IST8 · Single-phase UPS
IST8-3 Single-phase lithium UPS 3 kVA, rack 2U
The IST8-3 is a 3 kVA / 3 kW single-phase online double-conversion UPS with a built-in lithium-ion battery, the most efficient IST8 at 93% AC/AC. For full racks of up to 3 kW in data rooms, telecom and industrial cabinets that want lithium in two rack units.
Quick answers
IST8-3: quick answers
- What it is
- The IST8-3 is a 3 kVA / 3 kW single-phase online double-conversion UPS with a built-in lithium-ion battery, the most efficient IST8 at 93% AC/AC.
- Who it is for
- For full racks of up to 3 kW in data rooms, telecom and industrial cabinets that want lithium in two rack units.
- Supply and configuration
- 208 / 220 / 230 / 240 V
- Battery and backup
- lithium iron phosphate (LFP), built in · 11 min · 4 A
- Size and weight
- 438 × 570 × 87 mm (2U) · 16.1 kg
- Ordering code
- IST8-3
IST8
What sets apart the IST8-3
The IST8-3 gives 3000 W from the same 2U, 570 mm chassis as the IST8-2, at 16.1 kg. Its AC/AC efficiency rises to 93% (91.5% on the smaller two), and the input stays on the mains from 120 to 295 V, so short dips and brownouts do not draw on the battery.
Overload is carried for 1 minute at 101–115% and 1 second at 116–133%; above 134% the UPS moves to bypass after 200 ms. Like every IST8 it ships with the battery connector unplugged for transport, to be connected after installation.
- Against the IST8-2 (one size down): Power 3000 VA / 3000 W against 2000 VA / 2000 W; AC/AC efficiency 93% against 91.5%; Weight 16.1 kg against 13.6 kg.
Installation
Installing the IST8-3: space, heat, cables
Each figure with its source. Heat is the power lost at the peak efficiency stated.
| Item | Figure | Source |
|---|---|---|
| Clearances | rear 300 mm (recommended 500), left 300 mm (recommended 500), right 300 mm (recommended 500), top 500 mm; front: not given | IST8 user manual p.11–12, 19; EMEA 2026 catalogue p.41; IST8 user manual p.11–12; IST8 user manual p.19 |
| Cable entry | Plugs and sockets at the rear | IST8 user manual p.11–12, 19; EMEA 2026 catalogue p.41 |
| Heat at full load | 0.25 kW at 2.7 kW load, 91.5 % efficiency | EMEA 2026 catalogue p.39, 44 (IST8 1–2 kVA; 3 kVA 93 %) |
| Operating temperature | 0 to 40 °C | EMEA 2026 catalogue p.38, 44: lithium 0–60 °C, best 0–40 °C |
| Switches and terminals | Sockets and connections on the rear panel; lithium battery built in. | IST8 user manual p.11–12, 19; EMEA 2026 catalogue p.41 |
Size and floor
How big it is
438 × 570 × 87 mm · 16.1 kg.
Floor load = weight ÷ footprint (16.1 kg).
Backup time
How long does the AEC IST8-3 run at your load?
AEC's backup times for every ordering code: the minutes AEC publishes from 50 to 100% load, AEC's calculator below 50% and for a string you compose. Pick a battery option: the curve redraws, and every point says where it comes from.
Loading AEC's data…
Source: AEC EMEA product data: ordering codes, cabinets, blocks and strings, and the times AEC publishes from 50 to 100% load. Below 50%, AEC's calculator (W per cell = load ÷ 96% ÷ cells, read on a straight line between the columns of the battery maker's constant-power table at 1.70 V/cell), scaled to meet the published 50% figure. Lithium: published times only. New batteries, 25 °C. AEC checks every sizing. The catalogue prints 11 minutes without the load it is measured at; AEC's own data (EU portal) gives 12 minutes at full load for all three ratings, and the minutes from 50 to 100 % load shown here.
Table: the IST8-3 minutes at 20, 50, 80 and 100% load
| Batteries | Code | 20% | 50% | 80% | 100% |
|---|---|---|---|---|---|
| built-in lithium battery | IST8-3-Li | — | 42 | 20 | 12 |
For each battery type the smallest and the largest configuration; new batteries, 25 °C. AEC published figures. Every option is in the chart and the table of codes.
All 1 ordering codes of the IST8-3 and their backup times
| Code | Batteries | Cabinet | 100% | 90% | 80% | 70% | 60% | 50% |
|---|---|---|---|---|---|---|---|---|
| Built-in lithium battery | ||||||||
| IST8-3-Li | built-in lithium battery | internal | 12 | 15 | 20 | 26 | 33 | 42 |
Minutes from AEC EMEA product data: from 50 to 100% load, the times AEC publishes. The chart above adds AEC's calculation from 10 to 40%.
Efficiency
How efficient is the AEC IST8-3 at your load?
IST8-3, 3 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 50%: 0.14 kW (η 91.55%) · 75%: 0.17 kW (η 93%) · 100%: 0.23 kW (η 92.8%). At 50% load, 24/7, it loses about 1,213 kWh a year.
How the curve is drawn and where each figure comes from: the IST8 range page. ECO mode is set from the panel; the catalogue gives no efficiency figure for it.
- Load
- —
- Lost as heat
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at € per kWh
- —
- The catalogue's examples use €0.20 per kWh.
Where each figure comes from
| Mode | Efficiency | Kind | Models | Source |
|---|---|---|---|---|
| Online, double conversion | 30%: 90.54% · 50%: 91.55% · 75%: 93% · 100%: 92.8% | Typical curve, derived from the datasheet efficiency of 93% (AEC method) | IST8-3 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 86.81% · 50%: 89.37% · 75%: 90.73% · 100%: 91.5% | Typical curve, derived from the datasheet efficiency of 91.5% (AEC method) | IST8-1 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
| Online, double conversion | 30%: 88.3% · 50%: 90.17% · 75%: 91.1% · 100%: 91.5% | Typical curve, derived from the datasheet efficiency of 91.5% (AEC method) | IST8-2 | AEC technical datasheet IST3-J 1–3 kVA: AC/AC efficiency |
EMEA 2026 catalogue figures: Online, double conversion up to 91.5% · Online, double conversion up to 93%.
Drag to turnTechnical data
Technical data IST8-3
Only this model's values, from the EMEA 2026 catalogue table.
| Rating | |
|---|---|
| Power (VA / W) | 3000 / 3000 |
| Input | |
| Voltage range | 120–295 V AC |
| Frequency | 50 / 60 Hz ± 10%, auto-sensing |
| Power factor · THDi | ≥ 0.99 · < 5% |
| Input socket | IEC C20 |
| Output | |
| Voltage | 208 / 220 / 230 / 240 V ± 1%, settable from the panel |
| Frequency (battery mode) | 50 / 60 Hz ± 0.1 Hz |
| Power factor · voltage distortion | 1 · THDv < 3% |
| Transfer time | 0 ms |
| AC/AC efficiency | 93% |
| Overload | 101–115% 1 min · 116–133% 1 s · > 134% 200 ms |
| Output sockets | 6 × IEC C13 + 1 × IEC C19 |
| Battery | |
| Type | lithium iron phosphate (LFP), built in |
| Backup time · max. charging current | 11 min · 4 A |
| General | |
| Operating modes | online (INV) · ECO, set from the panel |
| Display | LCD, rack (RCK) or tower (TWR) reading |
| Communication | USB · intelligent slot (DB9, RS232 + dry contact as shown; optional SNMP card or RS485 + dry-contact card) · EPO |
| Protections | output over-voltage, battery under-voltage, input over-voltage, overload, short circuit, over-temperature |
| Noise | < 55 dB |
| Environment | 0–60 °C (best 0–40 °C; long periods at 40–60 °C may reduce the output power) · 0–95% RH non-condensing |
| Dimensions W × D × H (mm) | 438 × 570 × 87 (2U) |
| Weight (kg) | 16.1 |
| Item | IST8-3 |
|---|---|
| Power VA / W | 3000 / 3000 |
| W × D × H (mm) | 438 × 570 × 87 (2U) |
| Weight (kg) | 16.1 |
| AC/AC efficiency | 93% |
| Outlets | 6 × IEC C13 + 1 × IEC C19 |
| Inlet | IEC C20 |
230 V models. Specifications are subject to change without notice.
More technical detailsordering codes
Ordering codes
Ordering codes IST8-3
| Code | Description |
|---|---|
| IST8-3 | Online UPS 3 kVA, rack / tower, built-in lithium-ion battery |
| SNMP | Internal SNMP card |
Questions
Questions about the IST8-3
How long does the IST8-3 run on battery?
AEC's data give 12 minutes at full load and 42 at half load with the internal lithium-ion battery (the catalogue prints 11 minutes, without a load); there is no external battery option. For longer backup in a rack, look at the IST3-J with battery boxes.
What heat does the IST8-3 give off at full load?
At 3 kW and 93% efficiency the losses are about 0.23 kW (3 × (1/0.93 − 1)), heat the cabinet ventilation has to remove. Keep 300–500 mm free around the UPS and 500 mm above it, as the catalogue asks.
How long does a 3 kVA UPS like the IST8-3 run?
12 minutes at full load (3 kW), and 42 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With built-in lithium battery (IST8-3-Li): 12 minutes at 100% and 42 at 50%. For other loads and batteries use the backup-time tool.
How big is the AEC IST8-3 and how much does it weigh?
The AEC IST8-3 measures 438 × 570 × 87 mm (2U); weight: 16.1 kg (EMEA 2026 catalogue).
What is the ordering code of the AEC IST8-3?
In the EMEA 2026 catalogue the AEC IST8-3 is listed as IST8-3; AEC gives the full code, batteries included, from the load and the backup time.
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need for the AEC IST8-3: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.