg.

0.25 m²footprint
64 kg/m²floor load
0.09 mheight

Floor load = weight ÷ footprint (16.1 kg).

1.75 mFrontSide43857087

Backup time

How long does the AEC IST8-3 run at your load?

AEC's backup times for every ordering code: the minutes AEC publishes from 50 to 100% load, AEC's calculator below 50% and for a string you compose. Pick a battery option: the curve redraws, and every point says where it comes from.

Load50% · 1.5 kW

Loading AEC's data…

Source: AEC EMEA product data: ordering codes, cabinets, blocks and strings, and the times AEC publishes from 50 to 100% load. Below 50%, AEC's calculator (W per cell = load ÷ 96% ÷ cells, read on a straight line between the columns of the battery maker's constant-power table at 1.70 V/cell), scaled to meet the published 50% figure. Lithium: published times only. New batteries, 25 °C. AEC checks every sizing. The catalogue prints 11 minutes without the load it is measured at; AEC's own data (EU portal) gives 12 minutes at full load for all three ratings, and the minutes from 50 to 100 % load shown here.

Table: the IST8-3 minutes at 20, 50, 80 and 100% load
IST8-3: backup time in minutes at the load shown (100% = 3 kW)
BatteriesCode20%50%80%100%
built-in lithium batteryIST8-3-Li—422012

For each battery type the smallest and the largest configuration; new batteries, 25 °C. AEC published figures. Every option is in the chart and the table of codes.

All 1 ordering codes of the IST8-3 and their backup times
IST8-3: ordering codes and backup time in minutes at the load shown
CodeBatteriesCabinet100%90%80%70%60%50%
Built-in lithium battery
IST8-3-Libuilt-in lithium batteryinternal121520263342

Minutes from AEC EMEA product data: from 50 to 100% load, the times AEC publishes. The chart above adds AEC's calculation from 10 to 40%.

AEC IST8-3, rendered from its 3D modelDrag to turn

In 3D

Look around the IST8-3

Technical data

Technical data IST8-3

Only this model's values, from the EMEA 2026 catalogue table.

IST8-3 · Technical data
Rating
Power (VA / W)3000 / 3000
Input
Voltage range120–295 V AC
Frequency50 / 60 Hz ± 10%, auto-sensing
Power factor · THDi≥ 0.99 · < 5%
Input socketIEC C20
Output
Voltage208 / 220 / 230 / 240 V ± 1%, settable from the panel
Frequency (battery mode)50 / 60 Hz ± 0.1 Hz
Power factor · voltage distortion1 · THDv < 3%
Transfer time0 ms
AC/AC efficiency93%
Overload101–115% 1 min · 116–133% 1 s · > 134% 200 ms
Output sockets6 × IEC C13 + 1 × IEC C19
Battery
Typelithium iron phosphate (LFP), built in
Backup time · max. charging current11 min · 4 A
General
Operating modesonline (INV) · ECO, set from the panel
DisplayLCD, rack (RCK) or tower (TWR) reading
CommunicationUSB · intelligent slot (DB9, RS232 + dry contact as shown; optional SNMP card or RS485 + dry-contact card) · EPO
Protectionsoutput over-voltage, battery under-voltage, input over-voltage, overload, short circuit, over-temperature
Noise< 55 dB
Environment0–60 °C (best 0–40 °C; long periods at 40–60 °C may reduce the output power) · 0–95% RH non-condensing
Dimensions W × D × H (mm)438 × 570 × 87 (2U)
Weight (kg)16.1
IST8-3 · Models
ItemIST8-3
Power VA / W3000 / 3000
W × D × H (mm)438 × 570 × 87 (2U)
Weight (kg)16.1
AC/AC efficiency93%
Outlets6 × IEC C13 + 1 × IEC C19
InletIEC C20

230 V models. Specifications are subject to change without notice.

More technical detailsordering codes

Ordering codes

Ordering codes IST8-3

Ordering codes IST8-3
CodeDescription
IST8-3Online UPS 3 kVA, rack / tower, built-in lithium-ion battery
SNMPInternal SNMP card

Questions

Questions about the IST8-3

How long does the IST8-3 run on battery?

AEC's data give 12 minutes at full load and 42 at half load with the internal lithium-ion battery (the catalogue prints 11 minutes, without a load); there is no external battery option. For longer backup in a rack, look at the IST3-J with battery boxes.

What heat does the IST8-3 give off at full load?

At 3 kW and 93% efficiency the losses are about 0.23 kW (3 × (1/0.93 − 1)), heat the cabinet ventilation has to remove. Keep 300–500 mm free around the UPS and 500 mm above it, as the catalogue asks.

How long does a 3 kVA UPS like the IST8-3 run?

12 minutes at full load (3 kW), and 42 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With built-in lithium battery (IST8-3-Li): 12 minutes at 100% and 42 at 50%. For other loads and batteries use the backup-time tool.

How big is the AEC IST8-3 and how much does it weigh?

The AEC IST8-3 measures 438 × 570 × 87 mm (2U); weight: 16.1 kg (EMEA 2026 catalogue).

What is the ordering code of the AEC IST8-3?

In the EMEA 2026 catalogue the AEC IST8-3 is listed as IST8-3; AEC gives the full code, batteries included, from the load and the backup time.

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC IST8-3: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.