FERRUS SP · 120/240V split-phase UPS
FERSP10000-16X9 FERRUS SP 10 kVA, 120/240V split-phase UPS
The AEC FERRUS SP FERSP10000-16X9 is a 10 kVA / 10 kW online double-conversion UPS for 120/240 V split-phase loads, with internal VRLA batteries. Kept at 80 % of its rating, it carries loads up to 8 kW.
Drag to turnThe same on every FERRUS SP:The FERRUS SP display
Load by load
The FERSP10000-16X9 at 25, 50, 75 and 100 % load.
Its 10 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current on each leg | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|
| 25 % of the FERSP10000-16X9, 2.5 kW | 10.4 A on each leg | 90.8 % efficient | 253 W of heat | 860 BTU/h to cool |
| 50 % of the FERSP10000-16X9, 5.0 kW | 20.8 A on each leg | 92.8 % efficient | 388 W of heat | 1,320 BTU/h to cool |
| 75 % of the FERSP10000-16X9, 7.5 kW | 31.3 A on each leg | 93.0 % efficient | 565 W of heat | 1,930 BTU/h to cool |
| 100 % of the FERSP10000-16X9, 10 kW | 41.7 A on each leg | 92.8 % efficient | 776 W of heat | 2,650 BTU/h to cool |
Current = kVA × load ÷ volts.
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the FERSP10000-16X9 at your load?
The FERSP10000-16X9 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
From the 2026 catalog
What is the FERSP10000-16X9?
- Output: 10,000 VA / 10,000 W (unity power factor, kVA = kW).
- Battery: internal VRLA, 16 × 12 V 9 Ah.
The lines every FERRUS SP shares, from technology to warranty, are in the FERRUS SP key facts and in the datasheet below.
Size and floor
How big it is
9.9" W × 23.6" D × 29" H (252 × 599 × 738 mm); 235.9 lb (107 kg) net. It ships in one carton of 15.4 × 28.3 × 37 in, 264.6 lb (120 kg) gross.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
What does the FERRUS SP need in the room?
From the AEC US user manual of the FERRUS SP. Where the manual gives no distance, none is printed here: ask AEC.
- Clearances
- 19.7 in (500 mm) free on all four sides; front and rear vents open.
- Wiring
- Hardwired: an electrician connects it to the panel.
- Cable entry
- From below into the rear terminal cover (No space for the cable bend is given)
- Breakers and terminals
- Input breakers, maintenance bypass switch and terminal strip on the rear panel; terminals 17.0 in (433 mm) above the floor.
- Units in parallel
- Up to 3 of the same model.
Datasheet
FERSP10000-16X9 datasheet.
The FERSP10000-16X9 in the AEC 2026 catalog, figure by figure. Compare it with every FERRUS SP model.
| Parameter | FERSP10000-16X9 |
|---|---|
| Power | |
| Rated power (kVA) | 10 |
| Active power (kW) | 10 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 120/240 V split-phase |
| Topology | Online Double Conversion |
| Efficiency, up to | 93% |
| Battery DC bus | 192 V DC |
| Battery and runtime | |
| Battery type | VRLA (sealed lead-acid) |
| Battery configuration | Internal |
| Runtime at 50 % load | 7.5 min |
| Runtime at 100 % load | 3.2 min |
| Mechanical | |
| Form factor | Tower |
| Dimensions W × D × H | 9.9 × 23.6 × 29 in (252 × 599 × 738 mm) |
| Net weight | 235.9 lb (107 kg) |
| Footprint | 1.6 ft² (0.15 m²) |
| Shipping | |
| Cartons | 1 |
| Shipping weight | 264.6 lb |
| Common to every FERRUS SP | |
| Comms | RS-232, EPO and USB, standard |
| Battery, FERSP10000-16X9 | internal VRLA, 16 × 12V 9Ah |
| Network card | SNMP-M (SNMP) |
| Warranty | 3 years on UPS · 2 years on VRLA batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The FERRUS SP documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
User manuals
FERRUS SP 6–10 kVA: User manual (US, 2026)User manual · English · PDF · 6.8 MBDownload
FERRUS SP 6–10 kVA: Quick installation guide (US, 2026)User manual · English · PDF · 1.5 MBDownload
FERRUS SP 20 kVA: Quick installation guide (US, 2026)User manual · English · PDF · 1.4 MBDownload
FERRUS SP 20 kVA: User manual (40X9, EMPTY, EXT; US, 2026)User manual · English · PDF · 8.0 MBDownload
Quick answers
FERSP10000-16X9: what people ask
What is the output current of the FERSP10000-16X9?
41.7 A on each line at 240 V at full load: 10 kVA ÷ 240 V. Size the input breaker and the cables of the FERSP10000-16X9 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the FERSP10000-16X9 give off?
About 776 W, 2,650 BTU/h, at full load, where it is 92.8% efficient. Plan the room's cooling for a little more than that: the FERSP10000-16X9 is less efficient at part load and while its battery recharges.
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
FERRUS SP
Other FERRUS SP models
By power, the FERSP10000-16X9 is number 2 of 3 in the FERRUS SP series, which runs from 6 to 20 kVA. One size down is the FERSP6000-16X9 (4 kVA less and 40 lb lighter). One size up is the FERSP20000-40X9 (10 kVA more and 216 lb heavier).
Every FERRUS SP model side by side (3)
| Model | Power | Power against this model | Net weight | Weight against this model | Runtime at 50 % load |
|---|---|---|---|---|---|
| FERSP6000-16X9 | 6 kVA | 4 kVA less | 196 lb | 40 lb lighter | 14.3 min at 50 % load |
| FERSP10000-16X9 | 10 kVA | this page | 236 lb | this page | 7.5 min at 50 % load |
| FERSP20000-40X9 | 20 kVA | 10 kVA more | 452 lb | 216 lb heavier | 10 min at 50 % load |
Install and run it:FERRUS SP operating guide
The FERSP10000-16X9 for your project
Send the load, the voltage and the minutes you need from the FERSP10000-16X9. We reply with the configuration, the batteries and the lead time.