L6 Lithium · Batteries and cabinets

L6-100 LiFePO4 lithium battery cabinet, 100 Ah modules

Lithium100 AhLFP lithium battery cabinet

The L6-100 is a lithium iron phosphate battery cabinet for up to twelve hot-swappable 100 Ah modules: 69 kWh and 60 kW of rated output, for backup of one to four hours. For telecom, security, public buildings and smaller UPS (up to 40 kW) that need hours, not minutes, of backup.

60 kW per cabinetRating
600 × 850 × 2000 mmW × D × H
810 ± 24 kg with 12 modulesWeight
69 kWh · 12 × 100 AhBattery

Quick answers

L6-100: quick answers

What it is
The L6-100 is a lithium iron phosphate battery cabinet for up to twelve hot-swappable 100 Ah modules: 69 kWh and 60 kW of rated output, for backup of one to four hours.
Who it is for
For telecom, security, public buildings and smaller UPS (up to 40 kW) that need hours, not minutes, of backup.
Supply and configuration
240 / ±240 / 480 V DC
Battery and backup
69 kWh · 12 × 100 Ah · 1 / 2 / 4 h
Size and weight
600 × 850 × 2000 mm · 810 ± 24 kg with 12 modules
Ordering code
L6-100 cabinet, master or slave · code on request

L6 Lithium

What sets apart the L6-100

The 100 Ah module uses 1C cells in a wider 440 mm drawer: 57.6 V, 5.76 kWh, 52 ± 1 kg, with a 5 kW DC/DC output. Twelve of them fill the cabinet in one column for 69 kWh, close to an hour (57 minutes) at the 60 kW rating. The full cabinet weighs 810 ± 24 kg, less than the 40 / 50 Ah versions, and has one battery breaker.

The L6 long-backup sizing starts small: a 6 kW UPS needs two modules for 1 hour (never fewer than carry its power), three for 2 hours and six for 4 hours; a 20 kW UPS needs five, nine or seventeen (two cabinets). At 40 kW: nine modules for 1 hour, two cabinets (17) for 2 hours, three cabinets (34) for 4 hours.

  • Against the L6-50 (one size down): Nominal capacity 69 kWh against 58 kWh; Max. modules per cabinet 12 against 20; Rated output power (discharge) 60 kW against 200 kW; Capacity · cell discharge rate 100 Ah · 1C against 50 Ah · 4C; Rated voltage · energy 57.6 V · 5.76 kWh against 57.6 V · 2.88 kWh.

Planning data

L6-100: currents, breakers, cables, batteries

The rows and columns of the EMEA 2026 catalogue's and AEC manuals' tables that concern the L6-100.

One footprint, two module sizes

L6-100 · One footprint, two module sizes
ModuleEnergy per cabinetRated power per cabinet
100 Ah69 kWh60 kW

Long backup, in a wider drawer

L6-100 · Long backup, in a wider drawer
Item100 Ah · 1C
CellsLFP, 3.2 V · 18 in series · 1C
Module voltage · energy57.6 V · 5.76 kWh
DC/DC output240 / ±240 / 480 V · 5 kW
Current unbalance≤ 3%
Full cabinet, 12 modules69 kWh · 57 min at rated power
Size (W × D × H)440 × 665 × 132 mm
Weight · noise52 ± 1 kg · 58 dB

Installation

Installing the L6-100: space, cables

Each figure with its source.

L6-100 · installation
ItemFigureSource
Clearancesfront 800 mm, rear 800 mm, left 0 mm, right 0 mm, top 500 mmL6 user manual App. A; EMEA 2026 catalogue p.177–178; EMEA 2026 catalogue p.177
Cable entryDC cables from the topEMEA 2026 catalogue p.177
Operating temperature0 to 40 °C, best 20–30 °CL6 user manual App. A; EMEA 2026 catalogue p.177
Switches and terminalsBattery breakers behind the front door; 10" touch screen on the master's door.EMEA 2026 catalogue p.177
DoorOne leaf, hinged on the rightEMEA 2026 catalogue p.177
Module withdrawal665 mm in front of the cabinet to withdraw a moduleEMEA 2026 catalogue p.177–178

Size and floor

How big it is

600 × 850 × 2000 mm · 810 ± 24 kg with 12 modules.

0.51 m²footprint
1,588 kg/m²floor load
2 mheight

Floor load = weight ÷ footprint (810 kg).

1.75 mFrontSide6008502000
AEC L6-100, rendered from its 3D modelDrag to turn

In 3D

Look around the L6-100

Technical data

Technical data L6-100

Only this model's values, from the EMEA 2026 catalogue table.

L6-100 · Technical data
Cabinet
Nominal capacity69 kWh
Max. modules per cabinet12
Rated output power (discharge)60 kW
Rated output voltage (discharge)240 / ±240 / 480 V DC (three output systems)
Rated input voltage (charge)265 / ±265 / 530 V DC
Cell charge currentmax. 40 A, default 20 A
Discharge overload125–135%: 1 min · 135–150%: 30 s · > 150%: 500 ms
Current unbalance (module / cabinet)≤ 3%
Max. cabinets in parallel15
SOC · SOHmodule SOC accuracy ≥ 95% · SOH estimate accuracy ≥ 90%
Functionsdischarge SOC balance, battery cold start, self-start after power recovery, EPO, module-level fire control, cell insulation detection
Protectionover-temperature, over-current, short circuit, battery over- and under-voltage, low SOC
Module
Capacity · cell discharge rate100 Ah · 1C
Rated voltage · energy57.6 V · 5.76 kWh
Cell cycle life5,000 cycles at 50% depth of discharge
DC/DC output per module5 kW
Size (W × D × H)440 × 665 × 132 mm
Weight52 ± 1 kg
General
CommunicationTCP/IP, RS485 (CAN reserved)
Display10-inch touch screen (master cabinet) · indicators (slave cabinet)
Operating · storage temperature0 … +40 °C · −10 … +45 °C
Humidity · altitude5–95% non-condensing · < 4000 m, derating above 2000 m (IEC 62040-3)
Noise · protection< 65 dB · IP20 · battery-side overvoltage level 2
Cabinet size (W × D × H)600 × 850 × 2000 mm
Weight with full modules810 ± 24 kg
L6-100 · Models
ItemL6-100
Module capacity100 Ah
Cell discharge rate1C
Modules per cabinet12
Energy per cabinet69 kWh
Rated power per cabinet60 kW
Typical backup1 / 2 / 4 h

Cabinet energy and other cabinet and system data from the L6 user manual; module voltage, energy and DC/DC power from AEC lithium documentation. Specifications are subject to change without notice.

More technical detailsrange tables, ordering codes

Planning data

L6 Lithium range tables

1, 2 and 4 hours

Cabinets and modules for each UPS power (cabinets · modules), from the L6 sizing table (2026): new modules, 95% battery and inverter efficiency, the 10% reserve included, never fewer modules than carry the UPS rating.

L6-100 · 1, 2 and 4 hours
UPS kW1 h2 h4 h
≤ 61 · 21 · 31 · 6
≤ 101 · 31 · 51 · 9
≤ 151 · 41 · 72 · 13
≤ 201 · 51 · 92 · 17
≤ 401 · 92 · 173 · 34

Ordering codes

Ordering codes L6-100

Ordering codes L6-100
CodeDescription
L6-100 cabinetCabinet for up to 12 × 100 Ah modules, master or slave. Code on request.
Modules40 Ah · 50 Ah · 100 Ah lithium modules, hot-swappable. Code on request.
L6-C-2000 · L6-C-4000Combiner cabinet: L6-C-2000 (up to 4 cabinets) · L6-C-4000 (up to 8 cabinets). Code on request.
AccessoriesNetworking device · blank panels · in-row rear frame. Code on request.

Questions

Questions about the L6-100

How many L6-100 modules for 2 hours at 10 kW?

Five modules in one cabinet, from the L6 sizing table (10 kW: 3 modules for 1 h, 5 for 2 h, 9 for 4 h, the 10% reserve included). AEC sizes every project.

Why is the L6-100 cabinet rated only 60 kW?

Each 100 Ah module delivers 5 kW through its DC/DC converter and the cabinet holds twelve: 60 kW. The 40 / 50 Ah modules deliver 10 kW each, twenty per cabinet, for 200 kW, but store less energy per module.

How big is the AEC L6-100 and how much does it weigh?

The AEC L6-100 measures 600 × 850 × 2000 mm; weight: 810 ± 24 kg with 12 modules (EMEA 2026 catalogue).

Talk to an AEC engineer

Tell us the load, the supply and the backup time you need for the AEC L6-100: we answer with the model and the batteries that fit. AEC International sells through distributors in about 80 countries and an agency in every Italian region: ask AEC which one serves your area.