L6 Lithium · Batteries and cabinets
L6-50 LiFePO4 lithium battery cabinet, 50 Ah modules
The L6-50 is a lithium iron phosphate battery cabinet for up to twenty hot-swappable 50 Ah modules: 58 kWh and 200 kW of rated output on a 600 × 850 mm footprint. For AEC IST7 and IST6 UPS that need 15 to 30 minutes of backup: data rooms, hospitals and industrial sites.
Quick answers
L6-50: quick answers
- What it is
- The L6-50 is a lithium iron phosphate battery cabinet for up to twenty hot-swappable 50 Ah modules: 58 kWh and 200 kW of rated output on a 600 × 850 mm footprint.
- Who it is for
- For AEC IST7 and IST6 UPS that need 15 to 30 minutes of backup: data rooms, hospitals and industrial sites.
- Supply and configuration
- 240 / ±240 / 480 V DC
- Battery and backup
- 58 kWh · 20 × 50 Ah · 15 / 30 min
- Size and weight
- 600 × 850 × 2000 mm · 985 ± 20 kg with 20 modules
- Ordering code
- L6-50 cabinet, M or M1, master or slave · code on request
L6 Lithium
What sets apart the L6-50
The 50 Ah module fits the same 223 mm drawer as the 40 Ah but uses 4C cells, eighteen in series: 57.6 V and 2.88 kWh per module, 41% more energy, with the same 10 kW DC/DC output. A full cabinet stores 58 kWh and runs about 14 minutes at 200 kW (the L6 sizing table, reserve included), against 10 minutes for the L6-40. It weighs 985 ± 20 kg full (M1: 975).
The All-in-One 20 kVA uses the same 50 and 100 Ah modules. The L6 sizing table for 15 and 30 minutes asks a little more than one module per 10 kW: 11 modules for 15 minutes at 100 kW, 22 for 30 minutes, with the 10% reserve and the efficiencies included.
- Against the L6-40 (one size down): Nominal capacity 58 kWh against 41 kWh; Capacity · cell discharge rate 50 Ah · 4C against 40 Ah · 6C; Rated voltage · energy 57.6 V · 2.88 kWh against 51.2 V · 2.05 kWh; Weight 37 ± 1 kg against 36 ± 1 kg; Weight with full modules 985 ± 20 kg (M1: 975) against 965 ± 20 kg (M1: 955).
- Against the L6-100 (one size up): Nominal capacity 58 kWh against 69 kWh; Max. modules per cabinet 20 against 12; Rated output power (discharge) 200 kW against 60 kW; Capacity · cell discharge rate 50 Ah · 4C against 100 Ah · 1C; Rated voltage · energy 57.6 V · 2.88 kWh against 57.6 V · 5.76 kWh.
Planning data
L6-50: currents, breakers, cables, batteries
The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the L6-50.
One footprint, two module sizes
| Module | Energy per cabinet | Rated power per cabinet |
|---|---|---|
| 50 Ah | 58 kWh | 200 kW |
Two capacities, one drawer size
| Item | 50 Ah · 4C |
|---|---|
| Cells | LFP, 3.2 V · 18 in series |
| Module voltage | 57.6 V |
| Energy per module | 2.88 kWh |
| Cell discharge rate | 4C |
| DC/DC output | 240 / ±240 / 480 V · 10 kW |
| Current unbalance | ≤ 3% |
| Full cabinet, 20 modules | 58 kWh · 14 min at rated power |
| Size (W × D × H) | 223 × 665 × 152 mm |
| Weight | 37 ± 1 kg |
| Noise | 58 dB |
Installation
Installing the L6-50: space, cables
Each figure with its source.
| Item | Figure | Source |
|---|---|---|
| Clearances | front 800 mm, rear 800 mm, left 0 mm, right 0 mm, top 500 mm | L6 user manual App. A; EMEA 2026 catalogue p.177–178; EMEA 2026 catalogue p.177 |
| Cable entry | DC cables from the top | EMEA 2026 catalogue p.177 |
| Operating temperature | 0 to 40 °C, best 20–30 °C | L6 user manual App. A; EMEA 2026 catalogue p.177 |
| Switches and terminals | Battery breakers behind the front door; 10" touch screen on the master's door. | EMEA 2026 catalogue p.177 |
| Door | One leaf, hinged on the right | EMEA 2026 catalogue p.177 |
| Module withdrawal | 665 mm in front of the cabinet to withdraw a module | EMEA 2026 catalogue p.177–178 |
Size and floor
How big it is
600 × 850 × 2000 mm · 985 ± 20 kg with 20 modules.
Floor load = weight ÷ footprint (985 kg).
Backup time
The backup-time tool reads the catalogue's tables for lithium modules, L6 cabinets and VRLA strings.
Drag to turnTechnical data
Technical data L6-50
Only this model's values, from the EMEA 2026 catalogue table.
| Cabinet | |
|---|---|
| Nominal capacity | 58 kWh |
| Max. modules per cabinet | 20 |
| Rated output power (discharge) | 200 kW |
| Rated output voltage (discharge) | 240 / ±240 / 480 V DC (three output systems) |
| Rated input voltage (charge) | 265 / ±265 / 530 V DC |
| Cell charge current | max. 40 A, default 20 A |
| Discharge overload | 125–135%: 1 min · 135–150%: 30 s · > 150%: 500 ms |
| Current unbalance (module / cabinet) | ≤ 3% |
| Max. cabinets in parallel | 15 |
| SOC · SOH | module SOC accuracy ≥ 95% · SOH estimate accuracy ≥ 90% |
| Functions | discharge SOC balance, battery cold start, self-start after power recovery, EPO, module-level fire control, cell insulation detection |
| Protection | over-temperature, over-current, short circuit, battery over- and under-voltage, low SOC |
| Module | |
| Capacity · cell discharge rate | 50 Ah · 4C |
| Rated voltage · energy | 57.6 V · 2.88 kWh |
| Cell cycle life | 5,000 cycles at 50% depth of discharge |
| DC/DC output per module | 10 kW |
| Size (W × D × H) | 223 × 665 × 152 mm |
| Weight | 37 ± 1 kg |
| General | |
| Communication | TCP/IP, RS485 (CAN reserved) |
| Display | 10-inch touch screen (master cabinet) · indicators (slave cabinet) |
| Operating · storage temperature | 0 … +40 °C · −10 … +45 °C |
| Humidity · altitude | 5–95% non-condensing · < 4000 m, derating above 2000 m (IEC 62040-3) |
| Noise · protection | < 65 dB · IP20 · battery-side overvoltage level 2 |
| Cabinet size (W × D × H) | 600 × 850 × 2000 mm |
| Weight with full modules | 985 ± 20 kg (M1: 975) |
| Item | L6-50 |
|---|---|
| Module capacity | 50 Ah |
| Cell discharge rate | 4C |
| Modules per cabinet | 10 / 20 |
| Energy per cabinet | 29 / 58 kWh |
| Rated power per cabinet | 100 / 200 kW |
| Typical backup | 15 / 30 min |
Cabinet energy and other cabinet and system data from the L6 user manual; module voltage, energy and DC/DC power from AEC lithium documentation. Specifications are subject to change without notice.
More technical detailsrange tables, ordering codes
Planning data
L6 Lithium range tables
15 and 30 minutes
Cabinets and modules for each UPS power (cabinets · modules), from the L6 sizing table (2026): new modules, 95% battery and inverter efficiency, the 10% reserve included, never fewer modules than carry the UPS rating.
| UPS kW | 15 min | 30 min |
|---|---|---|
| ≤ 60 | 1 · 7 | 1 · 13 |
| ≤ 80 | 1 · 9 | 1 · 17 |
| ≤ 100 | 1 · 11 | 2 · 22 |
| ≤ 200 | 2 · 22 | 3 · 43 |
| ≤ 300 | 2 · 32 | 4 · 64 |
| ≤ 400 | 3 · 43 | 5 · 85 |
| ≤ 500 | 3 · 53 | 6 · 106 |
| ≤ 600 | 4 · 64 | 7 · 127 |
| ≤ 800 | 5 · 85 | 9 · 170 |
Ordering codes
Ordering codes L6-50
| Code | Description |
|---|---|
| L6-50 cabinet | Cabinet for up to 20 × 50 Ah modules, master or slave, M or M1. Code on request. |
| Modules | 40 Ah · 50 Ah · 100 Ah lithium modules, hot-swappable. Code on request. |
| L6-C-2000 · L6-C-4000 | Combiner cabinet: L6-C-2000 (up to 4 cabinets) · L6-C-4000 (up to 8 cabinets). Code on request. |
| Accessories | Networking device · blank panels · in-row rear frame. Code on request. |
Catalogue
This range's pages of the catalogue.
L6 Lithium · catalogue pagesCatalogue pages · English · 15 pages · 8.5 MBPDF
L6 lithium battery cabinet · user manualUser manual · English · 63 pages · 7.2 MBPDF
L6 touch screen (MBMU) · user manualUser manual · English · 46 pages · 4.3 MBPDF L6 lithium battery cabinet · quick installation guideInstallation manual · English · 8 pages · 1.3 MBPDF
L6 Lithium · UPS Catalogue EMEA 2026Catalogue · English · PDF · pages 165–179PDF
Questions
Questions about the L6-50
L6-40 or L6-50?
Same cabinet, same 10 kW per module, same 200 kW per cabinet. The L6-50 stores 58 kWh instead of 41 and gives 15 / 30 minutes where the L6-40 gives 10 / 20, with about 10% more modules. Choose by the backup time required.
How many L6-50 cabinets for 30 minutes at 400 kW?
The L6 sizing table gives five cabinets with 85 modules for 400 kW at 30 minutes, and three cabinets with 43 modules at 15 minutes. Above one cabinet, one master and its slave cabinets work in parallel; from four cabinets a combiner joins them.
How big is the AEC L6-50 and how much does it weigh?
The AEC L6-50 measures 600 × 850 × 2000 mm; weight: 985 ± 20 kg with 20 modules (EMEA 2026 catalogue).
Talk to an AEC engineer
Tell us the load, the supply and the backup time you need for the AEC L6-50: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.