INFINITE · 480V three-phase UPS
INF-100 INFINITE 100 kVA, 480V three-phase UPS
The AEC INFINITE INF-100 is a 100 kVA / 100 kW online double-conversion UPS for 480 V three-phase loads, built on one 100 kVA power module, with external VRLA or lithium cabinets. Kept at 80 % of its rating, it carries loads up to 80 kW.
3-wire · Delta480 V 3-wire, delta: three phases and ground, no neutral
Drag to turnThe same on every INFINITE:Open the INFINITE: modules and door, from the catalog's photosThe INFINITE display
Runtime
The INF-100 with its batteries, at your load.
The INF-100 has no batteries of its own: the chart draws in bold the catalog set-ups built on it, the other INFINITE set-ups faded behind. The same chart as the INFINITE page. 2026 catalog, new batteries.
At 50 % of the rating
INFINITE 100 kVA N+1
1 L6 cabinet, 20 lithium modules60 minINFINITE 100 kVA
half L6 cabinet, 10 modules30 min1 L6 cabinet, 20 lithium modules60 minINFINITE 200 kVA N+1
1 L6 cabinet, 20 lithium modules30 minINFINITE 200 kVA
1 L6 cabinet, 20 lithium modules30 minINFINITE 400 kVA
2 L6 cabinets, 40 lithium modules30 minINFINITE 600 kVA
3 L6 cabinets, 60 lithium modules30 minTable: this model at 25, 50, 75 and 100 % load
| Model | 25% load | 50% load | 75% load | 100% load |
|---|---|---|---|---|
| INFINITE 100 kVA N+1 · 1 L6 cabinet, 20 lithium modulesINF-100+1+L6-CAB-20x50LI | 120 min | 60 min | 40 min | 30 min |
| INFINITE 100 kVA · half L6 cabinet, 10 modulesINF-100+L6-CAB-10x50LI | 60 min | 30 min | 20 min | 15 min |
| INFINITE 100 kVA · 1 L6 cabinet, 20 lithium modulesINF-100+L6-CAB-20x50LI | 120 min | 60 min | 40 min | 30 min |
Load by load
The INF-100 at 25, 50, 75 and 100 % load.
Its 100 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current per phase, at 480 V | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|
| 25 % of the INF-100, 25 kW | 30.1 A per phase | 96.9 % efficient | 800 W of heat | 2,730 BTU/h to cool |
| 50 % of the INF-100, 50 kW | 60.1 A per phase | 97.3 % efficient | 1.4 kW of heat | 4,730 BTU/h to cool |
| 75 % of the INF-100, 75 kW | 90.2 A per phase | 97.3 % efficient | 2.1 kW of heat | 7,100 BTU/h to cool |
| 100 % of the INF-100, 100 kW | 120 A per phase | 97.3 % efficient | 2.8 kW of heat | 9,470 BTU/h to cool |
Current = kVA × load ÷ (√3 × volts).
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the INF-100 at your load?
The INF-100 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
Sizing
What load fits the INF-100?
Its minutes on battery depend on the batteries chosen with it: send the load in kW and the minutes you need, and AEC sizes the bank for the INF-100.
The INF-100 runs on one 100 kVA power module, which carries the rating with no spare; for N+1 redundancy at the same 100 kVA, the INF-100+1 adds one more.
From the 2026 catalog
What is the INF-100?
The code INF-100 orders these catalog items:
- 1 × INF-FRAME-100: 100 kVA frame, without power modules, 23.6 × 39.4 × 81.4 in (600 × 1,000 × 2,068 mm)
- 1 × INFINITE-PWR-100: 100 kVA hot-swappable power module, 119 lb (54 kg)
- Architecture: 1 × 100 kVA hot-swappable power module in a 100 kVA frame.
- Technology: Silicon-Carbide (SiC) semiconductors; unity power factor; 120 A settable charger; up to 3 frames in parallel (600 kVA).
- Input / Output: 480 V three-phase, 3-wire.
- Efficiency: up to 97.3%.
- Display: 7-inch color touchscreen.
- Comms: RS232, RS485/Modbus, EPO and dry contacts standard; SNMP card optional.
- Battery: external, lead-acid (30–50 blocks) or AEC L6 lithium cabinets.
- Warranty: 3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries.
Size and floor
How big it is
23.6" W × 39.4" D × 81.4" H (600 × 1,000 × 2,068 mm); 452.2 lb (205.1 kg) net.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
The INF-100 takes the clearances, wiring, cable entry and breakers of every INFINITE model, from its AEC US user manual: see them on the INFINITE page.
Datasheet
INF-100 datasheet.
The INF-100 in the AEC 2026 catalog, figure by figure. Compare it with every INFINITE model.
| Parameter | INF-100 |
|---|---|
| Power | |
| Rated power (kVA) | 100 |
| Active power (kW) | 100 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 480 V three-phase, 3-wire (delta) |
| Topology | Online double conversion, modular |
| Efficiency, up to | 97.3% |
| Battery DC bus | 480 V DC |
| Battery and runtime | |
| Battery type | VRLA or lithium LiFePO4 |
| Battery configuration | External VRLA bank or L6 lithium cabinets |
| Mechanical | |
| Form factor | Modular |
| Dimensions W × D × H | 23.6 × 39.4 × 81.4 in (600 × 1,000 × 2,068 mm) |
| Net weight | 452.2 lb (205.1 kg) |
| Footprint | 6.5 ft² (0.60 m²) |
| Common to every INFINITE | |
| Technology | Silicon-Carbide (SiC) semiconductors; unity power factor; 120 A settable charger; up to 3 frames in parallel (600 kVA) |
| Display | 7-inch color touchscreen |
| Comms | RS232, RS485/Modbus, EPO and dry contacts standard; SNMP card optional |
| Battery, INF-100 | external, lead-acid (30–50 blocks) or AEC L6 lithium cabinets |
| Use | 100 to 600 kVA: one 100 or 200 kVA frame, or up to three 200 kVA frames in parallel; above 600 kVA, INFINITE 1.5MW |
| Network card | SNMP-L (SNMP) |
| Warranty | 3 years on UPS, 5 if registered · 5 years on lithium cabinets incl. batteries |
| Quality system | ISO 9001:2015, the group's quality system (SGS) |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
Manuals and catalogs.
The INFINITE documents cover every model of the series, this one included. PDF, in English.
Catalogs and datasheets
Quick answers
INF-100: what people ask
What is the output current of the INF-100?
120.3 A per phase at full load: 100 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the INF-100 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the INF-100 give off?
About 2.8 kW, 9,470 BTU/h, at full load, where it is 97.3% efficient. Plan the room's cooling for a little more than that: the INF-100 is less efficient at part load and while its battery recharges.
Will the INF-100 fit through a standard door?
Not upright through a standard 36 × 80-inch door, which clears about 79 in in height: at 81.4 in (2,068 mm) high it needs an opening taller than 81.4 in. Check elevators and the floor load on the way in too.
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
INFINITE
Other INFINITE models
By power, the INF-100 is the smallest in the INFINITE series, which runs from 100 to 600 kVA. One size up are the INF-200, INF-200+1, INF-200+1+L6-CAB-20x50LI and INF-200+L6-CAB-20x50LI, all 100 kVA more. The same 100 kVA also comes as the INF-100+1, INF-100+1+L6-CAB-20x50LI, INF-100+L6-CAB-10x50LI and INF-100+L6-CAB-20x50LI: the table below gives each one's weight and battery.
Every INFINITE model side by side (13)
| Model | Power | Power against this model | Net weight | Weight against this model | Battery configuration |
|---|---|---|---|---|---|
| INF-100 | 100 kVA | this page | 452 lb | this page | External VRLA bank or L6 lithium cabinets |
| INF-100+1 | 100 kVA | the same power | 571 lb | 119 lb heavier | External VRLA bank or L6 lithium cabinets |
| INF-100+1+L6-CAB-20x50LI | 100 kVA | the same power | 2,743 lb | 2,291 lb heavier | External L6 lithium cabinets |
| INF-100+L6-CAB-10x50LI | 100 kVA | the same power | 1,808 lb | 1,356 lb heavier | External L6 lithium cabinets |
| INF-100+L6-CAB-20x50LI | 100 kVA | the same power | 2,624 lb | 2,172 lb heavier | External L6 lithium cabinets |
| INF-200 | 200 kVA | 100 kVA more | 591 lb | 139 lb heavier | External VRLA bank or L6 lithium cabinets |
| INF-200+1 | 200 kVA | 100 kVA more | 710 lb | 258 lb heavier | External VRLA bank or L6 lithium cabinets |
| INF-200+1+L6-CAB-20x50LI | 200 kVA | 100 kVA more | 2,882 lb | 2,430 lb heavier | External L6 lithium cabinets |
| INF-200+L6-CAB-20x50LI | 200 kVA | 100 kVA more | 2,763 lb | 2,311 lb heavier | External L6 lithium cabinets |
| INF-400 | 400 kVA | 300 kVA more | 1,183 lb | 730 lb heavier | External VRLA bank or L6 lithium cabinets |
| INF-400+2xL6-CAB-20x50LI | 400 kVA | 300 kVA more | 5,526 lb | 5,074 lb heavier | External L6 lithium cabinets |
| INF-600 | 600 kVA | 500 kVA more | 1,774 lb | 1,322 lb heavier | External VRLA bank or L6 lithium cabinets |
| INF-600+3xL6-CAB-20x50LI | 600 kVA | 500 kVA more | 8,597 lb | 8,145 lb heavier | External L6 lithium cabinets |
The INF-100 for your project
Send the load, the voltage and the minutes you need from the INF-100. We reply with the configuration, the batteries and the lead time.