L6 Lithium · Batteries and cabinets

L6-50 LiFePO4 lithium battery cabinet, 50 Ah modules

Lithium50 AhLFP lithium battery cabinet

The L6-50 is a lithium iron phosphate battery cabinet for up to twenty hot-swappable 50 Ah modules: 58 kWh and 200 kW of rated output on a 600 × 850 mm footprint. For AEC IST7 and IST6 UPS that need 15 to 30 minutes of backup: data rooms, hospitals and industrial sites.

200 kW per cabinetRating
600 × 850 × 2000 mmW × D × H
985 ± 20 kg with 20 modulesWeight
58 kWh · 20 × 50 AhBattery

Quick answers

L6-50: quick answers

What it is
The L6-50 is a lithium iron phosphate battery cabinet for up to twenty hot-swappable 50 Ah modules: 58 kWh and 200 kW of rated output on a 600 × 850 mm footprint.
Who it is for
For AEC IST7 and IST6 UPS that need 15 to 30 minutes of backup: data rooms, hospitals and industrial sites.
Supply and configuration
240 / ±240 / 480 V DC
Battery and backup
58 kWh · 20 × 50 Ah · 15 / 30 min
Size and weight
600 × 850 × 2000 mm · 985 ± 20 kg with 20 modules
Ordering code
L6-50 cabinet, M or M1, master or slave · code on request

L6 Lithium

What sets apart the L6-50

The 50 Ah module fits the same 223 mm drawer as the 40 Ah but uses 4C cells, eighteen in series: 57.6 V and 2.88 kWh per module, 41% more energy, with the same 10 kW DC/DC output. A full cabinet stores 58 kWh and runs about 14 minutes at 200 kW (the L6 sizing table, reserve included), against 10 minutes for the L6-40. It weighs 985 ± 20 kg full (M1: 975).

The All-in-One 20 kVA uses the same 50 and 100 Ah modules. The L6 sizing table for 15 and 30 minutes asks a little more than one module per 10 kW: 11 modules for 15 minutes at 100 kW, 22 for 30 minutes, with the 10% reserve and the efficiencies included.

  • Against the L6-40 (one size down): Nominal capacity 58 kWh against 41 kWh; Capacity · cell discharge rate 50 Ah · 4C against 40 Ah · 6C; Rated voltage · energy 57.6 V · 2.88 kWh against 51.2 V · 2.05 kWh; Weight 37 ± 1 kg against 36 ± 1 kg; Weight with full modules 985 ± 20 kg (M1: 975) against 965 ± 20 kg (M1: 955).
  • Against the L6-100 (one size up): Nominal capacity 58 kWh against 69 kWh; Max. modules per cabinet 20 against 12; Rated output power (discharge) 200 kW against 60 kW; Capacity · cell discharge rate 50 Ah · 4C against 100 Ah · 1C; Rated voltage · energy 57.6 V · 2.88 kWh against 57.6 V · 5.76 kWh.

Planning data

L6-50: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the L6-50.

One footprint, two module sizes

L6-50 · One footprint, two module sizes
ModuleEnergy per cabinetRated power per cabinet
50 Ah58 kWh200 kW

Two capacities, one drawer size

L6-50 · Two capacities, one drawer size
Item50 Ah · 4C
CellsLFP, 3.2 V · 18 in series
Module voltage57.6 V
Energy per module2.88 kWh
Cell discharge rate4C
DC/DC output240 / ±240 / 480 V · 10 kW
Current unbalance≤ 3%
Full cabinet, 20 modules58 kWh · 14 min at rated power
Size (W × D × H)223 × 665 × 152 mm
Weight37 ± 1 kg
Noise58 dB

Installation

Installing the L6-50: space, cables

Each figure with its source.

L6-50 · installation
ItemFigureSource
Clearancesfront 800 mm, rear 800 mm, left 0 mm, right 0 mm, top 500 mmL6 user manual App. A; EMEA 2026 catalogue p.177–178; EMEA 2026 catalogue p.177
Cable entryDC cables from the topEMEA 2026 catalogue p.177
Operating temperature0 to 40 °C, best 20–30 °CL6 user manual App. A; EMEA 2026 catalogue p.177
Switches and terminalsBattery breakers behind the front door; 10" touch screen on the master's door.EMEA 2026 catalogue p.177
DoorOne leaf, hinged on the rightEMEA 2026 catalogue p.177
Module withdrawal665 mm in front of the cabinet to withdraw a moduleEMEA 2026 catalogue p.177–178

Size and floor

How big it is

600 × 850 × 2000 mm · 985 ± 20 kg with 20 modules.

0.51 m²footprint
1,931 kg/m²floor load
2 mheight

Floor load = weight ÷ footprint (985 kg).

1.75 mFrontSide6008502000
AEC L6-50, rendered from its 3D modelDrag to turn

In 3D

Look around the L6-50

Technical data

Technical data L6-50

Only this model's values, from the EMEA 2026 catalogue table.

L6-50 · Technical data
Cabinet
Nominal capacity58 kWh
Max. modules per cabinet20
Rated output power (discharge)200 kW
Rated output voltage (discharge)240 / ±240 / 480 V DC (three output systems)
Rated input voltage (charge)265 / ±265 / 530 V DC
Cell charge currentmax. 40 A, default 20 A
Discharge overload125–135%: 1 min · 135–150%: 30 s · > 150%: 500 ms
Current unbalance (module / cabinet)≤ 3%
Max. cabinets in parallel15
SOC · SOHmodule SOC accuracy ≥ 95% · SOH estimate accuracy ≥ 90%
Functionsdischarge SOC balance, battery cold start, self-start after power recovery, EPO, module-level fire control, cell insulation detection
Protectionover-temperature, over-current, short circuit, battery over- and under-voltage, low SOC
Module
Capacity · cell discharge rate50 Ah · 4C
Rated voltage · energy57.6 V · 2.88 kWh
Cell cycle life5,000 cycles at 50% depth of discharge
DC/DC output per module10 kW
Size (W × D × H)223 × 665 × 152 mm
Weight37 ± 1 kg
General
CommunicationTCP/IP, RS485 (CAN reserved)
Display10-inch touch screen (master cabinet) · indicators (slave cabinet)
Operating · storage temperature0 … +40 °C · −10 … +45 °C
Humidity · altitude5–95% non-condensing · < 4000 m, derating above 2000 m (IEC 62040-3)
Noise · protection< 65 dB · IP20 · battery-side overvoltage level 2
Cabinet size (W × D × H)600 × 850 × 2000 mm
Weight with full modules985 ± 20 kg (M1: 975)
L6-50 · Models
ItemL6-50
Module capacity50 Ah
Cell discharge rate4C
Modules per cabinet10 / 20
Energy per cabinet29 / 58 kWh
Rated power per cabinet100 / 200 kW
Typical backup15 / 30 min

Cabinet energy and other cabinet and system data from the L6 user manual; module voltage, energy and DC/DC power from AEC lithium documentation. Specifications are subject to change without notice.

More technical detailsrange tables, ordering codes

Planning data

L6 Lithium range tables

15 and 30 minutes

Cabinets and modules for each UPS power (cabinets · modules), from the L6 sizing table (2026): new modules, 95% battery and inverter efficiency, the 10% reserve included, never fewer modules than carry the UPS rating.

L6-50 · 15 and 30 minutes
UPS kW15 min30 min
≤ 601 · 71 · 13
≤ 801 · 91 · 17
≤ 1001 · 112 · 22
≤ 2002 · 223 · 43
≤ 3002 · 324 · 64
≤ 4003 · 435 · 85
≤ 5003 · 536 · 106
≤ 6004 · 647 · 127
≤ 8005 · 859 · 170

Ordering codes

Ordering codes L6-50

Ordering codes L6-50
CodeDescription
L6-50 cabinetCabinet for up to 20 × 50 Ah modules, master or slave, M or M1. Code on request.
Modules40 Ah · 50 Ah · 100 Ah lithium modules, hot-swappable. Code on request.
L6-C-2000 · L6-C-4000Combiner cabinet: L6-C-2000 (up to 4 cabinets) · L6-C-4000 (up to 8 cabinets). Code on request.
AccessoriesNetworking device · blank panels · in-row rear frame. Code on request.

Questions

Questions about the L6-50

L6-40 or L6-50?

Same cabinet, same 10 kW per module, same 200 kW per cabinet. The L6-50 stores 58 kWh instead of 41 and gives 15 / 30 minutes where the L6-40 gives 10 / 20, with about 10% more modules. Choose by the backup time required.

How many L6-50 cabinets for 30 minutes at 400 kW?

The L6 sizing table gives five cabinets with 85 modules for 400 kW at 30 minutes, and three cabinets with 43 modules at 15 minutes. Above one cabinet, one master and its slave cabinets work in parallel; from four cabinets a combiner joins them.

How big is the AEC L6-50 and how much does it weigh?

The AEC L6-50 measures 600 × 850 × 2000 mm; weight: 985 ± 20 kg with 20 modules (EMEA 2026 catalogue).

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC L6-50: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.