INFINITE · L6 lithium · 480 V three-phase

INFINITE with L6 lithium cabinets, 100 to 600 kVA

The 2026 catalog lists seven codes that order an AEC INFINITE UPS together with its L6 lithium cabinets, from 100 to 600 kVA at 480 V. One cabinet of 20 modules runs 200 kW for 15 minutes or 100 kW for 30 minutes. The tables below give each code's minutes, floor area, weight and parts.

Runtime

How long does each set run?

New batteries, at the start of life. The minutes are the modules' usable energy, 2.5 kWh each in a 15-minute discharge, divided by the load. A battery gives less in a fast discharge, so read the light-load columns as an upper bound.

Ordering codeFull loadPower modulesL6 cabinets50 Ah modulesUsable energyAt 100% loadAt 75%At 50%At 25%
INF-100+L6-CAB-10x50LI100 kW1 × 100 kVA1 × L6-CAB-10x50LI1025 kWh15 min20 min30 min60 min
INF-100+L6-CAB-20x50LI100 kW1 × 100 kVA1 × L6-CAB-20x50LI2050 kWh30 min40 min60 min120 min
INF-100+1+L6-CAB-20x50LI100 kW2 × 100 kVA, N+11 × L6-CAB-20x50LI2050 kWh30 min40 min60 min120 min
INF-200+L6-CAB-20x50LI200 kW2 × 100 kVA1 × L6-CAB-20x50LI2050 kWh15 min20 min30 min60 min
INF-200+1+L6-CAB-20x50LI200 kW3 × 100 kVA, N+11 × L6-CAB-20x50LI2050 kWh15 min20 min30 min60 min
INF-400+2xL6-CAB-20x50LI400 kW4 × 100 kVA2 × L6-CAB-20x50LI40100 kWh15 min20 min30 min60 min
INF-600+3xL6-CAB-20x50LI600 kW6 × 100 kVA3 × L6-CAB-20x50LI60150 kWh15 min20 min30 min60 min

Each 50 Ah module delivers up to 10 kW, so a set needs at least one module for every 10 kW of load. For other minutes or a load in between: how to size L6 cabinets, or the UPS sizing tool.

Floor and weight

What does each set put on the floor?

Every cabinet is 23.6 in (600 mm) wide. Floor area is width × depth of the cabinets, before the clearances of the installation manual. The last weight column is one L6 cabinet's net weight over its own footprint: the figure to give the structural engineer.

Ordering codeCabinets (UPS + L6)Floor areaNet weight of the setEach UPS cabinetEach L6 cabinetL6 cabinet over its footprintCartons
INF-100+L6-CAB-10x50LI1 + 111.9 ft² (1.11 m²)1,808 lb (820 kg)452 lb (205 kg)1,356 lb (615 kg)247 lb/ft² (1,206 kg/m²)12
INF-100+L6-CAB-20x50LI1 + 111.9 ft² (1.11 m²)2,624 lb (1,190 kg)452 lb (205 kg)2,172 lb (985 kg)396 lb/ft² (1,931 kg/m²)22
INF-100+1+L6-CAB-20x50LI1 + 111.9 ft² (1.11 m²)2,743 lb (1,244 kg)571 lb (259 kg)2,172 lb (985 kg)396 lb/ft² (1,931 kg/m²)23
INF-200+L6-CAB-20x50LI1 + 111.9 ft² (1.11 m²)2,763 lb (1,253 kg)591 lb (268 kg)2,172 lb (985 kg)396 lb/ft² (1,931 kg/m²)22
INF-200+1+L6-CAB-20x50LI1 + 111.9 ft² (1.11 m²)2,882 lb (1,307 kg)710 lb (322 kg)2,172 lb (985 kg)396 lb/ft² (1,931 kg/m²)23
INF-400+2xL6-CAB-20x50LI2 + 223.9 ft² (2.22 m²)5,526 lb (2,506 kg)591 lb (268 kg)2,172 lb (985 kg)396 lb/ft² (1,931 kg/m²)44
INF-600+3xL6-CAB-20x50LI3 + 3 + 1 combiner39.5 ft² (3.67 m²)8,597 lb (3,900 kg)591 lb (268 kg)2,172 lb (985 kg)396 lb/ft² (1,931 kg/m²)67

Place the cabinets in your room with Room fit

What ships

What does each code order?

The catalog's own bill of each code. An L6 cabinet travels as one crate with its modules in a carton each. Every L6 cabinet has its BMS with a 7-inch display and a smoke detector; every INFINITE frame has its input, output and bypass breakers built in, with cable entry from the top.

Ordering codeCatalog itemsWhat they are
INF-100+L6-CAB-10x50LI1 × INF-100 + 1 × L6-CAB-10x50LI1 × 100 kVA UPS; 1 × L6 lithium cabinet with 10 LiFePO4 modules of 50 Ah
INF-100+L6-CAB-20x50LI1 × INF-100 + 1 × L6-CAB-20x50LI1 × 100 kVA UPS; 1 × L6 lithium cabinet with 20 LiFePO4 modules of 50 Ah
INF-100+1+L6-CAB-20x50LI1 × INF-100 + 1 × INFINITE-PWR-100 + 1 × L6-CAB-20x50LI1 × 100 kVA UPS; 1 × 100 kVA hot-swappable power module; 1 × L6 lithium cabinet with 20 LiFePO4 modules of 50 Ah
INF-200+L6-CAB-20x50LI1 × INF-200 + 1 × L6-CAB-20x50LI1 × 200 kVA UPS; 1 × L6 lithium cabinet with 20 LiFePO4 modules of 50 Ah
INF-200+1+L6-CAB-20x50LI1 × INF-200 + 1 × INFINITE-PWR-100 + 1 × L6-CAB-20x50LI1 × 200 kVA UPS; 1 × 100 kVA hot-swappable power module; 1 × L6 lithium cabinet with 20 LiFePO4 modules of 50 Ah
INF-400+2xL6-CAB-20x50LI1 × INF-400 + 2 × L6-CAB-20x50LI1 × 400 kVA UPS; 2 × L6 lithium cabinet with 20 LiFePO4 modules of 50 Ah
INF-600+3xL6-CAB-20x50LI1 × INF-600 + 3 × L6-CAB-20x50LI + 1 × L6-COMBINER1 × 600 kVA UPS; 3 × L6 lithium cabinet with 20 LiFePO4 modules of 50 Ah; 1 × L6 combiner cabinet

The codes with +1 carry one 100 kVA power module more than the rating needs. One module can fail or be changed and the others still carry the full load; the battery and the minutes are those of the set without the spare, and the UPS weighs 119 lb more.

The INF-100+L6-CAB-10x50LI fills 10 of the cabinet's 20 slots. Ten more L6-MOD-50LI modules, added with the load on, bring it to the 30 minutes at 100 kW of the INF-100+L6-CAB-20x50LI.

Against lead-acid

What does the L6 cabinet replace?

For the same INFINITE and the same minutes at full load, the catalog also lists a lead-acid (VRLA) bank. The table sets that bank and the number of its cabinets beside the L6 cabinets and the floor they take.

Load and minutesL6 cabinetsTheir floor areaLead-acid bankIts cabinetsCatalog runtime of the bank
100 kW for 15 min1 × L6-CAB-10x50LI5.5 ft² (0.51 m²)40 × 12 V 200 Ah1 × BC-G40-20019 min
100 kW for 30 min1 × L6-CAB-20x50LI5.5 ft² (0.51 m²)80 × 12 V 150 Ah2 × BC-G40-15035 min
200 kW for 15 min1 × L6-CAB-20x50LI5.5 ft² (0.51 m²)80 × 12 V 200 Ah2 × BC-G40-20019 min
400 kW for 15 min2 × L6-CAB-20x50LI11.0 ft² (1.02 m²)160 × 12 V 200 Ah4 × BC-G40-20019 min
600 kW for 15 min3 × L6-CAB-20x50LI16.5 ft² (1.53 m²)200 × 12 V 200 Ah5 × BC-G40-20015 min

Life, temperature and replacement cycles of the two chemistries: lithium or lead-acid for a UPS. The cabinet itself: L6 lithium cabinets.

How many VRLA sets the same years would take at your room temperature: lithium or VRLA.

The 50 Ah LiFePO4 battery modules are certified to UL 1973 and UL 9540A tested: the modules' own certification, not a listing of the cabinet or of the system.

Currents

What current does each rating draw?

Output current per phase at full load is kVA × 1,000 ÷ (√3 × 480 V). The battery side works at 480 V DC, and the INFINITE charger is settable up to 120 A.

RatingOutput current per phase at 480 V
100 kVA120.3 A
200 kVA240.6 A
400 kVA481.1 A
600 kVA721.7 A

Size the breakers and the cables from the installation manual and the local electrical code, not from these figures alone: INFINITE installation, INFINITE operating guide, L6 lithium cabinet guide.

The UPS on its own, with its datasheet: INF-100, INF-100+1, INF-200, INF-200+1, INF-400, INF-600.

Need other minutes or another load?

Send the load in kW and the minutes. We answer with the INFINITE, the number of L6 cabinets and modules, and the floor they take.