INFINITE · 480V three-phase UPS
INF-100+1 INFINITE 100 kVA, 480V three-phase UPS
The AEC INFINITE INF-100+1 is a 100 kVA / 100 kW online double-conversion UPS for 480 V three-phase loads, built on two 100 kVA power modules (N+1), with external VRLA or lithium cabinets. Kept at 80 % of its rating, it carries loads up to 80 kW.
3-wire · Delta480 V 3-wire, delta: three phases and ground, no neutral
Drag to turnIn 3D
Look around the INF-100+1
The turntable shows the 100 kVA, 1 power module configuration; the full 3D view opens on this model.
The same on every INFINITE:Open the INFINITE: modules and door, from the catalog's photosThe INFINITE display
Runtime
The INF-100+1 with its batteries, at your load.
The INF-100+1 has no batteries of its own: the chart draws in bold the catalog set-ups built on it, the other INFINITE set-ups faded behind. The same chart as the INFINITE page. 2026 catalog, new batteries.
At 50 % of the rating
INFINITE 100 kVA N+1
1 L6 cabinet, 20 lithium modules60 minINFINITE 100 kVA
half L6 cabinet, 10 modules30 min1 L6 cabinet, 20 lithium modules60 minINFINITE 200 kVA N+1
1 L6 cabinet, 20 lithium modules30 minINFINITE 200 kVA
1 L6 cabinet, 20 lithium modules30 minINFINITE 400 kVA
2 L6 cabinets, 40 lithium modules30 minINFINITE 600 kVA
3 L6 cabinets, 60 lithium modules30 minTable: this model at 25, 50, 75 and 100 % load
| Model | 25% load | 50% load | 75% load | 100% load |
|---|---|---|---|---|
| INFINITE 100 kVA N+1 · 1 L6 cabinet, 20 lithium modulesINF-100+1+L6-CAB-20x50LI | 120 min | 60 min | 40 min | 30 min |
Load by load
The INF-100+1 at 25, 50, 75 and 100 % load.
Its 100 kW rating in four steps, worked out from its own catalog figures.
| Load | Output current per phase, at 480 V | Load on each of its 2 power modules | Efficiency | Heat to remove | Heat to remove (BTU/h) |
|---|---|---|---|---|---|
| 25 % of the INF-100+1, 25 kW | 30.1 A per phase | 13 % on each module | 96.9 % efficient | 800 W of heat | 2,730 BTU/h to cool |
| 50 % of the INF-100+1, 50 kW | 60.1 A per phase | 25 % on each module | 97.3 % efficient | 1.4 kW of heat | 4,730 BTU/h to cool |
| 75 % of the INF-100+1, 75 kW | 90.2 A per phase | 38 % on each module | 97.3 % efficient | 2.1 kW of heat | 7,100 BTU/h to cool |
| 100 % of the INF-100+1, 100 kW | 120 A per phase | 50 % on each module | 97.3 % efficient | 2.8 kW of heat | 9,470 BTU/h to cool |
Current = kVA × load ÷ (√3 × volts).
Module load = load ÷ the kVA of the power modules fitted.
Heat = load × (100 ÷ efficiency − 1); 1 kW is 3,412 BTU/h.
Efficiency
How efficient is the INF-100+1 at your load?
The INF-100+1 in normal double-conversion mode, from the 2026 catalog's efficiency curve. Drag along it to see the heat lost and its yearly cost.
- Load
- —
- Lost as heat
- —
- Heat to remove
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at per kWh
- —
Sizing
What load fits the INF-100+1?
Its minutes on battery depend on the batteries chosen with it: send the load in kW and the minutes you need, and AEC sizes the bank for the INF-100+1.
Its two 100 kVA power modules give 200 kVA for a 100 kVA rating: if one module fails or is swapped, the others still carry the full 100 kW (N+1).
From the 2026 catalog
What is the INF-100+1?
The code INF-100+1 orders these catalog items, shipped in 2 cartons:
- 1 × INF-100: 100 kVA UPS, 23.6 × 39.4 × 81.4 in (600 × 1,000 × 2,068 mm), 452.2 lb (205.1 kg)
- 1 × INFINITE-PWR-100: 100 kVA hot-swappable power module, 119 lb (54 kg)
- Architecture: 2 × 100 kVA hot-swappable power modules in a 100 kVA frame.
Its other catalog lines are those of the INF-100, built in the same frame: see them on its page.
Size and floor
How big it is
23.6" W × 39.4" D × 81.4" H (600 × 1,000 × 2,068 mm); 571.3 lb (259.1 kg) net.
Floor load = net weight ÷ footprint, without batteries outside the cabinet.
Installation
The INF-100+1 takes the clearances, wiring, cable entry and breakers of every INFINITE model, from its AEC US user manual: see them on the INFINITE page.
Place the INF-100+1 in your room, to the inch, with Room fit
Datasheet
INF-100+1 datasheet.
The INF-100+1 in the AEC 2026 catalog, figure by figure. Compare it with every INFINITE model.
| Parameter | INF-100+1 |
|---|---|
| Power | |
| Rated power (kVA) | 100 |
| Active power (kW) | 100 |
| Output power factor | 1.0 |
| Electrical | |
| Input / output | 480 V three-phase, 3-wire (delta) |
| Topology | Online double conversion, modular N+1 |
| Efficiency, up to | 97.3% |
| Battery DC bus | 480 V DC |
| Battery and runtime | |
| Battery type | VRLA or lithium LiFePO4 |
| Battery configuration | External VRLA bank or L6 lithium cabinets |
| Mechanical | |
| Form factor | Modular |
| Dimensions W × D × H | 23.6 × 39.4 × 81.4 in (600 × 1,000 × 2,068 mm) |
| Net weight | 571.3 lb (259.1 kg) |
| Footprint | 6.5 ft² (0.60 m²) |
| Common to every INFINITE | |
| Battery, INF-100+1 | external, lead-acid (30–50 blocks) or AEC L6 lithium cabinets |
| Technology, display, communications, warranty | As on the INF-100 datasheet |
From the AEC 2026 catalog. Figures can change: the order confirmation rules.
Downloads
The INFINITE manuals and catalogs cover every model of the series, this one included: download them from the INFINITE page.
Quick answers
INF-100+1: what people ask
What is the output current of the INF-100+1?
120.3 A per phase at full load: 100 kVA ÷ (√3 × 480 V). Size the input breaker and the cables of the INF-100+1 from its installation manual and the local electrical code, not from this figure alone.
How much heat does the INF-100+1 give off?
About 2.8 kW, 9,470 BTU/h, at full load, where it is 97.3% efficient. Plan the room's cooling for a little more than that: the INF-100+1 is less efficient at part load and while its battery recharges.
Will the INF-100+1 fit through a standard door?
Not upright through a standard 36 × 80-inch door, which clears about 79 in in height: at 81.4 in (2,068 mm) high it needs an opening taller than 81.4 in. Check elevators and the floor load on the way in too.
The method, for any UPS: runtime explained · amps from kVA · heat output in BTU/h
INFINITE
Other INFINITE models
By power, the INF-100+1 is the smallest in the INFINITE series, which runs from 100 to 600 kVA. One size up are the INF-200, INF-200+1, INF-200+1+L6-CAB-20x50LI and INF-200+L6-CAB-20x50LI, all 100 kVA more. The same 100 kVA also comes as the INF-100, INF-100+1+L6-CAB-20x50LI, INF-100+L6-CAB-10x50LI and INF-100+L6-CAB-20x50LI: the table below gives each one's weight and battery.
Every INFINITE model side by side (13)
| Model | Power | Power against this model | Net weight | Weight against this model | Battery configuration |
|---|---|---|---|---|---|
| INF-100 | 100 kVA | the same power | 452 lb | 119 lb lighter | External VRLA bank or L6 lithium cabinets |
| INF-100+1 | 100 kVA | this page | 571 lb | this page | External VRLA bank or L6 lithium cabinets |
| INF-100+1+L6-CAB-20x50LI | 100 kVA | the same power | 2,743 lb | 2,172 lb heavier | External L6 lithium cabinets |
| INF-100+L6-CAB-10x50LI | 100 kVA | the same power | 1,808 lb | 1,237 lb heavier | External L6 lithium cabinets |
| INF-100+L6-CAB-20x50LI | 100 kVA | the same power | 2,624 lb | 2,053 lb heavier | External L6 lithium cabinets |
| INF-200 | 200 kVA | 100 kVA more | 591 lb | 20 lb heavier | External VRLA bank or L6 lithium cabinets |
| INF-200+1 | 200 kVA | 100 kVA more | 710 lb | 139 lb heavier | External VRLA bank or L6 lithium cabinets |
| INF-200+1+L6-CAB-20x50LI | 200 kVA | 100 kVA more | 2,882 lb | 2,311 lb heavier | External L6 lithium cabinets |
| INF-200+L6-CAB-20x50LI | 200 kVA | 100 kVA more | 2,763 lb | 2,192 lb heavier | External L6 lithium cabinets |
| INF-400 | 400 kVA | 300 kVA more | 1,183 lb | 611 lb heavier | External VRLA bank or L6 lithium cabinets |
| INF-400+2xL6-CAB-20x50LI | 400 kVA | 300 kVA more | 5,526 lb | 4,954 lb heavier | External L6 lithium cabinets |
| INF-600 | 600 kVA | 500 kVA more | 1,774 lb | 1,203 lb heavier | External VRLA bank or L6 lithium cabinets |
| INF-600+3xL6-CAB-20x50LI | 600 kVA | 500 kVA more | 8,597 lb | 8,026 lb heavier | External L6 lithium cabinets |
The INF-100+1 for your project
Send the load, the voltage and the minutes you need from the INF-100+1. We reply with the configuration, the batteries and the lead time.