All-in-One · Three-phase UPS
All-in-One 20 kVA Lithium UPS cabinet 20 kVA, 3/3 and 3/1
The All-in-One 20 kVA is one cabinet with an IST9 20 kVA UPS, distribution and maintenance bypass switches, and 2–8 × 50 Ah or 4 × 100 Ah lithium modules. For data rooms, offices, finance, transport and education sites with a three-phase supply and loads up to 20 kW that want lithium backup on a 0.6 m² footprint.
Quick answers
All-in-One 20 kVA: quick answers
- What it is
- The All-in-One 20 kVA is one cabinet with an IST9 20 kVA UPS, distribution and maintenance bypass switches, and 2–8 × 50 Ah or 4 × 100 Ah lithium modules.
- Who it is for
- For data rooms, offices, finance, transport and education sites with a three-phase supply and loads up to 20 kW that want lithium backup on a 0.6 m² footprint.
- Supply and configuration
- 3/3 · 3/1 · 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L (IST9, 3/3 · 3/1)
- Battery and backup
- 2–8 × 50 Ah or 4 × 100 Ah LFP · 15–60 min at 20 kW (50 Ah) · 60 min at 20 kW, 200 min at 6 kW (4 × 100 Ah)
- Size and weight
- 600 × 1000 × 1110 mm · 232 kg with 2 × 50 Ah, up to 460 kg with 8 × 50 Ah
- Ordering code
- AIO-20K-2X50 … AIO-20K-8X50 (2 to 8 × 50 Ah) · AIO-20K-4X100 (4 × 100 Ah)
All-in-One
What sets apart the All-in-One 20 kVA
There is one All-in-One: the 20 kVA, with the IST9 20 kVA inside, working 3/3 or 3/1. Mains, bypass and output are the only wires to run on site; the modules are connected to the UPS at the factory, and AEC sets their number and charge current (up to 10 A) at commissioning. In 3/3 the IST9 draws 35 A per phase on a 63 A 3P input breaker; in 3/1 the bypass and output carry 91 A on 125 A 1P breakers.
Each 50 Ah module gives up to 10 kW through its own DC/DC converter, so two of them already carry the full 20 kW: 15 minutes at 20 kW, 60 minutes with eight. The 100 Ah version always has four modules of 5 kW each: 23.0 kWh, 60 minutes at 20 kW and 200 minutes at 6 kW, in the same footprint and 108 kg lighter than eight 50 Ah modules.
Size and floor
How big it is
600 × 1000 × 1110 mm · 232 kg with 2 × 50 Ah, up to 460 kg with 8 × 50 Ah.
Floor load = weight ÷ footprint: 387 kg/m² at the lowest weight given (232 kg), 767 kg/m² at the highest (460 kg).
Backup time
How long does the AEC All-in-One 20 kVA run at your load?
AEC's backup times for every ordering code: the minutes AEC publishes from 50 to 100% load, AEC's calculator below 50% and for a string you compose. Pick a battery option: the curve redraws, and every point says where it comes from.
Loading AEC's data…
Source: AEC EMEA product data: ordering codes, cabinets, blocks and strings, and the times AEC publishes from 50 to 100% load. Below 50%, AEC's calculator (W per cell = load ÷ 96% ÷ cells, read on a straight line between the columns of the battery maker's constant-power table at 1.70 V/cell), scaled to meet the published 50% figure. Lithium: published times only. All-in-One lithium modules: the catalogue's reference values, to be confirmed by actual measurement. New batteries, 25 °C. AEC checks every sizing.
Table: the All-in-One 20 kVA minutes at 20, 50, 80 and 100% load
| Batteries | Code | 20% | 50% | 80% | 100% |
|---|---|---|---|---|---|
| 2 × lithium modules 50 Ah | AIO-20K-2X50 | — | 30 | 19 | 15 |
| 8 × lithium modules 50 Ah | AIO-20K-8X50 | — | 120 | 75 | 60 |
| 4 × lithium modules 100 Ah | — | — | 120 | — | 60 |
For each battery type the smallest and the largest configuration; new batteries, 25 °C. AEC published figures or EMEA 2026 catalogue figures. Every option is in the chart and the table of codes.
All 7 ordering codes of the All-in-One 20 kVA and their backup times
| Code | Batteries | Cabinet | 100% | 90% | 80% | 70% | 60% | 50% |
|---|---|---|---|---|---|---|---|---|
| Lithium modules, 50 Ah | ||||||||
| AIO-20K-2X50 | 2 × lithium modules 50 Ah | internal | 15 | 17 | 19 | 21 | 25 | 30 |
| AIO-20K-3X50 | 3 × lithium modules 50 Ah | internal | 22 | 25 | 28 | 32 | 37 | 45 |
| AIO-20K-4X50 | 4 × lithium modules 50 Ah | internal | 30 | 33 | 38 | 43 | 50 | 60 |
| AIO-20K-5X50 | 5 × lithium modules 50 Ah | internal | 37 | 41 | 47 | 53 | 62 | 75 |
| AIO-20K-6X50 | 6 × lithium modules 50 Ah | internal | 45 | 50 | 56 | 64 | 75 | 90 |
| AIO-20K-7X50 | 7 × lithium modules 50 Ah | internal | 52 | 58 | 65 | 75 | 87 | 105 |
| AIO-20K-8X50 | 8 × lithium modules 50 Ah | internal | 60 | 67 | 75 | 86 | 100 | 120 |
Minutes from AEC EMEA product data: from 50 to 100% load, the times AEC publishes. The chart above adds AEC's calculation from 10 to 40%.
Efficiency
How efficient is the AEC All-in-One 20 kVA at your load?
All-in-One 20 kVA, 20 kW at its rating, online, double conversion (typical curve, AEC's method). Heat to remove on this curve: 25%: 0.24 kW (η 95.4%) · 50%: 0.42 kW (η 96%) · 75%: 0.67 kW (η 95.7%) · 100%: 0.96 kW (η 95.4%). At 50% load, 24/7, it loses about 3,650 kWh a year.
How the curve is drawn and where each figure comes from: the All-in-One range page.
- Load
- —
- Lost as heat
- —
- Energy lost in a year, 24/7
- —
- Its cost in a year at € per kWh
- —
- The catalogue's examples use €0.20 per kWh.
Where each figure comes from
| Mode | Efficiency | Kind | Models | Source |
|---|---|---|---|---|
| Online, double conversion | 25%: 95.4% · 50%: 96% · 75%: 95.7% · 100%: 95.4% | Typical curve, derived from the datasheet efficiency of 96% (AEC method) | All-in-One 20 kVA | AEC datasheet: AC/AC efficiency of the IST6-PM100 100 kW power module (the curve's shape) |
| ECO | 99% | Datasheet figure, load not stated | All-in-One 20 kVA |
EMEA 2026 catalogue figures: Online, double conversion up to 96% · ECO up to 99%.
Drag to turnTechnical data
Technical data All-in-One 20 kVA
Only this model's values, from the EMEA 2026 catalogue table.
| Model | |
|---|---|
| AEC codes | AIO-20K-2X50 … AIO-20K-8X50 · AIO-20K-4X100 |
| UPS inside | IST9 20 kVA, rack 3U |
| Rated power (kVA / kW) | 20 / 20 |
| Input / output | 3/3 · 3/1 |
| Technology | online double conversion · IGBT rectifier with PFC · DSP control · battery from isolated DC/DC lithium modules |
| Input | |
| Voltage range | phase 176–280 V full load · 80–176 V with linear derating |
| Frequency | 40–70 Hz |
| Power factor · THDi | ≥ 0.99 · ≤ 3% resistive, ≤ 5% non-linear full load |
| Output | |
| Voltage | 220 / 230 / 240 V L-N · 380 / 400 / 415 V L-L · fine adjustment ± 5 V |
| Frequency on battery | 50 or 60 ± 0.1 Hz |
| Voltage distortion | ≤ 2% resistive full load |
| Power factor | 1.0 (kVA = kW) |
| Transfer time | < 1 ms synchronised · < 10 ms not synchronised |
| Overload | ≤ 105% continuous · 105–110% 60 min · 110–130% 10 min · 130–155% 1 min · > 155% 200 ms |
| Efficiency (AC/AC) | up to 96% · 99% in ECO mode |
| Modes | online · ECO · battery · bypass · generator · frequency converter · impact load · test load |
| Battery system | |
| Lithium modules | 2 to 8 × 50 Ah (5.76–23.0 kWh) or 4 × 100 Ah (23.0 kWh) |
| Backup time | 15–60 min at 20 kW (50 Ah) · 60 min at 20 kW, 200 min at 6 kW (4 × 100 Ah) |
| Charge current, max. | 10 A (UPS charger); per module set from the number of modules |
| General | |
| Communication | RS232 · EPO · RS485 · options: SNMP, RS485 + dry contact |
| System display | 4.3" touch screen, tilted, on the door, with 3-colour LED status bar · LCD of the UPS · USB for records and upgrades |
| Noise | < 65 dB at full load |
| Working temperature · humidity | UPS −5 … 40 °C · battery 0–40 °C (15–30 °C recommended) · humidity 5–95%, non-condensing |
| Altitude · protection degree | ≤ 2000 m (above: derating to IEC 62040-3) · IP20 |
| Earthing systems | TN-S · TN-C · TN-C-S |
| Cabinet size W × D × H (mm), on castors | 600 × 1000 × 1110 · 1000 mm high without castors |
| Cabinet weight with distribution, without UPS and modules (kg) | 138 ± 5 (50 Ah) · 134 ± 5 (100 Ah) |
| System weight (kg) | 232 (2 × 50 Ah) to 460 (8 × 50 Ah) · 352 (4 × 100 Ah) |
| UPS size W × D × H (mm) | 438 × 535 × 130 (3U) |
| UPS weight (kg) | 18.4 |
| Item | All-in-One 20 kVA |
|---|---|
| UPS inside | IST9 20 kVA |
| Input / output | 3/3 · 3/1 |
| UPS height | 3U |
| Number of modules (from backup tables) | 50 Ah: 2–8 · 100 Ah: 4 |
UPS data from the IST9 user manual; system data from the AEC All-in-One 20 kVA user manual and the EMEA 2026 catalogue. Specifications are subject to change without notice.
More technical detailsrange tables, ordering codes
Planning data
All-in-One range tables
Eight codes, one 20 kVA system
Every code: IST9 20 kVA, input / output 3/3 or 3/1. Weight: UPS 18.4 kg + cabinet with distribution 138 ± 5 kg (134 ± 5 kg for 100 Ah) + modules of more than 38 kg (50 Ah) or 50 kg (100 Ah) each. Backup times: reference values, to be confirmed by actual measurement; AEC sizes every system.
| AEC code | Lithium modules | kWh | min at 20 kW | min at 10 kW | min at 6 kW | Weight (kg) |
|---|---|---|---|---|---|---|
| AIO-20K-2X50 | 2 × 50 Ah | 5.76 | 15 | 30 | 50 | 232 |
| AIO-20K-3X50 | 3 × 50 Ah | 8.64 | 22 | 45 | 75 | 270 |
| AIO-20K-4X50 | 4 × 50 Ah | 11.5 | 30 | 60 | 100 | 308 |
| AIO-20K-5X50 | 5 × 50 Ah | 14.4 | 37 | 75 | 125 | 346 |
| AIO-20K-6X50 | 6 × 50 Ah | 17.3 | 45 | 90 | 150 | 384 |
| AIO-20K-7X50 | 7 × 50 Ah | 20.2 | 52 | 105 | 175 | 422 |
| AIO-20K-8X50 | 8 × 50 Ah | 23.0 | 60 | 120 | 200 | 460 |
| AIO-20K-4X100 | 4 × 100 Ah | 23.0 | 60 | 120 | 200 | 352 |
50 Ah modules · minutes
Backup grows one module at a time: 2 to 8 modules of 50 Ah, 2.88 kWh each. Load in kW; backup in minutes. 6 kW: catalogue reference values at 25 °C; 10 to 20 kW (50 to 100% load): AEC's product data. To be confirmed by actual measurement; AEC sizes every system. –: configuration not possible (at least two modules).
| Load · modules | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
|---|---|---|---|---|---|---|---|---|
| 6 kW | – | 50 | 75 | 100 | 125 | 150 | 175 | 200 |
| 10 kW | – | 30 | 45 | 60 | 75 | 90 | 105 | 120 |
| 12 kW | – | 25 | 37 | 50 | 62 | 75 | 87 | 100 |
| 14 kW | – | 21 | 32 | 43 | 53 | 64 | 75 | 86 |
| 16 kW | – | 19 | 28 | 38 | 47 | 56 | 65 | 75 |
| 18 kW | – | 17 | 25 | 33 | 41 | 50 | 58 | 67 |
| 20 kW | – | 15 | 22 | 30 | 37 | 45 | 52 | 60 |
100 Ah modules · minutes
Long backup with four 100 Ah modules, 23.0 kWh in all (AIO-20K-4X100); the 100 Ah version always has four. Catalogue reference values at 25 °C, to be confirmed by actual measurement. –: configuration not possible.
| Load · modules | 1 | 2 | 3 | 4 |
|---|---|---|---|---|
| 6 kW | – | – | – | 200 |
| 10 kW | – | – | – | 120 |
| 20 kW | – | – | – | 60 |
One cabinet to connect · IST9 20 kVA max. steady-state current (A)
Only mains, bypass and output are wired on site; the lithium modules are already connected to the UPS inside the cabinet.
| kVA | Mode | AC in | Bypass | AC out |
|---|---|---|---|---|
| 20 | 3/3 | 35 | — | 30 |
| 20 | 3/1 | 35 | 91 | 91 |
IST9 20 kVA · recommended breakers (A)
From the IST9 user manual. Breaker 1.5–2 × max. input current, without leakage protection.
| kVA | Mode | AC in | Bypass | AC out |
|---|---|---|---|---|
| 20 | 3/3 | 63 × 3P | 50 × 3P | 50 × 3P |
| 20 | 3/1 | 63 × 3P | 125 × 1P | 125 × 1P |
50 Ah or 100 Ah?
Same cabinet, same UPS: the module decides the backup. Catalogue reference values; AEC sizes every system.
| 50 Ah | 100 Ah | |
|---|---|---|
| Modules | 2 to 8, two per row | 4, one per row |
| Module width | 223 mm | 440 mm |
| Cells | 4C | 1C |
| Energy per module | 2.88 kWh | 5.76 kWh |
| Energy in all | 5.76–23.0 kWh | 23.0 kWh |
| Backup at 20 kW | 15–60 min | 60 min |
| System weight | 232–460 kg | 352 kg |
| Best for | short and medium backup | long backup, low and medium loads |
Ordering codes
Ordering codes All-in-One 20 kVA
| Code | Description |
|---|---|
| AIO-20K-2X50 | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 2 × 50 Ah lithium modules (5.76 kWh) |
| AIO-20K-3X50 | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 3 × 50 Ah lithium modules (8.64 kWh) |
| AIO-20K-4X50 | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 4 × 50 Ah lithium modules (11.5 kWh) |
| AIO-20K-5X50 | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 5 × 50 Ah lithium modules (14.4 kWh) |
| AIO-20K-6X50 | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 6 × 50 Ah lithium modules (17.3 kWh) |
| AIO-20K-7X50 | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 7 × 50 Ah lithium modules (20.2 kWh) |
| AIO-20K-8X50 | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 8 × 50 Ah lithium modules (23.0 kWh) |
| AIO-20K-4X100 | IST9 20 kVA (3/3 · 3/1), distribution switches with maintenance bypass, 4 × 100 Ah lithium modules (23.0 kWh), one per row |
| Options | SNMP card · dry-contact card · extra 50 Ah modules, up to 8 per cabinet |
Catalogue
This range's pages of the catalogue.
Questions
Questions about the All-in-One 20 kVA
What backup does the All-in-One 20 kVA give?
At 20 kW: 15, 22, 30, 37, 45, 52 or 60 minutes with two to eight 50 Ah modules, and 60 minutes with four 100 Ah modules. At 6 kW: 50 to 200 minutes with 50 Ah modules, 200 minutes with the 100 Ah version. Reference values, confirmed by AEC for each system.
Is there a single-phase All-in-One, or one above 20 kVA?
No. The All-in-One is built as 20 kVA only, three-phase input, 3/3 or 3/1: the 3/1 mode feeds single-phase loads. For a single-phase supply look at the IST3, IST3-J or IST8; for lithium above 20 kVA, at the L6 cabinets with the IST7 60–200 kVA or the IST6.
Can modules be added later?
Yes, with 50 Ah modules, up to eight: each module has its own DC/DC converter, so new modules work beside the ones in service and go in with the load supplied. The 100 Ah version is always four modules.
What are the ordering codes of the All-in-One 20 kVA?
AIO-20K-2X50 to AIO-20K-8X50 with 2 to 8 modules of 50 Ah, and AIO-20K-4X100 with four modules of 100 Ah. Tell us the load and the backup time: AEC chooses the code.
Lithium All-in-One or UPS with VRLA batteries?
AEC's comparison in the catalogue: one cabinet instead of UPS plus battery cabinet, installed by one person in 30–60 minutes instead of two people in 2–4 hours. The lithium lasts 10+ years with 5,000 cycles at 50% depth of discharge against 3–5 years and about 500 cycles for VRLA.
How long does a 20 kVA UPS like the All-in-One 20 kVA run?
15 to 60 minutes at full load (20 kW), and 30 to 120 minutes at half load, with the AEC battery options in the table: the battery chosen sets the figure. With 2 × lithium modules 50 Ah (AIO-20K-2X50): 15 minutes at 100% and 30 at 50%. For other loads and batteries use the backup-time tool.
How big is the AEC All-in-One 20 kVA and how much does it weigh?
The AEC All-in-One 20 kVA measures 600 × 1000 × 1110 mm; weight: 232 kg with 2 × 50 Ah, up to 460 kg with 8 × 50 Ah (EMEA 2026 catalogue).
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need for the AEC All-in-One 20 kVA: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.