Double conversion · 230 V and 400 V · 1 kVA to 1.2 MVA

Online UPS: double conversion, 1 kVA to 1.2 MVA

An online UPS turns the mains into DC and back into clean AC, so the load runs on the inverter all the time and sees no transfer when the mains fails. Every AEC UPS range for EMEA is online double conversion: 11 single-phase, three-phase and modular ranges, from 1 kVA to 1,200 kVA in one cabinet.

EMEA 2026 data

Every AEC online range, by phase and power

Efficiency in double conversion and in ECO from each range's EMEA 2026 data; where a figure is missing, the table says so.

AEC online double-conversion UPS ranges, EMEA
RangePowerVoltage, phasesFormDouble conversionECOBattery
IST81–3 kVAsingle-phase 208–240 V2U rack / towerup to 93%ECO mode, no figure publishedlithium built in
IST31–10 kVAsingle-phase 208–240 Vtower95.5% (6 and 10 kVA)ECO mode, no figure publishedVRLA inside; long-backup models with external cabinets
IST3-J1–10 kVAsingle-phase 208–240 V2U rack / tower95.5% (6 and 10 kVA)ECO mode, no figure publishedVRLA inside (1–3 kVA), external (6–10 kVA)
IST910–40 kVAthree-phase 400 V; 3/3, 3/1, 1/1 up to 20 kVA3U rack / towerup to 96%99%external: lead-acid or approved lithium
IST7 10–4010–40 kVAthree-phase 400 V; 3/3, 3/1, 1/1 up to 20 kVAtowerup to 96%99% (single UPS)internal (S models) or external
All-in-One20 kVAthree-phase 400 V; 3/3 or 3/1cabinet on castorsup to 96%99%lithium in the same cabinet
IST7 60–20060–200 kVAthree-phase 400 Vtowerup to 96.5%99%external: VRLA or lithium with the BMS card
IST7-T100–200 kVAthree-phase 400 V, output isolation transformer1000 mm cabinetnot publishedECO mode, no figure publishedexternal: VRLA or lithium
IST6-12030–120 kVAthree-phase 400 Vmodular, 30 kVA modules97%up to 99%external: lead-acid or lithium with the BMS card
IST6 200–500200–500 kVAthree-phase 400 Vmodular, 50 kVA modulesup to 98.1%99.2% in ECO (measured on the 100 kW module); W-ECO, no figure publishedexternal: lead-acid or lithium with the BMS card
IST6 400–1200400–1,200 kVAthree-phase 400 Vmodular, 100 kVA modules97.2% (General) / 98.1% (PLUS)99.2%external: lead-acid or lithium with the BMS card

By family: single-phase UPS · three-phase UPS · three-phase in, single-phase out · modular UPS.

Single-phase, 1–10 kVAIST3 tower, IST3-J in a 2U rack or tower, IST8 with lithium built in. IST3 and IST3-J reach 95.5% efficiency at 6 and 10 kVA; output settable to 208, 220, 230 or 240 V.
Three-phase, 10–200 kVAIST9 in 3U and IST7 10–40 tower, with 3/3, 3/1 or 1/1 output; IST7 60–200 up to 96.5% and up to 8 units in parallel; IST7-T 100–200 kVA with an output isolation transformer.
Modular, up to 1.2 MVAIST6-120 from 30 to 120 kVA with 30 kVA modules; IST6 200–500 with 50 kVA modules, up to 98.1%; IST6 400–1200 with 100 kVA modules, 99.2% in ECO.

Online or line-interactive

What the inverter changes

A line-interactive UPS passes the mains to the load and corrects its voltage; when the mains fails, it switches to the inverter. An online UPS makes its output from the DC bus all the time, so the switch never happens and the frequency is always its own. On a generator, whose frequency wanders under load, the inverter holds the output at 50 Hz.

Efficiency and heat

What double conversion costs in heat

The losses are the load times (1 ÷ efficiency − 1): at 100 kW, the 96.5% of IST7 60–200 leaves about 3.6 kW of heat to remove. Read each range at your own load: UPS efficiency · efficiency and ECO mode · heat output and cooling.

Questions

Questions people ask

What is an online double-conversion UPS?

A UPS that feeds the load from its own inverter all the time: the rectifier turns the mains into DC, the inverter makes new AC from it and the battery sits on the DC bus between them. When the mains fails there is no transfer. Every AEC UPS range works this way.

Is online the same as double conversion?

Yes. Online double conversion (VFI in IEC 62040-3) is named after the two conversions the power to the load goes through: AC to DC, then DC to AC.

Online or line-interactive?

A line-interactive UPS feeds the load from the mains through a voltage regulator and starts its inverter only when the mains fails. An online UPS keeps the load on its inverter, so dips, surges and frequency drift never reach it. AEC builds online UPS only.

What efficiency does an online UPS reach?

In the EMEA 2026 data the peak double-conversion efficiency runs from 90.83% on the 1 kVA IST3 and IST3-J to 98.1% on IST6 200–500 and IST6 400–1200 with PLUS modules. In ECO mode the load runs on the bypass and efficiency rises to 99.2% on IST6, with less protection.

Which 20 kVA three-phase online UPS?

The IST9 20 kVA in a 3U rack or tower, the IST7 20 kVA tower, or the All-in-One with the IST9 20 kVA and lithium in one cabinet. All three give 3/3 or 3/1 output.

Single-phase or three-phase?

Single-phase from 1 to 10 kVA (IST8, IST3, IST3-J); three-phase from 10 kVA at 400 V; three-phase in, single-phase out from 10 to 40 kVA. The panel the UPS connects to decides.

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need: we answer with the model and the batteries that fit.